Falló el Solenoide o la Válvula Expansión ?

Поділитися
Вставка
  • Опубліковано 27 лис 2024

КОМЕНТАРІ • 99

  • @pabloolmedo-zb6ly
    @pabloolmedo-zb6ly 9 місяців тому +2

    Sos un groso Derrick!!!! Capo total!!! Gracias por compartir tu conocimiento!!!!

  • @fernandoarielcano4210
    @fernandoarielcano4210 2 місяці тому

    Hace poco empeze a ver tus videos.. la verdad que tus aportes son geniales.. ayudas muchísimo.. muchas gracias por compartir tus experiencia.

  • @luisdiaz5818
    @luisdiaz5818 16 днів тому +1

    Buenas. No vi que Funcione el forzador del condensador. Tendrá algún sistema de presostato que lo active o sensor por temperatura por qué esto modificaría bastante el comportamiento del funcionamiento e incluso otro parámetro a tener en cuenta es la limpieza del condensador gracias muy útil sus videos.

  • @brattbautistaoscco3229
    @brattbautistaoscco3229 11 місяців тому

    un maestro enserio
    perfecta enseñansa en el campo mucha gracias tu experiencia nos sirve a todos gracias por darnos de tu tiempo y tu sabiduria

  • @DanielFernandez-fb4sb
    @DanielFernandez-fb4sb 2 роки тому +8

    Saludos desde uruguay,siempre que podemos vemos tus experiencias para aprender,seria bueno tener un profesor como vos para acá, gracia

  • @jesusquintero2514
    @jesusquintero2514 2 роки тому +1

    Nos vemos en el próximo capítulo jajaja! Éstos equipos son un cuento de nunca acabar pero eso es bueno para nosotros xq así tenemos trabajo y cada vez aprendemos algo nuevo! Saludos desde Ecuador-Venezuela!!!

  • @guillemartinez8247
    @guillemartinez8247 Рік тому

    Tus videos son excelentes,te hace falta una recuperadora de gases para estos trabajos ya que el refrigerante esta muy caro;podes recuperar en un envase todo el refrigerante del sistema podes trabajar tranquilamente.
    Tu método de trabajo es sobre la marcha donde tu diagnóstico es muy certero se aprende un montón con tus videos y se agradece el aporte.Saludos

  • @joseluisdelacruz3210
    @joseluisdelacruz3210 Рік тому

    Buenos días bendiciones para todos muy bueno el video excelente trabajo uste es un maestro

  • @manueldiez2929
    @manueldiez2929 2 роки тому +1

    que grande Derrick !! te izo renegar el acmar !!😵 a mí tmb me pasó con una válvula con el bulbo cortado se cerraba y no entendía ni @ !! hasta que me di cuenta pasa que esas fayas no son comunes por eso es bueno lo que ases de repasar los problemas para no olvidar !!! saludos colega !!! si tenés paste algún vídeo de cómo es las reparaciones en usa !! gracias

  • @enzitoo69
    @enzitoo69 2 роки тому +3

    Excelente video Derrick, gracias por compartir tus experiencias se agradece! Sigo esperando que algún día hagas otro vídeo explicativo, como fue el de válvulas de expansión pero sobre sobrecalentamiento y subenfriamiento un abrazo!

  • @ricardoconil1543
    @ricardoconil1543 2 роки тому +1

    Gracias .Derrick , muy bueno gracias x compartir tus conocimientos , saludos desde monte caseros corrientes

  • @carlospalacios3420
    @carlospalacios3420 2 роки тому

    Excelente explicasión y un buen trabajo amigo Dios te bendiga por tus enseñanzas

  • @federicovarela1038
    @federicovarela1038 2 роки тому +1

    Muy buenos tus videos Derrick, felicitaciones y seguí trayendo tus Derrickaventuras

  • @ottoa.menendez171
    @ottoa.menendez171 Рік тому

    Excelentes videos aprende mucho de todo, muchísimas gracias

  • @waltherherrera67
    @waltherherrera67 2 роки тому

    Excelente adelante y éxitos dios te guarde y bendiga

  • @juliosan2177
    @juliosan2177 2 роки тому +1

    Muy bien Derrick , otro cliente satisfecho

    • @andrewmartinez8459
      @andrewmartinez8459 3 місяці тому

      Ami personalmente me volvió loco un equipo , no abría la termostatica o válvula de expansión, también tenía falla en el selenoide de líquido ingreso a la válvula de expansión, y problema resuelto.

  • @willyfrias7330
    @willyfrias7330 2 роки тому +1

    Buen video instructivo derrick para aprender algo más 👍👍👍

  • @Joseaguilar-pt4iq
    @Joseaguilar-pt4iq 8 місяців тому +1

    ERES CHINGON PERO SOLO TE CONFUNDES!!

  • @victorangel9999
    @victorangel9999 2 місяці тому

    Gracias por compartir Derrick ..

  • @walteralvarez8496
    @walteralvarez8496 2 роки тому +2

    Hola Derrick ,como siempre dando clases y bien claras, asta el próximo video colega ,que sigas bien!!

  • @alvaropedrozo6117
    @alvaropedrozo6117 2 роки тому

    desdes colombia gracias amigo aprendi lo agradezco mucho por recordarme este chicharron

  • @tecnifriotequendama9452
    @tecnifriotequendama9452 2 роки тому

    Muy buenos el video gracias 🙂 Derrick saludos desde Colombia 👍

  • @dragonrojo1045
    @dragonrojo1045 2 роки тому

    Bien Derrick, siempre se aprende algo

  • @pablopescetti5136
    @pablopescetti5136 Рік тому

    Q buena explicacion deloq se leiso al eqipo y su problema...

  • @cesarblanco7955
    @cesarblanco7955 2 роки тому +1

    Que bien cuidas la herramienta, parece recién estrenada.
    Que importante tener mirilla en la línea de líquido y en buenas condiciones. Sino esta avería muy difícil de ver.
    ¿Porque no está instalado el tubo compensador de presión.?

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому

      Y maso menos intento de mantenerlas limpias. Tengo que hacer una limpieza general de mis herramientas pronto. El VET original no tenia opcion de compensador. Estos evaporadores son grandes y lo deberia tener para compensar la caida de presion a la salida del evaporador

    • @luisvillasmil5496
      @luisvillasmil5496 2 роки тому

      @@derrickenbuenosaires amigo Derrick una pregunta, qué sucede si a un equipo de congelación de 3hp le coloco una válvula de expansión de 3hp ? Trabaja bien, o hay q colocar una más pequeña? Y cual seria la correcta? Saludos.

  • @joselm653
    @joselm653 2 роки тому

    Perfecto amigo como siempre! Amaizing!!

  • @wolgfangruidiaz2782
    @wolgfangruidiaz2782 Рік тому

    Derrick saludos yo acostumbro cuando voy a recuperar una carga cierro el el tubo recibidor enciendo la unidad con mi presostato puentiado. Y antes de que llegue bacio .apago la unidad y cierro la linea de liquido .

  • @monguelo
    @monguelo 2 роки тому +1

    Buenas Derrick, gracias por tus conocimientos, ayudan mucho. Por qué pasa eso en las válvulas de expansión? Donde trabajo tengo una deshumectadora y cada año o a veces a los pocos meses toca cambiar la válvula de expansión. La marca que le pongo es danfoss. Los compresores están 24h en funcionamiento todos los días. Podría ser por estar tanto tiempo en funcionamiento? un saludo y gracias!

  • @fabianesparza6445
    @fabianesparza6445 2 роки тому

    Saludos desde México como le puedo hacer un cambio de aceite a a una máquina igual no le encuentro el tornillo de dernado

  • @SergioRaulTañoLazo
    @SergioRaulTañoLazo Рік тому

    Amigo Derrick,soy un seguidor de tus videos ,que para mi son " muy didácticos.Me gustaria poder hacerte consultas.Un saludo desde Cuba.

  • @VictorLopez-qv1fv
    @VictorLopez-qv1fv Рік тому

    Saludos camaradad #1 chingón carnalito.

  • @paracutirimi
    @paracutirimi 2 роки тому +1

    Buen trabajo

  • @escobar2021
    @escobar2021 2 роки тому

    hola saludos desde españa

  • @pelatitorial1054
    @pelatitorial1054 2 роки тому +2

    Que tal Derrick, pudiste ver la tobera y filtro de la VET? Para saber si la restricción era por falla, suciedad o humedad dentro del sistema... Lastima que no pudiste cambiar el filtro y la solenoide... buen laburo, saludos

  • @carloscolina2638
    @carloscolina2638 2 роки тому +2

    Saludos amigo.!! Disculpa mi ignorancia y se q no viene con el tema pero. Tengo un compresor q trabajaba con r12 pero en vista q está descontinuado el refrigerante r12 le cambié el aceite para r134a y le hice una buena limpieza a las tuberías. Fui a comprar una válvula d expansión para r134a pero no había la necesaria para 1 1/2 T. M ofrecieron una válvula para r12 y m indicaron q sirve para refrigerante r134a.! Mi pregunta es esto posible?? Sirve o no? Lo has hecho? Gracias x tu ayuda d ante mano.!

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому +2

      Hola Carlos, si te va funcionar perfectamente bien la valvula. Cuando reemplazo r12 mayormente utilizo 437A y compro una valvula de 134A. Son todos refrigerantes de baja presion que se pueden intercambiador sin problema despues que hallas cambiado el aceite a POE. Sigue adelante amigo sin preocupacion

  • @ernestovaldez495
    @ernestovaldez495 2 роки тому +1

    Primer comentario , siempre aprendiendo del maestro !!!

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому +1

      Gracias Ernesto, un abrazo !

    • @ernestovaldez495
      @ernestovaldez495 2 роки тому

      @@derrickenbuenosaires eres un capo, no me pierdo tus videos.. excelente contenido. Gracias por responder!

  • @joseluisgonzalezlopez9696
    @joseluisgonzalezlopez9696 2 роки тому

    exelente video y trabajo

  • @sterlingarcher46
    @sterlingarcher46 2 роки тому +2

    Primero quiero decir me disculpa para hablar inglés.
    Couple questions came to my head Derrick :
    Do you need copper flare washers in between the flare nuts and the male flare fitting on the Txv , and if you do but don't have them available then what can you do ? Nylog ? Loctite ?
    Do clients where you're located accept that you'd recover the charge and replace the solenoid , dryer and Txv at once , or do they only accept the bare bone minimum .
    And last , do you even have recovery tanks and supply houses take the freon back and recycle it , or is it just old school no recovery ? ( asking cause I know places where there isn't even logistics in place to recover freon even if you wanted to )
    Muchas gracias y cheers mate 👍.

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому +1

      Hey sterling, no problem talking in english 👍 I would say that proper installation would be to use copper or some type of nylon flare gasket on the mating surface but honestly down here I have no idea where one would even buy such an accessory since it's not commonly found. Brass against brass does seal though since I've installed the reducer before in a similar situation. I used some errecom "seal up" thread sealant as well, I prefer nylog but no nylog down here.
      As for recovery goes, the refrigeration supply houses don't accept recovered refrigerant to be recycled. That's why reclaiming here is practically non existent. The customer almost always has to replace the charge if a part fails where the charge can't be pumped down. There are recovery cylinders here but they are mostly owned by supermarket chains and large manufacturers where they may have 100s of kgs of refrigerant or thousands of lbs.
      We mostly do the minimum to get the equipment running. (at least with my clients) I would've liked to change the solenoid here because I wasn't sure where the restriction was but I'm sure the customer was grateful that I was able to diagnose correctly and not change something that did not fail even though it is old.
      The drier I couldn't change because the king valve wouldn't shut properly so he got to keep his older drier lol

    • @sterlingarcher46
      @sterlingarcher46 2 роки тому +1

      @@derrickenbuenosaires thank you very much indeed. Yeah so it's pretty much the exact same thing as the other places I was talking about . It appears that only the "developped" countries have the reclaiming process in place , it's a shame because there would be a whole lot of business to be done around it .

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому +1

      @@sterlingarcher46 What I would really like to see down here is some kind of certification to buy and handle refrigerants. Anyone underage, untrained, whoever can walk into a supply house and buy refrigerant. It takes away jobs from the true technicians and it makes us look bad because some random will do a job for half the price, do it wrong, collect money and disappear. Then the customers become weary of the HVAC techs down here. There's no respect for the residential guys. I'm glad I don't do residential regardless lol

    • @sterlingarcher46
      @sterlingarcher46 2 роки тому

      @@derrickenbuenosaires Ah man ! 🤦‍♂️they've put that in place over here in EU it's called the F-Gas license .
      Without it you can't handle refrigerant, and there's a second category license that you need to buy refrigerant and then you have to annually report what and how much you've bought , used , reclaimed , recycled and so on and so forth .
      But then again it's only been put in place and finalised in 09 or 2010 , so not so long ago innit .

  • @carlosdariomartinez1294
    @carlosdariomartinez1294 2 роки тому +1

    Hola amigo Derrick! Saludos de Santa Fe. Gracias por tus vídeos me sacan un montón de dudas continuamente! Quería preguntarte dónde puedo conseguir el imán para destrabar las solenoides, cómo el que vos usas, acá en el país. Gracias!

  • @eduardpalma6781
    @eduardpalma6781 Рік тому

    Hace poco me pasó algo parecido la unidad condensadora itarcon no apagan por Pug dawn el control apaga el equipo y tiene presostatos de alta y baja tipo pila y apagan por estos controles si se baja más la presión o se sube el presostato se demora.en reponer y hay que activar las selenoides con el iman

  • @carlosjavierariaspena6766
    @carlosjavierariaspena6766 Місяць тому

    Q número de orificio le colocó a la válvula?

  • @yoberrojas5815
    @yoberrojas5815 8 місяців тому

    Exelente vídeo

  • @joseortoneda1649
    @joseortoneda1649 2 роки тому +1

    Gracias, gracias

  • @educastillo3805
    @educastillo3805 Рік тому +1

    excente

  • @anibalrivera7529
    @anibalrivera7529 3 місяці тому

    Porque nunca prendio el fan del condensador? Gracias

  • @IvanRRubio-cx5zz
    @IvanRRubio-cx5zz Рік тому

    Hola Derrick, gusto saludarte, soy Iván Rubio de Honduras, te sigo desde ya hace más de un año y he aprendido mucho con tus videos y tutoriales.
    Que refrigerante me recomiendas para una unidad condensadora de un cuarto frío que actualmente utiliza R-502 ?

  • @ivanhhss
    @ivanhhss Рік тому

    Estimado ese equalizador externo debe ir conectado porque sino no trabajará la válvula correctamente

  • @kikebiker
    @kikebiker Рік тому

    Super incómodo ese igualador externo o compensador. Es parte de cambiar una valvula

  • @Luis-2124
    @Luis-2124 Рік тому

    después del solenoide se podría poner otro filtro

  • @carlosandrade7091
    @carlosandrade7091 2 роки тому +3

    TE extrañabamos derrick, el profesor derrick

  • @manuelbenito2186
    @manuelbenito2186 Рік тому

    Si metes un iman en la solenoide y luego cuando lo tienes la aspiración a 0 bares cierras la lleve de el compresor lo más seguro es que no tengas el problema de tirar tanto gas

  • @roceloi
    @roceloi 2 роки тому +2

    11:46 cables pegando en las resistencias de desescarche esperando ha hacer corto!

  • @Oscar-zt2di
    @Oscar-zt2di Рік тому

    La válvula selenoide probar en ohmios y la válvula de expansión cambiar la tobera ???

  • @josemateo5430
    @josemateo5430 Рік тому

    Excelente

  • @cristiangonzalez1939
    @cristiangonzalez1939 9 місяців тому

    Que pasa si un motor compresor de frío por alrta Sele echar aceite que con secuessia trae

  • @elektrotecnico
    @elektrotecnico Рік тому +1

    hola como estas? quisiera saber como se llama el instrumento que utilizar para comprobar la bobina del selenoide en el minuto 7:12 gracias

    • @derrickenbuenosaires
      @derrickenbuenosaires  Рік тому +1

      "Solenoid checker" o "tester". No he encontrado alguien que lo vende aca en el mercado pero lo puedes conseguir por amazon

    • @elektrotecnico
      @elektrotecnico Рік тому

      @@derrickenbuenosairesgracias, muy amable Derrick, saludos !!

  • @carolineustaquiocastro8756
    @carolineustaquiocastro8756 Рік тому

    como saber el orificio calibrado que lleva la unidad

  • @RobertojavierMeichtri-ig5vt

    Solo un cosejo tendrias que haver anulado el presostato para travajar con el compresor en marcha para guardar el refrijerante

  • @alejandrocaller4477
    @alejandrocaller4477 Рік тому

    Esa falla se produce por la saturación del filtro, afloja la tuerca y sabrás si pasa o no.

  • @leoderosario9150
    @leoderosario9150 2 роки тому +1

    Muy bueno Saludos

  • @jndenisbergeaud3200
    @jndenisbergeaud3200 2 роки тому +1

    Hello my friend how are you doing? From New Orleans

  • @raulhoraciolecce4926
    @raulhoraciolecce4926 2 роки тому

    Hola derrick! Una pregunta de curioso, tú llevas una ficha de servicio por equipo intervenido por ti?

  • @cristiancarrondi2460
    @cristiancarrondi2460 2 роки тому

    Soy de Rosario Argentina, cuando veo un equipo de esos se lo hago tirar a la basura

  • @jndenisbergeaud3200
    @jndenisbergeaud3200 2 роки тому +1

    Que sucede tengo una clienta que me llamo por carro que no enfría correcto ,yo chequeó todas casas están bien, lo que yo viendo fué el ventilador qué tarda 5 a 6 minutos pará arranca ,puedes me dar un idea que sucede?

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому +1

      Es posible que en tu caso tienes un ventilador que cicla por presostato. Eso lo puedes comprobar viendo donde enciende y corta el ventilador con el manifold conectado al lado de alta.
      Igual deberia encenderse enseguida si hace calor, si no es porque esta muy baja con carga de refrigerante.
      Si el ventilador tiene una plaqueta puede ser la logica tambien pero es raro que tarde 5 mins para encenderlo. Yo iria a ver si tiene presostato para el ventilador

    • @jndenisbergeaud3200
      @jndenisbergeaud3200 2 роки тому

      Gracias mi amigo

  • @sergioflores7651
    @sergioflores7651 2 роки тому

    Hola dereick necesitas un ayudante? Quisiera aprender más... soy d bs as.. tengo herramientas y vehículo.. j😁

  • @mariogustavomoreno6157
    @mariogustavomoreno6157 2 роки тому

    Maestro !!!

  • @Walteracon
    @Walteracon 2 роки тому +1

    mira esos cables de la resistencia re quemados haciendo contacto

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому +1

      Hola Walter, no me di cuenta hasta que empeze a editar el video, parece que en 13:04 los movi de donde tocaban 😂😂

  • @fredysantonioospina5932
    @fredysantonioospina5932 7 місяців тому

    Yo cambiaría el filtro y válvula solenoide

  • @electronicaconrodiiy9447
    @electronicaconrodiiy9447 4 місяці тому

    El que tengo se apaga después de un rato según está bien ya revisamos todo de repente se apaga

  • @victoravalosjavier3826
    @victoravalosjavier3826 2 роки тому

    Muy bueno el vídeo pero veo que nunca arrancó los ventiladores de la condensadores

    • @derrickenbuenosaires
      @derrickenbuenosaires  2 роки тому

      Gracias Victor, ese equipo es condensado por agua. Cuando empieza verano devuelta en esos dias calidos puede llegar a ciclar devuelta. Saludos !

    • @victoravalosjavier3826
      @victoravalosjavier3826 2 роки тому

      @@derrickenbuenosaires ok gracias por sus explicaciones sos el único que sube vídeos de equipo grande. Amii me encanta la refrigeración estudié me recibí y en mismo tiempo libre hago algunos trabajo. Tengo empleo pero mi sueño sería vivir de este ofició qué es tan lindo la refrigeración .Tengo trabajo fijo en una empresa. Pero algún día me gustaría vivir de este ofició qué es tan lindo la refrigeración le mandó un abrazo grande esperó que tenga mucho éxito en todo. Yo quisiera algún día vivir de este ofició y renunciar a mi trabajo.

  • @zottagustavo
    @zottagustavo 2 роки тому +1

    Maldita llave, siempre hay alguna en mal estado...
    Si no, era VET, filtro, y a cobrar!
    😉
    Chinwewencha, tenés un magnetómetro!

    • @arrionda1
      @arrionda1 2 роки тому +2

      Puedes tambien usar una brujula comun

    • @fabiangamarra1687
      @fabiangamarra1687 2 роки тому +2

      El telefono también lo podés usar

  • @edgarescalona7590
    @edgarescalona7590 Рік тому +1

    Que orifioc lleva esa unidada

  • @JoséChauran-t7c
    @JoséChauran-t7c 4 місяці тому

    .todp fimo