THE DINING AC IS NOT WORKING

Поділитися
Вставка
  • Опубліковано 8 лип 2020
  • This was a call on their dining room ac not working, it had a tripped breaker and I found an interesting issue.
    HVACR VIDEOS NEW MERCH WEBSITE - www.hvacrvideos.com
    Please consider supporting my channel by
    Becoming a Patreon member - Patreon / hvacrvideos
    Becoming a UA-cam channel member / @hvacrvideos
    By purchasing tools via my affiliate links below at TRUTECHTOOLS.COM and use the offer code BIGPICTURE to save 8% on your total purchase (exclusions apply)
    Visiting my website and purchasing merch www.hvacrvideos.com
    TOOL LINKS
    Fieldpiece wireless scale www.trutechtools.com/SRS3?aff...
    Fieldpiece SC480 meter www.trutechtools.com/Fieldpie...
    Fieldpiece JobLink wireless probes www.trutechtools.com/JL3KH6?a...
    Sman 480 digital manifold www.trutechtools.com/Fieldpie...
    Fieldpiece MR45 recovery machine www.trutechtools.com/Fieldpie...
    Fieldpiece VP85 vacuum pump- www.trutechtools.com/Fieldpie...
    Wireless probes charging tee - www.trutechtools.com/AVT45?af...
    Samsung 8" Tablet amzn.to/3bW8QJ6
    OtterBox case amzn.to/2wgd0M5
    Manfrotto tripod - amzn.to/3bPoupz
    Jobi phone mount- amzn.to/2Yh2EY0
    Magnetic Umbrella - www.trutechtools.com/Supco-Ma...
    Bomber safety glasses - amzn.to/2yD6sbs
    Bomber safety sunglasses- amzn.to/2zmhdPp
    BlueVac Pro micron gauge - www.trutechtools.com/BluvacPr...
    TruBlu pro evacuation kit - www.trutechtools.com/Accutool...
    Accutools core removal tools - www.trutechtools.com/Accutool...
    Nitrogen purging regulator - www.trutechtools.com/Western-...
    Nylog blue - www.trutechtools.com/RT201B?a...
    Flir One Pro thermal imaging camera www.trutechtools.com/FLIR-One...
    Check out my new UA-cam channel- / @hvacrtools
    For Optimizing my videos I use Tube Buddy
    www.tubebuddy.com/HVACRVIDEOS
    Please consider subscribing to my channel and turning on the notification bell by clicking this link goo.gl/H4Nvob
    Social Media
    Facebook / hvacr-videos. .
    Instagram / hvacrvideos
    For any inquiries please contact me at chris@hvacrvideos.com
    Mailing Address
    HVACR VIDEOS
    12523 LIMONITE AVE.
    #440 - 184
    MIRA LOMA, CA. 91752

КОМЕНТАРІ • 475

  • @russellhltn1396
    @russellhltn1396 4 роки тому +13

    As an electronics tech, something that caught my eye was that line of dirt on the bottom of the main board. Dirt can become conductive, especially when the humidity rises and then you'll get all kinds of weird problems. Just part of how I roll when it comes to big picture, inspecting, and doing it right. I use an acid brush that I've cut the bristles to half length to stiffen them. That and a vacuum cleaner.

  • @Samsquanch96
    @Samsquanch96 4 роки тому +17

    I know absolutely nothing about HVAC. I have no idea why UA-cam recommended this channel but I'm glad they did. I have no idea why this is so entertaining. I think it's the way you explain things so well. I'm subbing.

  • @RichGT350r
    @RichGT350r 4 роки тому +55

    I Stand Behind My Work!!! ..... Far Behind... So if it blows up, I Don’t Get Hurt! Thanks for sharing! 👍

  • @feelingtardy
    @feelingtardy 4 роки тому +9

    gotta love tech support. you can ask the same question to 3 different people and get 3 different answers sometimes

  • @rickharris4258
    @rickharris4258 3 роки тому +7

    Super videos, 50 years in our trade but still learning. I will never forget my instructor so many years ago saying for the first five years you know nothing. Keep safe.

  • @FerroequinologistofColorado
    @FerroequinologistofColorado 4 роки тому +98

    The placement of that fire sprinkler by the ladder is just an accident waiting to happen. Great video as always.

    • @lwilton
      @lwilton 4 роки тому +7

      And I bet it is mandated by the local fire codes. A sprinkler in the top of a chimney to keep it cool.

    • @mman454
      @mman454 4 роки тому +5

      l wilton I would’ve expected to see that in his other videos where he shows the roof hatch then.

    • @kittyztigerz
      @kittyztigerz 4 роки тому +1

      i have seen one guy got his hat caught in it n set off sprinker ROFL
      easy way get away with it put big cup with duck tape on it that way doesnt get caught on something when ya coming up there

    • @alanr585
      @alanr585 4 роки тому

      Haha, yes, love it! lol each time I saw it in the video just thinking of it and it being caught on video too. I'm glad I didn't choose your trade when I left school but I love watching you doing such an important job in often horrible conditions. Respect to you.

    • @graemebardsley-smith4394
      @graemebardsley-smith4394 4 роки тому +2

      Almost certainly mandated by code - would be here in Aus. So in reality the failure is on the part of the architect providing insufficient space for access (fairly normal from experience) or failing to provide other suitable access -,eg external. That of course brings in a much bigger picture and that has always been the issue with facilities design for engineering services. In the end, it’s the service tech. wearing the problem. I think a cage over the outside of the head would avoid triggering the head but might reduce available space too much. Another two inches on the access and much better!

  • @arthouston7361
    @arthouston7361 3 роки тому +6

    As soon as they came out with the first Prodigy, I learned to replace every controller with a new display as well.

  • @alexs3030
    @alexs3030 3 роки тому +5

    God bless you for working at so many restaurants, I imagine it’s like pulling teeth at times convincing people they actually need things repaired/replaced

  • @sebastiannielsen
    @sebastiannielsen 4 роки тому +44

    suggestion: When filming the prodigy boards - try using a slightly longer shutter time (in most phone models if you use a phone to film - have a "advanced" or "pro" mode to set shutter). You might need to reduce apeture tough. If your phone or camera allows saving profile, try getting a good profile for just prodigy boards, and then save it as 2 profiles, one for "normal" filmning and one for "prodigy". Play around with the camera settings - should be pretty easy if you have a prodigy board at home, until you get a nice view.

    • @chakflying1
      @chakflying1 4 роки тому +4

      Usually wouldn't work as the outdoor sun is too bright for a slower shutter speed. We use ND filters for that, but finding one for phone cameras might be difficult. An easier way might be to just put sunglasses / welding goggles in front of the camera and let the auto exposure adjust.

  • @SalDarkSeed
    @SalDarkSeed 4 роки тому +2

    Anyone else just enjoy watching him fix stuff?

  • @lwilton
    @lwilton 4 роки тому +42

    Pretty fair guess about what happened to that unit:
    Looking at the VFD innards, it is immediately obvious that two of the main filter caps have failed. Others may have also failed, but those two probably were enough. They were probably bad enough that they were supplying AC to the VFD logic when it should have been DC.
    This probably wouldn't have damaged the chips, but it trashed their operation, and they got completely confused. Somewhere in their confusion, they turned on two or maybe all three phases at once, shorting the line across the power MOSFETs in the driver part of the board.
    The result was a lot of black greasy smoke and shrapnel all over the inside of the VFD. A lot of nice greasy conductive smoke, probably along with a nice hot arc for a very short time. Probably the arc migrated from the power MOSFETs into the logic chips. From there it fed back along the control lines and momentarily put 208 onto the logic of the main control board.
    The VFD control may be partially isolated, but not enough so. The short pulse of HV didn't completely smoke the control, but it was enough to confuse the heck out of it, and possibly fry some logic as well as wiping out the flash/EEPROM memory in the unit.
    You are probably right that having that VFD in a more climate controlled room would have preserved it. I suspect if you put a recording thermometer in the VFD case you would find that it is way over the max continuous operating temperature for a good part of the day in summer.
    I'm not an air conditioning guy, so I might seriously consider going to Lowes and getting a 5000 BTU room AC and and ducting it into that electrical area of the package unit. Might be real cheap insurance. (And I'm sure you can think of some more reasonable idea.)

    • @zjeepgozweeln
      @zjeepgozweeln 4 роки тому +23

      The better designed units have a hole to leak a small amount of conditioned air through the controls compartment during operation.

    • @joelacosta2082
      @joelacosta2082 4 роки тому +7

      @@zjeepgozweeln a little suggestion put the vfd in the blower compartment it's colder

    • @Magiobiwan
      @Magiobiwan 4 роки тому +7

      Joel Acosta then you run into Condensation issues with the VFD.

    • @lwilton
      @lwilton 4 роки тому +2

      @mark robertson I'm not sure if that is a deliberately snarky comment for reasons I don't understand, or if maybe the comment means something completely different that I don't understand. What does describing a probable VFD failure cause have to getting venereal disease?

  • @analogmoz
    @analogmoz 4 роки тому +8

    I'm going to pay to put up a bunch of upside-down billboards in Chris' service area and watch him slowly slip into madness.

  • @thephantom1492
    @thephantom1492 4 роки тому +7

    With a proving circuit, you now have 3 possible states:
    - Open: wire is broken
    - Shorted: Wire melted or detector tripped.
    - Supervisory state: All is fine.
    How it often work is with a simple resistor. Basically the resistor 'soft short' the wiring at the end of it. If the panel see the resistor, then the wiring is intact. Open then something is broken, and sorted it mean it tripped or the wire shorted/melted.
    Some system will use two resitors, one end of line (the first one) plus another series one with the detector. Now you can have 4 states: open, close, EOL resistor or the tripped resistor. Those can therefore detect between the shorted or tripped condition. Those can help to avoid some nuisance alarm due to a nail in the wiring.

  • @michaelsassenus3154
    @michaelsassenus3154 3 роки тому +3

    “stand back man” lol, made me feel like I was there on the roof with you,

  • @matthewsykes4814
    @matthewsykes4814 4 роки тому +5

    It's the worst thing to come into a fault half way through the fix, stuff's been removed and the bolts have wandered off ..... great to see just that little bit of detail. Makes life so much easier, especially when you've bolts of different lengths.... that's always fun. I've the same issues at work, you can't fix everything first time. Sometimes you get lucky, most times you open up a whole can of worms....... it's why I like my job. It's boring for the most part but there are moments of happiness when I'm sorting problems out.

  • @PeterParker-tb7ce
    @PeterParker-tb7ce 4 роки тому +31

    Looked up Spec on that VFD (FR-D720-100-NA). It looks border line in it's sizing. It's rated at 10 A up to 122°F. It should have over temp protection. But from all that dirt I see from the cooling fan means the heat sink is most likely dirty. Thus reducing it's cooling capacity. If this is an common issue look at replacing them with the FR-D720-165-NA model. It's rated for 16.5 A.

    • @lwilton
      @lwilton 4 роки тому +15

      It's also probably running closer to 150 F ambient mounted in that unit on the top of a roof in So Cal. You can see two of the main filter caps have died, and this was quite likely from the prolonged high temperature soaking. I strongly suspect those caps failing was the root cause of the VFD failure, not a (stupidly) borderline current rating.

    • @stephenhunter70
      @stephenhunter70 4 роки тому +7

      @@lwilton Not to mention dirty supply from all the contractors and motors etc in the various AC's etc/ But you are right the caps are not going to like sitting out there in the hot sun all day at 150f/65.55556c. That's going to be a bit hot even for the micro controller inside of the VFD too. I'd go as far as 50% de-rate them, go find one that will supply the required amps after 50% de-rating it.

    • @443DM
      @443DM 4 роки тому

      @@lwilton Seems like a business to re-solder new caps.

  • @blazeeisner9620
    @blazeeisner9620 4 роки тому +10

    Hey Chris. Great job and video again. The haters sometimes criticize you for using tech support. But we mechanics don’t know each and every machine. The folks with tech support many times make us look like heroes. When I was in the field; I loved Lennox units. At Emcor when I was there, we took care of a lot of National accounts. Many times it was a hassle to deal with them but bottom line; they put food on my table. Most of the Target stores that I serviced in San Diego county had those Lennox boxcars. I hope that your business is doing excellent. Stay safe and careful out there. Have a great Thursday evening with your family. God bless.

  • @dashcamandy2242
    @dashcamandy2242 4 роки тому +17

    That opening clip... I cringed so hard. Brought back memories of working in a certain home improvement chain's local distribution center. A sprinkler head was RIGHT next to the warehouse racks, and there were many than occasions where we had to shut down and evacuate because someone on powered equipment had taken off the head and triggered the fire alarm. I kept suggesting to anyone that would listen that we should install a small cage of rebar around it to protect it from impact, but nobody cares what the fireman's son has to say about the fire alarm system.
    OOOF, those exploded capacitors on the VFD are definitely the cause of the tripped breaker! I wonder if they failed due to high temperatures on the roof? High temps cause the dielectric to breakdown and the caps then basically become shorts. Mitsubishi also had an issue with bad capacitors in some of their cars' ECMs in the '90s because they used a cheaper brand instead of their own parts - they dried out under the harsh temperatures inside a car and failed. As you said, putting the VFDs in a cooler environment will extend their lifespan. Judging by the incredible scorch marks inside the dead VFD, I guarantee some HV arced over to the LV sections, if I had to offer a theory (much simpler, but similar to I wilton's theory) the faulty caps became dead short, high voltage arced to low voltage sections, and from there basically grenaded the daughter board and probably parts of the main board.

  • @pepsicolachao4537
    @pepsicolachao4537 4 роки тому +25

    Remember this place where the main exhaust fan was replaced?

  • @CM-dt1et
    @CM-dt1et 4 роки тому +3

    That's a nice rooftop!

  • @watermanone7567
    @watermanone7567 4 роки тому +30

    Nice job: You can't beat the older style units that have only relays that operate the stages and systems. Sometimes the new tech stuff cost more that it saves. Thanks for the video.

    • @gordonrichardson2972
      @gordonrichardson2972 4 роки тому +11

      Waterman one Watching this video was fascinating, but also a infuriating. Why so complex? KISS...

    • @DocNo27
      @DocNo27 4 роки тому +10

      @@gordonrichardson2972 thank our "environmentalist" buddies. Don't get me wrong - I'm all for conservation. But how about conservation with some common sense that's not completely divorced from reality?

    • @OcRefrig
      @OcRefrig 4 роки тому +2

      @@ItsMrAssholeToYou 👍. Agreed.

    • @russlehman2070
      @russlehman2070 4 роки тому +4

      Yeah. I'm not in the industry, but I have to wonder if that VFD and all the circuitry that controls it is really more economical than a two speed motor controlled by relays and contactors.

    • @hgbugalou
      @hgbugalou 4 роки тому +6

      @Sean That is throwing the baby out with the bathwater. Nothing wrong with using chips and such where it makes sense. It just doesn't make sense to use them for ~5% energy savings while sacrificing ~25% in the reliability.

  • @k.sullivan6303
    @k.sullivan6303 2 роки тому +2

    Nice work Chris. Good job on getting things up and running temporarily with the contactor.

  • @marknaravas318
    @marknaravas318 4 роки тому +1

    Don’t worry about the sprinkler. I’m a truck driver and had a load to an enclosed strip mall that had a height hog 13’6.5”. My truck is 13’6”. The day before they had lowered the sprinklers 2”. I took off 4 sprinkler heads; it looked like a Roman fountain goin off on the top of my trailer. It was quite scenic.
    Not!

  • @jojomorgan8556
    @jojomorgan8556 4 роки тому +3

    Merch is our way of supporting you and advertising your channel while getting something cool in return love the videos keep it up

  • @haydenuk02
    @haydenuk02 4 роки тому +9

    Who in the hell put a sprinkler right in the way of the ladder to the roof excellent work and thanks for the awesome content stay safe and take care

  • @caerusdharken57
    @caerusdharken57 4 роки тому +3

    I've been watching your Videos for the past two weeks now, even though I'm not even remotely connected to HVACR I'm an electrical engineer, but I picked up a fair bit and after reading up on some terms that meant nothing to me like superheat etc. I even start to understand how and why you do things. So you do a pretty good job on explaining and methods. Probably will never put that knowledge to any greater use since the HVACR guy at our company didn't even take me serious as I told him that it sounds like a bearing in the compressor is about to die (compressor died 2 Weeks later, took them 3 months to get a new unit installed, industrial carrier cold water circuit, those roof direct air units are very uncommon in europe) but it never hurts to know things outside of your job, so thanks for providing :)

  • @wwolf771177
    @wwolf771177 4 роки тому +5

    You forgot to flip the contractor cover over. 😂🤣😂

  • @Eddy63
    @Eddy63 4 роки тому +15

    Man , this was a good vid Chris ...Love the little Prayers before start-up ...Lol ... Very bourbon worthy ...

  • @jimgill5706
    @jimgill5706 3 роки тому +2

    That is an insane sprinkler head placement.

  • @FreshRoastCoffeeOhio
    @FreshRoastCoffeeOhio 4 роки тому +6

    i know nothing about hvac at all, but these vids are just very interesting for some reason. keep them coming

  • @rmarkesteijn
    @rmarkesteijn 4 роки тому +1

    Small tip from a hvac tech taken a brush and brush the dust from the circuit boards dust can make a short and with the low control voltage that the board needs can give strange problems VFD went due to bad capacitor nice video again Chris

  • @TheLenaweeTrekker
    @TheLenaweeTrekker 4 роки тому +4

    Thank you, for this video. I have not seen these here in Michigan, yet, but given the energy regulations and the closing of coal fired plants, it's only a matter of time before I have to deal with these VFDs. Thanks to you, and your experience, I will have a leg up. Thank You.

    • @neon-john
      @neon-john 4 роки тому

      Real electrical engineers know how to do multi-speed motors with no electronics. This gratuitous electronic is being put in there simply to generate service calls. True variable speed units like the mini-splits I installed in my retirement cabin are a different matter. Even then the chicoms are running the power transistors at absolute max rating which is why one driver board has already failed.

  • @38911bytefree
    @38911bytefree 4 роки тому +7

    When something blows up like this, probably the lov voltage got shorted to the high voltage side as a result, and tooks with t whatever is connected to it on the LV side. Nice they tear appart as explode, so you it will catch your eye instantly.. Good job man, seeing a pro in his trade has no price.

  • @sherwinalvarez7365
    @sherwinalvarez7365 4 роки тому +5

    Yo Chris i just wanna say thanx for all your hard work and vigilance bringing us these videos. I enjoy watching you making it a little easier for us new guys. ✊🏽

  • @obeythesociety
    @obeythesociety 4 роки тому +1

    “Im not perfect I don’t always get it on the first call...it is what it is..” man I appreciate the realness.

  • @chieft3357
    @chieft3357 4 роки тому +4

    I see taking a picture with your phone of the elect control panel helps to make sure the connectors go back in the proper place?? I hope you have a employee with you so he can learn from what you are doing. You are doing so really good troubleshooting right now. Nothing like hands on training for the troops.

  • @THEMANTR
    @THEMANTR 4 роки тому +3

    You get a like before I watched the whole video. That says so much about me LOVING your videos!

  • @gabe2483
    @gabe2483 4 роки тому +1

    One of the best HVAC UA-cam videos ever made... all your HVACR videos are top notch but this was next level. Nice work Chris thanks for making these.

  • @carlosedwardos
    @carlosedwardos 4 роки тому +3

    Those black electrolytic capacitors in the VFD are toast! - see how puffy they are?

  • @mechanicwarrior20
    @mechanicwarrior20 4 роки тому +2

    It would of been really nice if that RTU came with a VFD Bypass option! That would of saved you a lot of trouble! I am happy that the customer didn't flip out at you! I hate it when you have to go back to the customer multiple times telling them they are more problems then what was previously quoted? But It's part of the HVAC&R Field! Great Video!

  • @uxwbill
    @uxwbill 4 роки тому +5

    Just like the switchmode power supplies to which they're very closely related, the active components in those VFDs have almost no tolerance for errors in their controlling circuits.
    I'm always fearful of those sprinkler heads when pulling network cables and putting up wireless APs, that some absent minded movement is going to trigger a major disaster through the whole building.

  • @johankling9994
    @johankling9994 4 роки тому +30

    Damn, you could've had a real problem if you broke the vial of the sprinkler.

    • @OcRefrig
      @OcRefrig 4 роки тому +11

      At a minimum that sprinkler should have a wire cage around it.

    • @johankling9994
      @johankling9994 4 роки тому +6

      @@OcRefrig that would seem like a smart thing to do.

  • @cityscene121
    @cityscene121 4 роки тому +1

    Whew! The attention it took to follow exactly what you were saying and why was mesmerizing and like running an uphill mile. Exhausted but exhilarating. I felt accomplished by hanging on to the end. Just wonderful hearing your mind work. Great job.

  • @jhp110
    @jhp110 3 роки тому +2

    Great video amazing how complicated these units can get to meet energy consumption requirements. I’m an electrician and what I find odd is the fire alarm supervisory circuit should not be dependent on the units power supply, the supervisory power should come from the fire alarm panel/sub panel and should just monitor the continuity of the alarm wires and the smoke detector it shouldn’t matter if the unit has power or not to cause a supervisory alarm. I think you may have had a surge on the system power side that may have damaged the board maybe that unit was the closest to the surge is why it was the only one effected. Just my two cents, great video and great service skills to get that unit working temporarily.

  • @CHOMAHOMA
    @CHOMAHOMA Рік тому +1

    Good video. I really liked this one and I agree with Russell's comment. I wouldn't know what to charge for a type of work like this when it takes different trips plus replacing very expansive parts. Thank you again for filming this type of work. It is not easy do film and work at the same time.

  • @coffeecoffee5914
    @coffeecoffee5914 4 роки тому +8

    shaming for calling for tech support is as bad as those that throw out the wiring diagrams

  • @Ted_E_Bear
    @Ted_E_Bear 4 роки тому +2

    Great customer service !!

  • @chriscooley906
    @chriscooley906 4 роки тому +2

    Nice video Chris, you covered the entire cooling operation with this call, I would recommend you get a pair of MAGJUMPERS instead of skinning the insulation on the control wires, Thanks for sharing bud !

  • @travishamilton1659
    @travishamilton1659 3 роки тому +2

    Chris you're awesome man! Way to find the problem then find a temporary solution and then come back and fix it totally. Awesome video man keep up the great work

  • @HappilyHomicidalHooligan
    @HappilyHomicidalHooligan 4 роки тому +4

    19:33 And that right there is likely what killed the old VFD...
    It got dirty, overheated and went BANG!
    These things really need to be cleaned regularly, once every 6 months just isn't going to cut it.
    Clean them every 4-6 weeks or you'll likely severely reduce their Lifespan...

  • @jazbell7
    @jazbell7 4 роки тому +25

    The environment for electronics in a unit like that is terrible, comparable to an automobile. High heat, very cold in winter, vibration and lots of dirt. Not to mention lots of big motors being stopped and started, causing power line transients. VFDs are now everywhere, clothes washing machines, garage openers, residential A/C.

    • @mikeydk
      @mikeydk 4 роки тому +5

      Even fridges got VFD's in them now. Pretty cool (no pun intended), I can never hear my fridge running under normal circumstances. Only time I can hear it very low, is if it has been powered off, or a lot of new stuff has been put into it.

    • @m8onethousand
      @m8onethousand 4 роки тому

      On the bright side, the epoxy (?) coating on the new M2 seems thicker which should help a bit.

    • @OrangeRAZ
      @OrangeRAZ 4 роки тому

      Most units have vent holes that keep that compartment warm, some times

    • @fortfun46835
      @fortfun46835 4 роки тому +1

      Drives don't care about cold except maybe condensing water. However, in the heat you need to derate those drives. I would have gone up a larger drive if that was the second one blown. We use a lot of those Mitsubishi drives and I've never seen one fail like that.
      Surprised that if they are only using two speeds they would go through the trouble of a variable output. Just set the two different speeds and use the RH and RM input to select.

    • @443DM
      @443DM 4 роки тому +2

      Stupid to have a VFD at 59hz. It should just bypass at that point, run at 60hz and let the VFD electronics take a rest.

  • @MrHeliorabelo
    @MrHeliorabelo 4 роки тому

    How enjoyable is watching your videos ! I love see people passionate doing their job, motivate us ! Great videos 👏🏻👏🏻👏🏻

  • @kerrydavis2919
    @kerrydavis2919 4 роки тому

    I always get some new knowledge from your videos! A good tech will never stop learning. Thanks for the great video as always.

  • @alexzapata692
    @alexzapata692 4 роки тому

    Great content you explaining the sequence of operations and the idea behind the VFD. Thank you.

  • @daniellocke4172
    @daniellocke4172 3 роки тому +1

    That skyline backdrop is amazing. even with a huge ac in the frame.

  • @elijahtalbot5288
    @elijahtalbot5288 4 роки тому +8

    I agree that is a stupid spot for a sprinkler

  • @boeing747-8
    @boeing747-8 4 роки тому +3

    I'm gonna be honest, I'm only 15 and no one in my family works in HVACR, and i have no idea how i found your channel. I am so glad that i did find your channel, your videos are just so interesting! I hope we could eventually meet in real life!

    • @brandoncherry1651
      @brandoncherry1651 4 роки тому

      I'm 38 it blows my mind...your young though.....he will point you in right direction...

  • @TheWoodman064
    @TheWoodman064 2 роки тому

    I greatly appreciate your humility but you are incredible!

  • @starlite528
    @starlite528 4 роки тому

    Who complains about calling tech support?? I was on the phone with them at least twice a week! Calling tech support is not a sign of weakness or that you don't know what you're doing, but it's always nice to have another brain working with you that specializes in a specific product.

  • @MattTrevett
    @MattTrevett 4 роки тому +2

    I don't know if you (or anyone) will ever be in this situation again, but it looks like the D700 series is able to have a minimum frequency programmed in relatively simply, so instead of reinstalling the contactor while you waited for the board to be ordered, you possibly could have set a minimum frequency for the VFD which could have saved some installation time.

  • @RoboSkyrat
    @RoboSkyrat 4 роки тому +1

    Impact rated/bashable screw drivers are the #1 tool in any tool bag.

  • @2swagdaddy
    @2swagdaddy 4 роки тому +1

    So funny I dealt with a similar situation today and this somehow this came up on my recommended. We had a open trouble on the FACP. The demo guys cut through a thermostat cable and tripped the control transformer fuse. Good documentation here!

  • @joshjones3227
    @joshjones3227 4 роки тому

    Often times when changing dense boards like that, I will write with a fine point sharpie on the flying connector the number of the mating connector on the PCB. Taking a few pictures from different angles is also a big time saver.

  • @thornmountain8129
    @thornmountain8129 3 роки тому +1

    Just waiting for tech support to tell you to change out the whole unit....😂😂😂

  • @godbluffvdgg
    @godbluffvdgg 4 роки тому

    You're the difference between a "Mechanic" and a Swapologist ...Nice to see someone that knows their job and does it well...:)...

  • @Mrcaffinebean
    @Mrcaffinebean 3 роки тому +1

    Well that was I interesting, the VFD adds a few challenges. But now you know what to look for next time they fail.

  • @ME-kv8ew
    @ME-kv8ew 4 роки тому +1

    Wow that view is amazing! I live in Southern Illinois and of course we have nothing like it. Thanks for the video and the wonderful view.

    • @lwilton
      @lwilton 4 роки тому

      Nothing like a 9,000 foot high mountain range 5 miles away to improve the view! :-)

  • @howardharaway2259
    @howardharaway2259 3 роки тому

    Matt ,right ? You are inspiring me .
    Really ! I have been leaving comments left and right on alot of your video's.
    I only wish I found you awhile ago.
    Thank you for your time . It must be distracting troubleshooting and shooting a video.

  • @brianpiper3188
    @brianpiper3188 4 роки тому

    Excellent video! The best advice I've ever received regarding unplugging motherboards (or even doing anything that you're not familiar with) is to take a picture. Unlike the old days, it only takes one high resolution picture and you can zoom in on whatever pin, plug, bolt, etc that you want. For mechanical disassembly, I remove like bolts and group them in a line based on assembly stage. If one stage has two or more sizes, mark each length with a dot matching its corresponding location. It's like a car engine, each piston is marked to belong in a specific cylinder.

  • @bait28
    @bait28 4 роки тому

    Had a serious heart attack when you touched the belt of the fan with the unit still powered and the blower not locked out with a digital control unit, i've had units power the blower up due to funny faults causing the fan, something scary you never forget

  • @rubenrojas8632
    @rubenrojas8632 3 роки тому +1

    Thank you for the video. The company Forgot about maintenance. the new Units Have More Electronics Parts the require maintenance.

  • @samueleddy3112
    @samueleddy3112 4 роки тому +6

    Seems like we’re starting to go from HVACR techs to computer techs. I’m on the ice cream side and it’s always one board doesn’t communicate with the other and now I use my meter more than my gauges.

    • @lwilton
      @lwilton 4 роки тому +6

      Watch the "South Main Auto" channel for a little bit and you will see that car diagnostics and repair are now all poking at a computer screen and only occasionally twisting a wrench. Its pretty much the wave of the future (present) for most all trades, I suspect.

    • @ischmidt
      @ischmidt 4 роки тому +2

      @@lwilton Funny you reference SMA. On this video when I saw the blown-up VFD I said "Well there's your problem, lady!" in my best Eric O voice (which isn't very good).

    • @thenewsshow
      @thenewsshow 4 роки тому

      Same thing happened in the telephone industry... went from hardware debugging and repair to all software and just replace the sets when they go bad over the course of only like 10 or 15 years. whack.

    • @OcRefrig
      @OcRefrig 4 роки тому +1

      Wilton - sma rules.

  • @OldePhart
    @OldePhart 4 роки тому +2

    As for the VFD, the caps are swollen, common problem over time and with heat, dirty fan would indicate that's a possibility. The destruction can also happen in startup when the spare VFD has been on the shelf for a long time (years) and the caps lose their polarity. You have to "reform" them with a slow introduction of the supply voltage. That is far less common but it worth knowing about. Another advantage of the VFD is that they don't care about the phase rotation.

  • @Athstavr24
    @Athstavr24 4 роки тому +8

    Hey great video very informative but did you actually remove the balloon??😂😂

    • @HVACRVIDEOS
      @HVACRVIDEOS  4 роки тому +8

      Yeah we pulled the whole economizer out and cleaned them all out there were like 4 in there, it just didn't make the final cut

  • @zjeepgozweeln
    @zjeepgozweeln 4 роки тому +2

    I think VFDs are great when they're of good quality and properly installed. They allow you to do so much with just one motor. Low demand or a need for de-humidification? Low and slow... High demand? Full speed ahead! You can maintain static pressure or airflow based on feedback... the options are endless.
    VFDs typically are set up with 3 I/Os. start/stop, analog speed (or in this case a pre-programmed 2nd speed), and a dry contact for alarm. Of course you can configure a lot more I/Os for other things as well. The better units can be configured for a lot more.
    Alas, here you see what seems to be a poor implementation. 3 compressors and other equipment sharing the same space on a roof that can reach extreme temps, baking in the sun. Sounds like a recipe for disaster if I've ever seen one.

  • @zarnaihjeneborra9292
    @zarnaihjeneborra9292 4 роки тому +1

    You're great man i learn lot of you thank you for your videos i hope my skill and technical experience it's getting more improvement to learn kind of this jobs and ideas, keep it up my friend.

  • @rRobot0
    @rRobot0 4 роки тому +12

    The reason why the camera can't see the displays is because they're doing something called multiplexing. It's much cheaper/less wires to display certain segments of a display at a time rather than every led at once.

    • @russellhltn1396
      @russellhltn1396 4 роки тому +6

      A lot of that is the camera is doing a high shutter speed due to being outdoors in the sunlight. Put a neutral density filter on it when you're outdoors and I'll bet the LED start looking a lot better.

  • @lackeydehackey405
    @lackeydehackey405 4 роки тому +1

    When you pulled the VFD, take note of the capacitors. They were severely bulged. Toss it. Electrolytic caps have paste inside. When that paste dries out, kabllooey.

    • @443DM
      @443DM 4 роки тому

      Or find replacement capacitors and re-solder new ones. Same thing happened to motherboards back in the day.

  • @maxi-g
    @maxi-g 4 роки тому +1

    again, great entertaining yet educational video

  • @kennethlobo4420
    @kennethlobo4420 4 роки тому

    Ghosh! Ur experience is great wish i worked with U.God Bless.

  • @wiedehopf9068
    @wiedehopf9068 4 роки тому +5

    Feels like those VFD drives should just have versions with more fans and changeable filters.
    That way they don't get as dusty inside and should last a lot longer.
    For this application having them be very compact doesn't matter.
    Maybe have an attachable intake fan + filter?
    But that would reduce sales for the VFD guys so... not sure if that would happen ... also maybe that use is too niche for those drives?

    • @thenewsshow
      @thenewsshow 4 роки тому +1

      it is interesting, I don't think I have ever seen a running VFD that was not full of dust.

  • @hvac97849
    @hvac97849 3 роки тому +1

    On the job training for this side of the camera, thanks for sharing.
    Oh, and thanks for the promo code as my Fieldpiece should arrive around the 13th or so.
    Cheers

  • @jeremydefreitas9753
    @jeremydefreitas9753 3 роки тому +1

    Very informative video thanks

  • @thesearcherman6652
    @thesearcherman6652 4 роки тому

    In that situation, with 2 other identical units on the roof, I very carefully swap boards to see which board is bad. But, you really gotta be careful not to screw up. Lennox had/has great tech support. I’d call them in a heart beat. Slowing the fan down de-humidifies much better as coil is colder. Thanks.

  • @mrbyamile6973
    @mrbyamile6973 3 роки тому +1

    I think I would have stuck with the contactor, needed overload protection though as the VFD provided that. Way to hot inside that compartment for a VFD as Chris eluded to when he mentioned the dust.

  • @sherwinanago9106
    @sherwinanago9106 4 роки тому

    Awesome video always it's very accurate ...👍👍❤❤...watching from Philippines

  • @Railtech_63.
    @Railtech_63. 4 роки тому

    There is nothing wrong with calling tech support, it can save you a lot time and some headaches too. An Another great video and showing sometimes jobs are more involved.

  • @DWAYNE2ism
    @DWAYNE2ism 4 роки тому

    Great troubleshooting skills

  • @donnierobertson3088
    @donnierobertson3088 4 роки тому

    Great job again like always and great video

  • @S_a_n22
    @S_a_n22 4 роки тому

    You are a lucky man. We had a technician pop one while replacing a water heater on the 7 floor. Costly mistake, They should have it replaced to be safe. Don't want that sucker popping after hours.

  • @frankmontefusco6016
    @frankmontefusco6016 4 роки тому

    Great video!! watched to the end!

  • @CCross777
    @CCross777 4 роки тому

    Oh man! That looks like Upland! Sweet :)

  • @LazyLifeIFreak
    @LazyLifeIFreak 4 роки тому +1

    Sunscreen, don't leave the home without it or forgot to wear it.
    Landscape gardener here, spending +12-14 hours outside in all weather.
    Raincoat is good too, maybe a packet of single use poncho's, a pair of wellies (if you're british/rain boots if you're 'Murican) because wet socks sucks.

  • @semifavorableuncircle6952
    @semifavorableuncircle6952 4 роки тому +16

    Why the hell do these units have no fuses for just about anything? Normally there would be fuses or breakers for the drive, motors etc.
    Looks like electrical regulations in the US are really lax about this. No surprise the VFD fails that way. When these blow here, even with 400V mains, the input fuse blows and there isnt any damage beyond the power module and it usually can be repaired.

    • @riccardoz2953
      @riccardoz2953 4 роки тому

      it should have also a self protection cyrcuit.. was a mitzubishi if i didnt see wrong.. how can fail so badly?

    • @semifavorableuncircle6952
      @semifavorableuncircle6952 4 роки тому +3

      @@riccardoz2953 Normally VFDs dont have any internal fusing and require external, properly sized, current limiting, fuses.

    • @semifavorableuncircle6952
      @semifavorableuncircle6952 4 роки тому +3

      @Timothy Salomon Idk about HVAC, in my field of industry, we frequently have to deal with really old, hard to replace parts and often go for component level repair, sometimes going as far as to qualify as re-engineering.

    • @russellhltn1396
      @russellhltn1396 4 роки тому +4

      Fuses are about protecting the wire. In this case, I doubt if any amount of fusing would help much. The protection circuit has to allow enough energy to run the fans - which is more than enough energy to go "bang".

    • @russlehman2070
      @russlehman2070 4 роки тому +1

      Kind of looks like the VFD IS the fuse. Why sell a $5 fuse, when you can sell a $50 VFD . Or whatever the acctual prices are. I just pulled those numbers out of the air.

  • @RubenKelevra
    @RubenKelevra 4 роки тому +2

    If you expect that a system has no power it's actually better to use the NCV function of the multimeter, additionally to checking AC voltage with the leads. It makes sure there's no backfeed from a different circuit you didn't expect.

  • @jeffgrant6914
    @jeffgrant6914 4 роки тому

    Nice repair video 👍

  • @hasnomoney1800
    @hasnomoney1800 3 роки тому

    First of all, that mountain looks dope.

  • @GottSegneDich
    @GottSegneDich 4 роки тому +9

    Check out the shit-stain by the VFD at 4:19 😬
    Edit: Currently a 4th gen locksmith but these videos have me thinking of a career change.
    Edit #2: It was dust. Ignore my ignorance.

  • @OcRefrig
    @OcRefrig 4 роки тому

    Good vid. That was a Pain in the backside job. Holy smokes.

  • @IFIXCASTLES
    @IFIXCASTLES 4 роки тому +2

    Could have a brownout. Had a store where I was constantly replacing burned out 24 coil contactors on the a.c.. It turned out the feed lines to the store in the ground were effed up.