DP Type Level Transmitter Calibration Procedure of Dry Leg | Instrument Guru

Поділитися
Вставка
  • Опубліковано 16 січ 2025

КОМЕНТАРІ • 168

  • @avinashbhatt2317
    @avinashbhatt2317 Рік тому +1

    very useful and informative video Sir thank you very much sir again

  • @arunantony2281
    @arunantony2281 5 років тому +2

    Lrv#50
    Urv#550

  • @Saabai_Saabai
    @Saabai_Saabai 6 років тому +17

    Lp should be ( x with 0) due to dry leg...(1100mm x 0)= 0

    • @technicianks1932
      @technicianks1932 3 роки тому

      Yes

    • @vikas786001
      @vikas786001 3 роки тому +1

      No in lp side transmitter connected below datum line.thats why it is not zero.if transmittee is connected in datum line then lrv is o

    • @vivekenergy
      @vivekenergy 2 роки тому

      Atmospheric pressure acted

  • @pradoshhampale9947
    @pradoshhampale9947 Рік тому

    Thanks bhai
    Good explanation

  • @dhrubamukherji8673
    @dhrubamukherji8673 5 років тому

    really bro u had made a amazing vedeo on dp transmetre keep it up

  • @askarihasanzaidi1211
    @askarihasanzaidi1211 5 років тому

    Good videos h appreciate

  • @AsadPassionateEngineer
    @AsadPassionateEngineer 2 роки тому

    💖 This is an inspiration for ME !! Even I make "INSTRUMENTATION VIDEOS".
    I hope I can emulate your presentation skills.
    All the best for your future videos ☺

  • @vikaskumarvishwakarma6796
    @vikaskumarvishwakarma6796 2 роки тому

    It's very helpfully.... Nice sir 👍👍👍
    Please make a more videos on Radar type level tx range calculation for emerson and vega etc

  • @jitubabusay2826
    @jitubabusay2826 4 роки тому

    Plz make a video on close tank

  • @ramgr6888
    @ramgr6888 5 років тому

    Super explain. Tks friend

  • @sahilKhan-xw3bo
    @sahilKhan-xw3bo 6 років тому +1

    Very nice videos sir

  • @devendraduryodhan8840
    @devendraduryodhan8840 8 місяців тому

    good job

  • @muhammadasif5826
    @muhammadasif5826 2 роки тому

    Good bro

  • @VinothKumar-ks2xd
    @VinothKumar-ks2xd 6 років тому +1

    Thanks
    Pls explain types of level transmitter

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      Thanks for your suggestions, ur suggestion is noted. i will share detail in upcoming videos.

  • @mannuemotional150
    @mannuemotional150 Рік тому

    Close tank k baare m v btaye

  • @mukeshsable3714
    @mukeshsable3714 Рік тому

    Can we used DP Type Level Transmitter for Interface Layer Separation from agitated batch reactors (jacketed)?

  • @vinayk171
    @vinayk171 6 років тому

    Is there necessary of taping at Lp side

  • @atulrohit727
    @atulrohit727 5 років тому +3

    What is zero-suppression-and-zero-elevation-calculations in DP LT

  • @hariharbabuofficial7095
    @hariharbabuofficial7095 4 роки тому

    Hello""
    Sir ye Master instrument kya hota espe video bnaye sir'''
    Apka video se bhut kuch sikhne ko milta hai...????👍 THANKS

  • @mannuemotional150
    @mannuemotional150 Рік тому

    Specific gravity kaise pta krenge kitna dry leg..
    And weight leg m

  • @vijendramehra530
    @vijendramehra530 4 роки тому

    Good

  • @vshakeher
    @vshakeher 6 років тому +5

    Few clarifications needed
    1. Do we need LP connection in case of level measurement in open tank
    2. Please recheck your calculations of LRV. What density have you considered for dry leg?
    I feel it needs correction.
    Thank you

    • @InstrumentGuru
      @InstrumentGuru  6 років тому +2

      no we don't need any LP connection in case of open tank but in closed tank we required LP connection.

    • @vshakeher
      @vshakeher 6 років тому +1

      Instrument Guru please check the calculation as well in this example

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      Thanks for your suggestions and notfying me. this will help me to improve quality of my videos. thanks again.

    • @InstrumentGuru
      @InstrumentGuru  6 років тому +1

      i have written the open tank and given the Example of closed tank thats why this confusion occure, Thanks for your notice.

    • @savethenature-savethefutur9867
      @savethenature-savethefutur9867 6 років тому

      1. not necessary, as lp is always atmospheric pressure.

  • @Lopanfernando
    @Lopanfernando 6 років тому

    good information...

  • @chandreshparmar4092
    @chandreshparmar4092 5 років тому

    Sir level trol ke bareme bataye

  • @bharat9711
    @bharat9711 Рік тому

    How to feed - value ,,pl..guide sir

  • @mohammedlubaid
    @mohammedlubaid 6 років тому +1

    diff calibration measurements steps bhi bataa dijiye bhai

    • @patelsanket2996
      @patelsanket2996 6 років тому

      dear instrument guru please check lrv value ....and also check to formula...

  • @neerajsharma-nl6lq
    @neerajsharma-nl6lq 3 роки тому

    Plz tell me FIT Orific type.calibration and zero adjustment

  • @dharmendrakumarsah6772
    @dharmendrakumarsah6772 5 років тому

    Conductivity transmitter per video banaye

  • @studyforcompetitiveexams4251
    @studyforcompetitiveexams4251 6 років тому

    Thanks a lot

  • @freedomoflife9459
    @freedomoflife9459 4 роки тому

    Close tank ki upar calibration video sahe a.. Thank you

  • @zafareqbal656
    @zafareqbal656 5 років тому +4

    Dear I appreciate you, you are making nice videos but in this video u have make a mistake, as per level calculations in dry leg HP will be zero always and LP will be maximum hight but u mounted transmitter in down side so it will be +50 mm not -50 please correct it because many people will miss understood and its not good, thank-you

  • @sushilgharat2264
    @sushilgharat2264 6 років тому

    Thanks bro...

  • @aamirbashir4242
    @aamirbashir4242 3 роки тому

    Can you advise how we can replace diaphragm seal.?

  • @kannanhariprasad
    @kannanhariprasad 6 років тому

    Is ur calculation is for open tank or closed tank?

  • @shakirgour5298
    @shakirgour5298 6 років тому

    sir kya aap training bhi karate hai instrumentation and dcs ki

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      currently abhi training session available nahi hai, mai aap sabhi youtube ke madhyam se sab kuch sikhane ki kosis karunga.

  • @Jawed183
    @Jawed183 6 років тому

    Nice video

  • @mdhafeezurrahman3487
    @mdhafeezurrahman3487 Рік тому

    Pls load more videos

  • @AbhishekKumar-mw5lj
    @AbhishekKumar-mw5lj 6 років тому

    Can you plz explain install and commissioning process of ultrasonic and radar type level transmitter

  • @sohailrockakhtar4055
    @sohailrockakhtar4055 6 років тому

    Sir ek bar radar level transmitter ke bare me video banaye details aur calibration ke sath thanks

  • @ravikumar-pt4wn
    @ravikumar-pt4wn 6 років тому +3

    Sr aap jis instrument ke bare me bta rhe ho uske working principle bhe btaya kre

  • @manikantanaidu1577
    @manikantanaidu1577 6 років тому

    Lrv value is wrong because it is dry leg. If it is wet leg then the lrv value which u said is correct.

  • @nitheeshkuttan1190
    @nitheeshkuttan1190 6 років тому

    Sir tomorrow interview for me to at chennai for maintance shutdown project pls some questions answer give me

  • @jaydeepmahida5635
    @jaydeepmahida5635 5 років тому

    Close tank Ka bhi aese hi karte he..calculation

  • @AbhishekKumar-mw5lj
    @AbhishekKumar-mw5lj 5 років тому

    Bhai FF transmitters ka configuration or error troubleshooting ka video banao aap

  • @akramzmin4721
    @akramzmin4721 6 років тому

    Sir , tell me Radar , ultrasonic level transmitter kiya hai aur uska principal

  • @MohdShahid-vh1iu
    @MohdShahid-vh1iu 10 днів тому

    Sir, in this case tank is open and LP taping is non filled, so LP don't have any gravity then why you take 1100

  • @akramzmin4721
    @akramzmin4721 4 роки тому

    Dp level transmitter working principle kiya h pls tell me

  • @jaydeepmahida5635
    @jaydeepmahida5635 5 років тому

    Exple me konsa liquid use Kareng open tank or close tank me

  • @gavsraw7812
    @gavsraw7812 6 років тому

    Open tank mein dry leg ke bajaye open to atm karne pe LRV & URV kya hogi?

  • @vasudevanveeraragavan1937
    @vasudevanveeraragavan1937 5 років тому

    sir please make video in English.Tks

  • @ajeetchauhan1152
    @ajeetchauhan1152 6 років тому

    Sir transmitter calibration ka video banaye please

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      watch video abt PT Calibration:-
      ua-cam.com/video/FLCfLBymQ8s/v-deo.html

  • @vijaysolanki5267
    @vijaysolanki5267 3 роки тому

    Sir -50 to 50 LRV URV he ur tx -45 PV dikhata he to use less calculate kare

  • @dpgupta2
    @dpgupta2 6 років тому

    Open tank me lp side connect karne ki Kya jaruri hai

  • @mdzeeshan8118
    @mdzeeshan8118 6 років тому

    Level troll interface transmitter wet our dry dono bataie

  • @akramzmin4721
    @akramzmin4721 5 місяців тому

    have one question
    Lt hai Jo c to c hai 1000mm
    Tank Mai 2 liquid hai ek water hai dosra oil h
    Water ki density 1 hai aur oil ki density 0.8 hai
    Lrv aur urv kiya hoga
    Pls reply me

  • @mohdasif-sf4pm
    @mohdasif-sf4pm 5 років тому

    How many type flow transmitter and how many type pressure transmitter

  • @PK-eg8yy
    @PK-eg8yy 5 років тому +2

    You are wrong in this LRV calculation
    LRV must be 50 because there is no pressure in LP side
    HP - LP
    (100*0.5)- LP
    50-0
    50
    There is no pressure in LP side

  • @amolpatilnityaaassociates2602
    @amolpatilnityaaassociates2602 5 місяців тому

    What is LRV?

  • @kkr9993atoz
    @kkr9993atoz 2 роки тому

    Need correction on LRV

  • @Abu-sohail
    @Abu-sohail 4 роки тому

    Good explaintion 👍
    Can write formula of Range and how to calculate specific gravity?

  • @tamizhadanceteamtamizhadan8441
    @tamizhadanceteamtamizhadan8441 4 роки тому

    This calculation was closed tank. Not open tank. Calculation is correct for closed tank. Open tank lrv is 50 and urv 550. LP is Open to atm.

  • @gavsraw7812
    @gavsraw7812 3 роки тому

    Why LP side connected to top of open tank, it should be keep open to atmosphere.

  • @thebrightway6409
    @thebrightway6409 5 років тому

    P N ID Drawing k bare me btaye

  • @chaibilamri8042
    @chaibilamri8042 6 років тому

    thenk you ser

  • @kadirperwez6564
    @kadirperwez6564 6 років тому

    sir app online class ki kosis kijie

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      Thanks for your valuable suggestion. i thought youTube is the easiest way to teach the people.

  • @TiberiusStorm
    @TiberiusStorm 6 років тому

    Please do videos in English as well!

    • @InstrumentGuru
      @InstrumentGuru  6 років тому +2

      Channel is dedicated for Instrumentation in Hindi, but i will try to add subtitles/CC in English which help you to understand.

    • @TiberiusStorm
      @TiberiusStorm 6 років тому

      Great thanks!

  • @lutforrahman3358
    @lutforrahman3358 5 років тому +1

    dada me bangladesh hoge bath korage ak P I D controloler masibus 5040 program setup ak video banayi ok

  • @chandreshparmar4092
    @chandreshparmar4092 5 років тому

    Aapke video kyu nahi aa rahe sir

  • @sandeepyadav4713
    @sandeepyadav4713 6 років тому

    Sir please explain karen ki open tank me lp side kaise connect hota hai jaha tak mai janta hu ki lp side atmosphere me went hota hai

  • @suhaibjubail6097
    @suhaibjubail6097 6 років тому +2

    Why do u need LP side tubing for open tank.
    I think
    It is 50 mm h20
    And urv is 550 mm h20 as per ur diagram.

  • @vijaysisodiya8128
    @vijaysisodiya8128 6 років тому

    Dear sir,
    Please make an video for remote seat type LT range calculation

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      remote seal LT ki jald hi video daalunga

  • @Usman.9234
    @Usman.9234 6 років тому

    4 to 20 ma ka chart kaise ready kare dono k bich ka 8 ma 12ma 16ma ka kitna hoga wo formula v bata dijiye sir

  • @rajanpiush6359
    @rajanpiush6359 6 років тому +1

    Sir diaphragm type DPLT hoga to kya Karen's

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      Jald hi iski video dekhne ko milegi aapko

  • @Khusbupatel2001
    @Khusbupatel2001 6 років тому

    close tank dry and wet ka calibration double liquids double density

  • @shivkumargupta9335
    @shivkumargupta9335 6 років тому

    how to calculate LRV & URV for DP flowmeter?

  • @chaudharirinam275
    @chaudharirinam275 6 років тому +1

    Dear sir displacer level transmitter pe video nana do

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      thanks for your suggestions... i will try to make video on this topic.

  • @shamshiqubal348
    @shamshiqubal348 6 років тому

    if tank is full then what is the value LRV in such case

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      value calculation will be same... LRV= HP-LP

  • @sahilKhan-xw3bo
    @sahilKhan-xw3bo 6 років тому +1

    Sir iska linearity 25% to 100% kaise check karenge. Apne to 25% and 100% bataya. But 50% and 75% nikalne ka formula nahi bataya. Please ise v bata dijiye.

    • @InstrumentGuru
      @InstrumentGuru  6 років тому +1

      okay next video me mai jarur bataunga iske bare me

  • @dpgupta2
    @dpgupta2 6 років тому

    Wet leg and dry leg Kya hai kaha kaha use hota hai please bataae

  • @feraquebakhat9784
    @feraquebakhat9784 2 роки тому

    L. P=100*0.5 =pressure hogaya, hp side me specific gravity hai hi nahi 1100 *? , to pressure ke product se hight minus kaise hoga

  • @sufianshah8107
    @sufianshah8107 3 роки тому

    ye banda bs apni vedio ko lambi karne k chakkar me rehta abi me ye batane wala hon abi me wo batane wala hon

  • @ARIFANSARI-rb7un
    @ARIFANSARI-rb7un 6 років тому

    Sir instrumentation ka koi book ka name bataye .kise bhai ko malum hoga to help kare...please

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      Bela G. liptak author is costly but very useful for all instrumentation guys. all levels diploma degree master degree.

  • @vanjalasatish895
    @vanjalasatish895 4 роки тому

    Explanation is good but why hurry burry

  • @vijaysisodiya8128
    @vijaysisodiya8128 6 років тому

    Dear sir,
    Please make a video on wet leg calibration also

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      Wet Leg Calibration video will be available today at 9 PM

  • @gyanandchaubey3709
    @gyanandchaubey3709 6 років тому

    drum ki level measure karne K liye negative mei kyon rakhate hain

  • @sunilprajapati8088
    @sunilprajapati8088 6 років тому +1

    Urv and lrv minus me kyo ayi h plus me nhi aa sakti h kya

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      aa sakti h open tank k case me.

    • @sunilprajapati8088
      @sunilprajapati8088 6 років тому

      Uska bhi vedio banaiye

    • @satishsharma7213
      @satishsharma7213 6 років тому

      Wet leg mein lrv and urv kya hogi
      Spouse level transmiter range is -670 to 0 close loop wet leg case

  • @prakashjadhav9385
    @prakashjadhav9385 6 років тому

    एक हि transmittar अलग अलग जगह पे leval, pressure, flow कैसे मापते हैं।
    Leval, pressure,flow के principle क्या है।

  • @VinothKumar-ks2xd
    @VinothKumar-ks2xd 6 років тому +1

    How many types of level transmitter ? Pls explain bro

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      thanks for your Suggestions, ur suggestions is noted and will make a video om this topic.

  • @rakeshtirki6570
    @rakeshtirki6570 6 років тому +1

    Thanks sir
    Par ap ne sensor ka vidio q nahi dal rahe hai

  • @engineertashkeelahmedshah4548
    @engineertashkeelahmedshah4548 6 років тому

    Dear first of all i like your all video but dp type level transmitter calculation is some mistake please check 1050 LRV AND 550 URV but 550 is not _ range this is + rang -1050 to =550 ok please see and tell me and dear make video interface level measurement dp or displacer types

  • @souravkumar2522
    @souravkumar2522 6 років тому

    DP ka kya MATLAB hota h ?

  • @dharmesh.jpatel2013
    @dharmesh.jpatel2013 6 років тому +2

    wrong range you show us.in dp dry leg always in plus value not in minus.

    • @Vijay.0233
      @Vijay.0233 5 років тому

      Dharmesh.j Patel yes agreed

  • @motilalhansda4318
    @motilalhansda4318 2 роки тому

    Open tank me dry leg nhi hota h ..sir...

  • @ajaisunesh68
    @ajaisunesh68 5 років тому

    Lp side is applicable to closed tanks why you saying open tank???

  • @Mohsinkhan1015
    @Mohsinkhan1015 6 років тому

    Sir aap jo drow kar rahe ko use pdf me upload kr diya karo

    • @InstrumentGuru
      @InstrumentGuru  6 років тому

      i am working on this or jald hi aapko meri sabhi video ki drawings dekhne ko milegi mai aap sabhi ko update kar dunga.

  • @babaranchhoddas9423
    @babaranchhoddas9423 6 років тому

    Ye video aapka hamein samjh mein nahi aaya baki almost video dekh chuka hun par level transmiter calibration clear nahi hua . Please clarify it .

  • @muhammadfaheem8582
    @muhammadfaheem8582 3 роки тому +1

    Dear this calculation is wrong. Please don't mislead new Technicians. You have made a mistake, as per Dry Leg level calculations LP side will be zero Always
    Correct values for LRV and URV are as under. Both values will be Positive in Dry leg.
    LRV: 50
    URV: 550
    I hope u understand. Thanks

  • @haniaissam5558
    @haniaissam5558 5 років тому

    why you have used 1100 mm at the LP side, please whether you edit it or you delete it diffenitely, you are using the methode of wet leg instead of the dry leg.

  • @niksrathia
    @niksrathia 4 роки тому

    URV=LRV+Range. As u say.
    That means
    URV-LRV=Range to isme cross verification kaise hua.. 🤔🤔🤔

  • @allwinr7187
    @allwinr7187 6 років тому

    Close tank calibration sent me