PowerFlex 750 Series HIM Copy Cat How To

Поділитися
Вставка
  • Опубліковано 22 січ 2025

КОМЕНТАРІ • 22

  • @billschmidt1182
    @billschmidt1182 4 роки тому

    I live very much the added touches. Very polished.

  • @BravoCristian
    @BravoCristian Рік тому +1

    Hi. Can you make a backup with the HIM with the VSD working?

    • @solutionconsultantsnetwork6843
      @solutionconsultantsnetwork6843  Рік тому +1

      Hi, BravoCristian. HIM-to-Device needs the Drive to be stopped. Device-to-HIM can be done when the Drive is running provided that the HIM is firmware 1.006 or higher. Thanks!

    • @BravoCristian
      @BravoCristian Рік тому

      @@solutionconsultantsnetwork6843 thanks

  • @alejandroperezpulido2533
    @alejandroperezpulido2533 2 роки тому

    Hi, where is the option "Download all ports" and for do it, do I need to do anything else or just put my HIM on the new driver and look for that option? I would appreciate your answer and this was a really helpfull video. Thank you.

    • @solutionconsultantsnetwork6843
      @solutionconsultantsnetwork6843  2 роки тому

      Hi Alejandro. To get to "download all ports," press the menu button on the HIM and go to the Memory tab. Select HIM, copycat. Once inside, scroll down until you see "Download All Ports" Thanks!

    • @alejandroperezpulido2533
      @alejandroperezpulido2533 2 роки тому

      @@solutionconsultantsnetwork6843 Thank you!

  • @edinetgrunhed6000
    @edinetgrunhed6000 3 роки тому

    nice videos, i have some questions if example im using DriveExecutives and replacing new drives shall i upload all ports and download to all ports too? assuming same option cards. thanks,

    • @solutionconsultantsnetwork6843
      @solutionconsultantsnetwork6843  3 роки тому

      Hi, edinet. This video does not cover the use of DriveExecutive. With that said, using DE (or, preferably, connected components workbench) to copy and download parameters is a fine way of backing up your drives and will catch all ports involved. Here is a link to more information for CCW: ua-cam.com/video/vYThulr6FcI/v-deo.html

  • @MarkMcMillen2112
    @MarkMcMillen2112 3 роки тому

    What's the reason you used upload from all ports as opposed to copycat from device to HIM?

    • @solutionconsultantsnetwork6843
      @solutionconsultantsnetwork6843  3 роки тому +1

      Hi Mark. Sorry for the tardiness of my reply! "all ports" copy the parameters for each option card, the mainboard, and DeviceLogix. Device to HIM only copies the parameters from the mainboard to the HIM. If your drive has options cards and or DeviceLogix programming, then "all ports" comes highly recommended. :)

  • @amelvin32
    @amelvin32 2 роки тому

    What happens if you don't even get the option to upload all ports? Just go with Copycat from device to him, I'm assuming?

    • @solutionconsultantsnetwork6843
      @solutionconsultantsnetwork6843  2 роки тому +1

      Hi Javias. Here is a tip from the manual: "Before any CopyCat files are created, only the ‘CopyCat From Device to HIM’ menu item is shown. When Port 00 for the Host Drive is selected..., the ‘Upload All Ports’ menu item also appears." Hope that helps! literature.rockwellautomation.com/idc/groups/literature/documents/um/20him-um001_-en-p.pdf (page 50)

  • @mdmehedi8912
    @mdmehedi8912 2 роки тому

    how to parameter upload download allen bradly 753 old vfd to new vfd

  • @sparkyedu
    @sparkyedu 3 роки тому

    does it copy from all Allen Bradley vfd's or just certain ones?

    • @solutionconsultantsnetwork6843
      @solutionconsultantsnetwork6843  3 роки тому +1

      Hi sparky, this is only for the PowerFelx 750 series. Though the door-mounted HIM for the 520 series does allow for this functionality as well.

    • @sparkyedu
      @sparkyedu 3 роки тому

      Thanks buddy

  • @DOLPsc
    @DOLPsc 3 роки тому

    What is port 0

  • @jackieho168
    @jackieho168 3 роки тому

    Hi, whats is the restore password

  • @kashifnaveed4494
    @kashifnaveed4494 2 роки тому

    Usefull video