Pretty amazed that it takes a few minutes before the chiller trips on no flow . The ones I work on will trip almost instantly whilst running , or have a 60 second time delay on start ups , while the pump alone will run but not the compressors. This way they prevent the cooling from running without water flow .
If its in operation it will trip immediately on A201, if flow never stops after it goes unoccupied it will trip A202. A200 is when it never see's flow upon going occupied.
The overload is slow reacting device. Remember, if you are running slightly more current then it set to - it might take 20 minutes before it trips ( depending on OL code) I think that was a inductive spike from both transformer and contractor coil that blew the fuse on sudden power interruption.
Hallo Sir, Carrier Chiller 30XA I have one issue, Display Show ready but not running, showing on status override but not running again going on ready and again shows override but not running, could you suggest....?
Awesome walkthrough & follow through. My money was on the pump heating up & shorting. Most newbies miss the control circuit!
Another great video. Thanks for making the trade better for everyone. Your videos are awesome.
Thanks bud
Thanks SUPER-YORK, again for the videos!
🥃🥃🍺🍺🍺🎯🏌🏻♀️
Stay safe.
Retired (werk'n)keyboard super tech. Wear your safety glasses!
To the rescue!
Interesting chiller work 🤔 👌
Its a lot of fun!
Pretty amazed that it takes a few minutes before the chiller trips on no flow .
The ones I work on will trip almost instantly whilst running , or have a 60 second time delay on start ups , while the pump alone will run but not the compressors.
This way they prevent the cooling from running without water flow .
If its in operation it will trip immediately on A201, if flow never stops after it goes unoccupied it will trip A202. A200 is when it never see's flow upon going occupied.
@@HVACTIME Makes way more sense now , cheers !
Another good vid ... Thx for sharing 👍👍👍
Awesome tech
The overload is slow reacting device. Remember, if you are running slightly more current then it set to - it might take 20 minutes before it trips ( depending on OL code)
I think that was a inductive spike from both transformer and contractor coil that blew the fuse on sudden power interruption.
😊7
😅😅5😅
Hallo Sir,
Carrier Chiller 30XA I have one issue,
Display Show ready but not running, showing on status override but not running again going on ready and again shows override but not running, could you suggest....?
Like it, thanks for sharing :)
Your electronics can shut off current so fast that it can interrupt proper tripping of a breaker...especially on an old breaker.
Didn't you just post a question about megging motors and state you never meg over the motors voltage? Is it a 1000 volt motor?
Never more than 2x motor voltage
Can you make a video on how to use a megger?