HVAC Blower Motor Class! PSC Motor Speeds, Colors, Ohms, Current, Shorts, Air Restrictions!

Поділитися
Вставка
  • Опубліковано 6 лип 2024
  • In this HVAC Training Video, I show Furnace and Air Handler Blower Fan Motor Operation, Speeds, Wire Colors, Electrical Resistance Values on the Windings, How to Rest for Shorts, and How These PSC Blower Motors are Affected by Airflow Restrictions. PSC means Permanent Split Capacitor Motor. This Means that the Motor Requires a Capacitor to both Start and to Run. Supervision is needed by a licensed HVACR Tech while performing tasks as Experience and Apprenticeship garners Wisdom and Safety.
    Tools Used In The Video
    UEI DL479 Multimeter With Temp Sensor: amzn.to/2jtsUbJ
    Alligator Jumpers- amzn.to/2PxqJXn
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our Related Videos
    • HVAC Blower Fan Motor ...
    • Finding Run CAPACITOR ...
    • How to tell if a AC Ca...
    • HVAC ECM Variable Spee...
    • Testing ECM Variable S...
    • How to Troubleshoot a ...
    ECM Multi-Speed and Variable Speed Blower Motor Troubleshooting Playlist:
    • ECM Blower Motor Troub...
    Full Blower and Fan Motor Troubleshooting Playlist: • Troubleshooting HVAC F...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
    All Our Educational Products on Our Site: www.acservicetech.com/store
    All Our Educational Products on Amazon: amzn.to/48pDd82
    Mini Split Book and E-Book on Our Site- www.acservicetech.com/mini-sp...
    Mini Split Paperback on Amazon- amzn.to/3ytHJSs
    Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
    Refrigerant Charging Book and E-Book: www.acservicetech.com/ac-book
    Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Online Resources!
    Our HVAC Calculators: www.acservicetech.com/hvac-ca...
    Our Newest Articles: www.acservicetech.com/articles
    Try our HVAC/R Quizzes! www.acservicetech.com/quizzes
    Our Other Resources: www.acservicetech.com/resources
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Tools Used in Our Videos!
    Tool Links on Our Site: www.acservicetech.com/tools
    Our Tool List on Amazon: www.amazon.com/shop/acservice...
    Support the Channel by purchasing tools through TruTech Tools!
    Use this link www.trutechtools.com/?aff=8
    Save 8% at checkout using code "acservicetech"
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Follow Us On Our Social Media & Podcasting Channels!
    Patreon: / acservicetech
    Facebook: / acservicetech
    Instagram: / acservicetech
    X: / acservicetech
    LinkedIn: / ac-service-tech-llc
    Tiktok: / acservicetech
    Spotify: open.spotify.com/show/74KXLz5...
    Apple Podcasts: podcasts.apple.com/us/podcast...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    ⚠️ Disclaimer:
    Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided.
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    #hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #visual #accidental #testing #sequence #operation #HSI #silicion #nitride #carbide #blowermotor #motor #hvacclass #class #PSC #current #air #restriction
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

КОМЕНТАРІ • 61

  • @BartSimpson-nr1dy
    @BartSimpson-nr1dy 2 роки тому +19

    Out of all the channels teaching heating and air conditioning, you have the very very best examples, explanation’s and detailed instructions. Your verbal tempo and rhythm are excellent. Some talk way too fast and mumble a bit leading to many many play backs. Not with you.
    Thanks for your time and effort’s

    • @chrisdeanndavison3626
      @chrisdeanndavison3626 2 роки тому +4

      I purchased the AC service book and it is great. Detailed explanations and great illustrations. I've been doing HVAC since I was 15 with my dad (I'm 45 now and am the owner/operator of my dad's business) and I've picked up a lot of great information from this guy.

  • @Studentofhvac
    @Studentofhvac 2 роки тому +7

    I had one of those “I was today years old” moments on the amp drop due to restricted air flow. Thanks for doing these!

  • @scottsmith4430
    @scottsmith4430 2 роки тому +5

    You did an excellent job buddy! I retired after 48 years in the field starting from apprenticeship up to being a Maintenance Supervisor for many years and organized and ran our apprenticeship program for many years. Great life. Best of everything to you!

  • @performancebasedheatingair8006
    @performancebasedheatingair8006 2 роки тому +4

    The most common issue service techs have when testing blower motor amperage in the field is leaving the blower door off. This will give an amperage that is out of spec and confuse a tech. And sadly, its used as a means to show a customer their motor is bad and sell them a new one. Better to plan on using a wire outside of blower compartment, even the plug wire can work by deducting inducer voltage from total if the heat is on.....Awesome video.

  • @BestHVAC
    @BestHVAC 2 роки тому +4

    Craig, very well done on your explanation of blower motor diagnostics. Keep up the good work. I appreciate the effort you put into your videos. You are an excellent instructor.

  • @enriquehvac6004
    @enriquehvac6004 2 роки тому +1

    You’re a very good teacher thanks for the videos they have helped me a lot throughout the years

  • @pizzle1011
    @pizzle1011 2 роки тому +1

    Thanks for the videos. I learn a lot from them 👍🏾👍🏾

  • @sparkytech8787
    @sparkytech8787 2 роки тому +5

    Please do a video on checking inverter on split air con's, I'm old school analog caps and contacts. thank you love your explanations

  • @eacjones
    @eacjones 2 роки тому

    Thank you Craig. This is very helpful. I love the videos!!!

  • @equiteemfg
    @equiteemfg Рік тому

    Absolutely amazing amount if exact information is a very short video. Great presentation!!

  • @REFEREEMOUSE
    @REFEREEMOUSE 2 роки тому

    Awesome video, I am happy I bought your study material

  • @CommercialGasEngineerVideos
    @CommercialGasEngineerVideos 2 роки тому

    Good information on a plate. Thanks a million.

  • @felipeballi7679
    @felipeballi7679 2 роки тому

    Great job man,
    Very well explained class

  • @TonyHoanz-vc2pq
    @TonyHoanz-vc2pq 2 місяці тому

    Thanks for sharing. Tony from Houston

  • @GotchaplumberGotchahvac
    @GotchaplumberGotchahvac 6 місяців тому

    Another good video; informative, tailored to learning.

  • @Ageehvac
    @Ageehvac 2 роки тому

    Thanks Craig, I needed this...

  • @jimmysegovia2688
    @jimmysegovia2688 2 роки тому

    thanks, Craig for sharing! good stuff man.

  • @andresperez5812
    @andresperez5812 2 роки тому

    simple you are the best . Thank you

  • @lolocamacho3249
    @lolocamacho3249 2 роки тому

    Thank you very much and God bless you

  • @watchme7192
    @watchme7192 2 роки тому

    your video is very helpful way better than the school I went to. last week I received the book from amazon a bit expensive but that's fine . watching from United Arab Emirate (UAE)

  • @JaykeSapalaran-iq3qs
    @JaykeSapalaran-iq3qs Рік тому

    AC SERVICE TECH, ❤❤❤ BEST VIDEO INFORMATION ❤ THANK YOU VERY MUCH SIR FOR SHARING YOUR KNOWLEDGE 🇵🇭👍

  • @MsFishingdog
    @MsFishingdog 2 роки тому +1

    Great video

  • @resurgensix
    @resurgensix 2 роки тому

    Thank you Professor Mig. Seeing the higher ohm reading I would have thought it must be a higher speed. Key information. Need to go back and study my Ugly right? And now it makes more sense. Less resistance means more voltage delivered to the fan. TY
    Just bought the paperback version of your Refrigerant Carving and Service. It is my new Bible

  • @pine0981
    @pine0981 2 роки тому

    Good video.

  • @deanmartin1966
    @deanmartin1966 2 роки тому

    Good info thanks for sharing.

  • @gregoriocanales3974
    @gregoriocanales3974 2 роки тому

    Excelente great job thank you

  • @Mudcat597
    @Mudcat597 2 роки тому

    👍👍, thanks for sharing!

  • @elicose771
    @elicose771 8 місяців тому

    ❤❤❤❤❤❤❤❤ thanks!!

  • @sammy60164
    @sammy60164 2 роки тому

    I ALWAYS tell apprentices to take a picture of the wiring and all tags BEFORE mounting in the band, or just mounting in general.

  • @spelunkerd
    @spelunkerd 2 роки тому

    The great thing about videos like this is the way they challenge preconceived notions. From your video I spring boarded into better understanding of how PSC motors allow variable speed. A standard formula to determine synchronous speed of a squirrel cage induction motor is to multiply 120 by 60, then divide by the number of poles in the motor. Most, including most shaded pole motors, have two poles. Am I correct to assume that the speed control of those extra windings is because the extra windings effectively create more poles in the stator, resulting in a slower synchronous speed? Is the slip % of slow speed significantly more for slow speed operation in PSC motors?

  • @Zepsswansong
    @Zepsswansong 11 місяців тому

    Great tutorial, thanks! So now that we identified our speeds, how do we find out the RPM of each speed with out a rotation meter. The reason I ask is my motor at home on my condenser was an 860 RPM motor. I only had a 1075 two speed motor on the truck to replace it with. So naturally i put it in so my wife could have some air conditioning. I wired it to the low speed, but it still seems to be a bit too fast. I searched some for the answer to this, without much luck, any help would be great, thanks again.

  • @Abo_Moussa
    @Abo_Moussa 4 місяці тому

    What happens if all speeds are assembled and connected together at the same time?

  • @realSamAndrew
    @realSamAndrew 2 роки тому

    Craig, is there a way to tell if the blower motor is getting weak, like not blowing as hard as you think it should?
    Also if you want the fan to always blow on high speed for everything, can you put a dual connector or y adapter on the black wire to both the heat and cool terminals?

  • @jesusgil931
    @jesusgil931 2 роки тому

    Hello. Thanks for your videos.
    A question...if im checking resistence between any of the wires of the blower to ground, and i get a value differento to OL. What should do? Replace motor? Or what step?

  • @hvac-r977
    @hvac-r977 2 роки тому +1

    Can you explain what was happening in the motor when air flow was blocked? Why got higher speed yet current went down? It was already at its highest set speed. Will motor be dead sooner when air flow is consistently blocked? Thank you

  • @BigDripLip
    @BigDripLip 2 роки тому

    So what wires are you using to test the wires resistance when you turning the blower on

  • @innovativeoutdoorsman5067
    @innovativeoutdoorsman5067 Рік тому

    I have a 1/2 HP,GE motor from my Rheem furnace (this is a spare motor) Its got 2 brown wires for the cap, a white wire which is the common and then black (which should make the motor spin the fastest) and it also has a blue, yellow and red wire. (red should make it turn the slowest)
    Depending on which of the colored wires I pair with the white, I should get a different speed (RPM) out of the direct drive motor.
    I hope to use this HVAC motor for another task but need to understand the RPM
    So I set up my stop watch on my Iphone, I put a piece of tape on the shaft and set up my camera to record video which Im able to slow down to very low speeds so I could count the turns of the shaft.
    It did not matter which wire I paired with the white wire, all of them made the motor spin the same speed (1200 RPM) which is faster than the rated speed on the motor label which is 1050 RPM.
    After talking with a friend, he thinks it might be because Im free wheeling the motor with no load on it, (no impeller and no duct work)
    Im stumped. Im not an electrical guy. All my engineering work is on the mechanical side of things.

  • @Ricoswavaey
    @Ricoswavaey 2 роки тому

    What about on a ecm motor will the amps go up or down with restriction?

  • @Mbtech77
    @Mbtech77 2 роки тому

    Sir, I find it difficult to take out the blower motor out from blower wheel.Please do a video.

  • @sergiohernandez4163
    @sergiohernandez4163 2 роки тому

    Our tech support retired and I was kind thrown under the bus and put me doing service. I been watching your video's and learned quite of bit. This one of my problems diagnosing either raw board or motor was bad. I'm having little of issues working on mobile home electric furnace. Do you have any videos on them?

    • @MorganBW53
      @MorganBW53 2 роки тому

      Here are a couple that he has.
      ua-cam.com/video/U7Tqk2Xh1Jw/v-deo.html
      ua-cam.com/video/7_-x6u9uzhU/v-deo.html

  • @chriseh09
    @chriseh09 2 роки тому

    Were you adding a restriction or adding static pressure? A duct system will,add static pressure without adding a “restriction” but a PSC running without static pressure will over amp, get hot and shut down.....am I correct?

  • @douglieberman6406
    @douglieberman6406 2 роки тому

    For instance in terms ohms law and watts law, you are reading 4 ohms and 10 amps with black wire that means there is 40 volts present and according to watts law that means there is 400 watts also! Can you reply about that?

  • @UltraHydrophobiccoat
    @UltraHydrophobiccoat 2 роки тому +1

    1: 120v PS motor is easier to be burned out since it has higher current?
    2: You showed the motor current is much lower when its air flow was blocked, which is good for motor since its current is much lower? In reality when insulation pad fell off and blocked the air flow it normally caused the motor to be burned out. Can you explain that? Thank you

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 роки тому

    It better than a regular TV!🤣
    Thanks again for the videos!
    🍺🍺🍺🥃🥃🎳⛳
    Stay safe.
    Retired (werk'n)keyboard super tech. Wear your safety glasses!

  • @dennisqwertyuiop
    @dennisqwertyuiop 2 роки тому

    I have a blower as seen in video,if I run it without a restriction the amps are high,with some restriction the amps go down,how souuld I run blower for moving air in shop ?

  • @harkamagar201
    @harkamagar201 Рік тому

    why double the voltage lower the amps? what is explanation behind the low voltage(120v) got move amps than high voltage(240v)? any one can explain me plese

  • @Michael046145
    @Michael046145 4 місяці тому

    I could just kick myself for incorrectly believing that an air restriction would cause an increased amp draw! Thank you!

  • @juanrobles9511
    @juanrobles9511 2 роки тому

    240v is a lot less amperage than 120v, therefore less electricity usage. Good refresher course. Thanks👍

  • @aliancafirme
    @aliancafirme 2 роки тому +1

    How can this blower motor have so high amps?!! 8ish amps on a blower motor???

  • @innovativeoutdoorsman5067
    @innovativeoutdoorsman5067 Рік тому

    My motor says 1050 rpm. What does that mean the other two speeds are???? My motor label says 5Kcp39kg 1/2 HP

  • @ccthepope
    @ccthepope 2 роки тому

    Craig, had you blocked off the outlet would you also have lower currents?

    • @performancebasedheatingair8006
      @performancebasedheatingair8006 2 роки тому +1

      Yes

    • @mackenziegray2090
      @mackenziegray2090 2 роки тому

      If the outlet was blocked off you would read a higher amps. Because the motor is struggling to move that air forward. It reads lower when restricting the intake side because their is no air to move

    • @lnk4328
      @lnk4328 2 роки тому

      MG, wrong. Blocking either the inlet or outlet results in the fan moving less air which means the motor is doing less work which equals lower current.

    • @performancebasedheatingair8006
      @performancebasedheatingair8006 2 роки тому +1

      @Mackenzie Gray on a PSC motor your answer is wrong. On an ECM motor your answer is right. This video was on PSC.

  • @publicmail2
    @publicmail2 2 роки тому

    SP one of the most important and out of spec. in the field costing $.

  • @John-dp3ln
    @John-dp3ln 2 роки тому

    Wish you had included demonstration of operation with a bad capacitor, open, shorted and wrong value. Otherwise excellent.

  • @thesilentonevictor
    @thesilentonevictor 2 роки тому

    Great video