Old HVAC industry practices are holding us back and costing us money. But we can fix it.

Поділитися
Вставка
  • Опубліковано 16 тра 2024
  • More Pumping More Now
    Looking for that condensed version? • HVAC professionals are...
    Links 'n' stuff:
    How heat pumps actually work:
    • Heat Pumps: the Future...
    The video I did on home electrification:
    • Home Electrification: ...
    Technology Connections on Mastodon:
    mas.to/@TechConnectify
    Technology Connections on Bluesky:
    bsky.app/profile/techconnecti...
    This channel is supported through viewer contributions on Patreon. Thanks to the generous support of people like you, Technology Connections has remained independent and possible. If you'd like to join the amazing people who've pledged their support, check out the link below. Thank you for your consideration!
    / technologyconnections
    00:00 Intro
    02:19 This video is about sizing equipment
    04:03 My home and its oversized system
    08:49 So many homes have the same problem
    10:41 Oversizing needs to stop
    13:31 Price gouging
    15:56 A note on duct sizing
    18:12 How a smart thermostat can do all the work for you
    23:00 LOAD CALCULATIONS
    29:34 An experiment to validate those calculations
    40:06 RESULTS
    42:12 The impact for me
    43:17 A rant on ductwork design
    48:57 Why the heck is my furnace so big?
    50:00 My parents (wrongly!) got told they'd need a giant heat pump
    55:08 Debrief
    1:01:11 Bloops
  • Наука та технологія

КОМЕНТАРІ • 8 тис.

  • @TechnologyConnections
    @TechnologyConnections  2 місяці тому +808

    Are you looking for a less cantankerous, more shareable version of this video? The condensed version on Connextras has got you covered!
    ua-cam.com/video/_hAuKtoRxJI/v-deo.html

    • @mmmm768
      @mmmm768 2 місяці тому +7

      Kool 👍

    • @555-xd1fo
      @555-xd1fo 2 місяці тому +8

      Another video about something interesting in technology and electronic

    • @Iandmacb
      @Iandmacb 2 місяці тому +27

      Love the idea, but I think short ones should be targeting 15 min or less. At 26min, anyone I might send it to would probably be just as likely to watch the 60 min version.

    • @sinistar6000
      @sinistar6000 2 місяці тому +19

      No, more cantankery!!

    • @mystifoxtech
      @mystifoxtech 2 місяці тому +4

      "Baked beans."

  • @TheAnnyParker
    @TheAnnyParker 2 місяці тому +3549

    I like to imagine Alec is talking to an HVAC rep who's sitting tied up across from him. It makes the video so much funnier

    • @ohnonomorenames
      @ohnonomorenames 2 місяці тому +142

      I only saw this comment at the end and now am trying to decide if I go back and watch the whole hour again.
      You hear that your comment may cost me an hour of my life!

    • @stalincat2457
      @stalincat2457 2 місяці тому +84

      Well since he used terms like "some of you" it's probably more than one.
      What does one call a group of HVAC salesmen?

    • @enmiredbythelazy4401
      @enmiredbythelazy4401 2 місяці тому +60

      @@stalincat2457 The plural of thief is thieves 🤣😂🤣😂

    • @raphiseth6942
      @raphiseth6942 2 місяці тому +13

      ​@@ohnonomorenamesuse the 26 min version for that

    • @JC-jv5xw
      @JC-jv5xw 2 місяці тому +5

      @@stalincat2457 A Sweat?

  • @henningerhenningstone691
    @henningerhenningstone691 2 місяці тому +4199

    How fitting that Alec is just about the only UA-camr who puts the long version on the _main_ channel, rather than saying "here's a bite-size video - for the full-length, go to the second channel"

    • @dave_n8pu
      @dave_n8pu 2 місяці тому +110

      Yep, I'm currently subscribed to close to 120 different channels, it rare to find a upload even close to 20 minutes, closer to 10 ~ 15 minutes is more common.

    • @KurticeYZ
      @KurticeYZ 2 місяці тому +134

      Cuz he knows his fans love this stuff 😂😂😂

    • @thequietpart_
      @thequietpart_ 2 місяці тому +75

      *makes rude gesture at best practices for channel growth*

    • @HunterJE
      @HunterJE 2 місяці тому +48

      Did have a moment of "wait why did I get two almost identical notifs for this video in different lengths" before noticing one was connextras hah

    • @randomblock1_
      @randomblock1_ 2 місяці тому +41

      Normally you don't do that because people get bored and leave early. But because there are so many long videos here, we're used to long videos, and watchtime statistics outweigh early leaving statistics, and the algorithm is happy.

  • @bobfuscator
    @bobfuscator 2 місяці тому +246

    "Maybe you think that's strange, but I think I'm strange too." ...This encapsulates part of the reason I like this channel.

  • @Hurtydwarf
    @Hurtydwarf 2 місяці тому +196

    Whew, he almost missed the nice on 69 but stopped himself.
    You are quite literally the Project Farm of the electrical side of youtube. Your tests are always so indepth and well logged and you come up with creative ways of running these tests.

  • @WanJae42
    @WanJae42 2 місяці тому +2771

    I won't bore everyone with the saga, but trying to find an actual pro HVAC installer in a major market that understood this stuff and was willing to work with me took over a year and too much of my life energy.

    • @phealy3330
      @phealy3330 2 місяці тому +52

      This is too true

    • @TheRealE.B.
      @TheRealE.B. 2 місяці тому

      Brain drain from the trades.
      If not going to university is seen as failure, then you're going to have a lot of failures doing important jobs that don't require a degree.

    • @the_darkgameryt
      @the_darkgameryt 2 місяці тому +54

      How were you all here 3 days ago when it was only uploaded 7 mins ago!?

    • @EvenTheDogAgrees
      @EvenTheDogAgrees 2 місяці тому +5

      Tell me about it...

    • @nairocamilo
      @nairocamilo 2 місяці тому +136

      ​@@the_darkgamerytthese are usually paying members who get to watch the video early

  • @88porpoise
    @88porpoise 2 місяці тому +820

    One of my favourite things about heat pumps:
    My parents regularly used the old cliche line of parents telling their kids to close the doors / windows, "we aren't air conditioning outside".
    And now they aircondition the outside for half the year.

    • @andrebaron1387
      @andrebaron1387 2 місяці тому +62

      Dang it, you mean as a Dad if I go for a heat pump I won't be able to use that line?! Aww man!

    • @randomname4726
      @randomname4726 2 місяці тому +9

      ​@andrebaron1387 Yes you still can.

    • @estrheagen4160
      @estrheagen4160 2 місяці тому +33

      The line is technically wrong, if you open the doors you aren't air conditioning anything, but you are dehumidifying outside. Because a heat pump where the hot and cold sides are in the same connected space is exactly that, a dehumidifier.

    • @atk05003
      @atk05003 2 місяці тому +51

      ​@@andrebaron1387 Just replace it with, "Close the door, I just paid to move that heat!"

    • @Chriscraft50
      @Chriscraft50 2 місяці тому +6

      What were you, born in a barn?

  • @bloooning1
    @bloooning1 2 місяці тому +81

    Michigander here, i LOVED the hard flex on midwesteners having those most common sense for the past 100 years. my house is 100yrs old and guess where my vents run??? THROUGH THE WALLS

    • @jimjjewett
      @jimjjewett Місяць тому +4

      Plenty of Michigan houses use the basement for heat ducts, which has the same good result as his garage route or Christmas lights. The basement doesn't have to be as comfortable as the living quarters, but you don't want the pipes near the washing machine to actually freeze. That said, I personally miss the older norm of "It's winter. You can wear long sleeves." so that going outside didn't require such an extreme transition. (Though lately, we mostly solved that by skipping winter.)

    • @bellemorelock4924
      @bellemorelock4924 Місяць тому

      My current home turns 100 this year. In around 2021 it had a spaghetti octopus installed in the attic. My oh my how that is working. The only insulation is 2-3 inches of "rock wool" between the ceiling joists, and the attic has open vents on both sides and the top (two whirlys AND a peak gap). The bills are ungodly, and the system heat cannot keep up below 40 F, running nonstop. Its at best 10 F warmer in the attic than outside. It didn't seem too strange, coming from homes in Florida, but the delta-T is at most 30 in Florida at any time of year, and attic venting helps there. The same system here, with tree shade, cools the home very efficiently (cheap). Hopefully I won't be here next winter!
      Also, the "droop" was NOT set by the installer, and defaulted to zero, the signal for a shared Gas Heat/AC system. Why? With "cold" here being 20 F, and the droop at 5, the "strip heat" still takes over around 50 F indoors! And the bill is still enormous for 55 F interior temps. Its ghastly when these things are done wrong. In my case, the spaghetti octopus in an actual freezer is my problem. Did I mention no ceiling fans and 9'8" ceiling? So you sometimes get a hot forehead walking through the house while your legs are freezing.

    • @bloooning1
      @bloooning1 26 днів тому +1

      @@bellemorelock4924 when it comes to the cold feet and hot head I 100% agree. i have nearly the same insulation factor, we had a stint by me where it was -10 for a good week or so and there was a SERIOUS draft coming from my front door and each room had a different temperature. plaster only does so much to hold heat lol

  • @jamikellburns4551
    @jamikellburns4551 Місяць тому +32

    As a hvac tech. We do load calcs on every single sale (except mobile homes). We fit to the home but upsize the coil a half ton to dehumidify a little more. We're also trying to get into insulation to help our installs work more efficiently so this video was awesome to listen to

    • @bellemorelock4924
      @bellemorelock4924 Місяць тому +1

      You deliberately mismatch the air handler to "dehumidify a little more"? That is genius, if you are in Louisiana, Mississippi, etc, but reverse if Arizona Colorado etc. At first I misread this as "we upsize... a half-ton" (typically implying the comp or whole split unit) which dehumidifies _less_ not more. Also, just from experience, most homes are too dry 90% of the time. It can help some elderly and allergy sufferers as long as they drink an extra 2-3 quarts of water daily to compensate (almost none do).

  • @Goabnb94
    @Goabnb94 2 місяці тому +729

    Is this the ultimate Technology Connections video? Combining space heaters, with extension leads, with incandescent Christmas lights, with heatpumps and the latent heat of vaporization? Like a call back to every previous video.

    • @winrawrisyou
      @winrawrisyou 2 місяці тому +99

      It can't be. I watched the whole thing and there was no dishwasher detergent powder anywhere...

    • @MrKANIOREX
      @MrKANIOREX 2 місяці тому +45

      @@winrawrisyou Except in 35:32

    • @oliverer3
      @oliverer3 2 місяці тому +28

      Might need some more antiquated photography methods. Oh and more relays!

    • @romangiertych5198
      @romangiertych5198 2 місяці тому +19

      Don't forget obsolete media formats!

    • @ajbp95
      @ajbp95 2 місяці тому +14

      One or two turn signals wouldn't have been out of place...

  • @Deucehoru
    @Deucehoru 2 місяці тому +1310

    As someone in the HVAC Trade, this video is extremely valuable to homeowners and you are empowering my own standards. Not only that, you are calling out the predatorial practices of HVAC Companies. Heat pumps are amazing tech, and I would cite this source 7 days of the week. Fantastic breakdown, thank you!

    • @Metallica4Life1995
      @Metallica4Life1995 2 місяці тому +15

      But even he said Heat Pumps are just ACs working in reverse. Don't get me wrong, ACs in themselves are amazing tech but they're nothing new, and reversing them isn't something that we didn't know we could do for ages.

    • @MonkeyJedi99
      @MonkeyJedi99 2 місяці тому +36

      @@Metallica4Life1995 On the coldest days I have seriously contemplated putting my window AC units back in, but backwards after fiddling with the thermostat.
      Then I put on a sweater and sit in the fluffy recliner with a book.

    • @Deucehoru
      @Deucehoru 2 місяці тому +83

      @@Metallica4Life1995 This isn't his first video about heat pumps, and just because it's not new, pointing out more efficient systems WITH SCIENTIFIC PROOF is not only refreshing, it's unheard of in 2024.

    • @patrickday4206
      @patrickday4206 2 місяці тому +6

      The problem with refrigerate is the oil breaks down with heat you really don't want to over run it

    • @techedhiko9275
      @techedhiko9275 2 місяці тому +34

      Fun fact, oversizing was super popular in the 80s-90s in Illinois. Not only that but salesman would often say something along the lines of “ours is the same price as the other guys but in our bid you can see that we are putting in a bigger furnace.
      Then they put an 80k in a 700sqft home.

  • @stevesar4867
    @stevesar4867 2 місяці тому +39

    I work at an engineering firm & design HVAC systems every day. You hit the nail on the head! Every time i thought “well what about x” you would say “on the other hand -“ its like you were reading my thoughts. Great video!

  • @EmilySmirleGURPS
    @EmilySmirleGURPS 2 місяці тому +22

    As a Canadian, I absolutely grok your midwestern rant about the placement of ducting and vents. The spaghetti octopus in the attic gave me the giggles.

  • @Maplenr
    @Maplenr 2 місяці тому +381

    HVAC guy here. A lot of the issues I've seen have been lack of adequate training. I've literally googled my way to competency, and that is completely unacceptable. But, they don't care as long as we figure it out eventually because the customer is footing the bill anyways. It's horrifying

    • @hhiippiittyy
      @hhiippiittyy 2 місяці тому +54

      I was in HVAC for years, and had to learn so much of the stuff myself.
      It's a chronic issue with the entire economy... nobody wants to train, but everybody complains about how unqualified people are.

    • @ecospider5
      @ecospider5 2 місяці тому +21

      I have found this to be true. If I give real useful information to my hvac installer they will actually use it. I just have to also respect what knowledge they have.
      Also I had one hvac installer say he enjoyed coming to my place because I stood and watched but not to complain but so I could learn. And we would talk about new hvac technologies. This was a decade ago so my heatpump is only efficient down to 25f. We talked about the idea of stuff that is on the market now. He was not having those conversations many other places.

    • @coyote_den
      @coyote_den 2 місяці тому +15

      No kidding. When my new system was installed a few years ago (2-ton, heat pump, 11.5kW aux heat) about the only thing they got right was they put the heat pump outside and the air handler inside.
      They reused the existing lineset that was too small, which they had to fix. Unfortunately they didn't fix anything else:
      Reversing valve was left disconnected because they didn't know how to program the thermostat for B vs O. I fixed that.
      W was wired to W2 at the air handler, but I do not have 2 stage aux heat. Combined with the reversing valve issue that means *I HAD NO HEAT AT ALL* the first time I needed it.
      HP is a 2-stage unit, wasn't wired that way. I fixed that.
      Since then I have learned a lot about HVAC, including how to check and adjust charge, find leaks, etc.. and I'm just an IT guy.
      And yes, they did try to upsell me on the tonnage. I insisted I only needed 2 ton.

    • @1337billybob
      @1337billybob 2 місяці тому +1

      @@coyote_den I went over tonnage several years ago when I replaced my unit. The house is a '57 in the desert chaparral which did get hot back in the day but not like today. The walls were thin and the old unit could keep the house at 88 F running 24/7. The new unit was 3.5 tons for 1250 sq ft with a detached garage and a roof too low guys wouldn't install or said it wasn't worth the effort to install a fan. With the new unit in it we kept it at 78 F in the summer and basically kept blackout curtains up during that time. I don't think it could get below 78 F. When I moved the container I was loading ceiling (where I'd be up to do the tie downs) got to 120 F, I'd do 20 minutes then go inside chug water lay down for 20 minutes. Prep for 20 minutes then go out and do another 20 minutes of loading. I worked till past midnight cause that was cooler.

    • @evancombs5159
      @evancombs5159 2 місяці тому +1

      ​@@hhiippiittyy yup this is the problem with outsourcing all training to schools.

  • @Rintarok5
    @Rintarok5 2 місяці тому +619

    Am HVAC design engineer (floor plan layouts not the actual units), one of the reasons why gas furnaces are always oversized is because that 60k BTU is the smallest many manufacturers make, and they end up being the most common/cheapest because they're used on everything 5 tons and under. To get a smaller heater, you basically have to go electric or heat pump

    • @TechnologyConnections
      @TechnologyConnections  2 місяці тому +370

      I _almost_ made this point but I did find some 30k BTU furnaces on the market so it was a damned-if-do-don't type situation.

    • @eris_void
      @eris_void 2 місяці тому +10

      @@TechnologyConnections What about maintenance concerns over time with wear and tear?

    • @CoffeeKadachi
      @CoffeeKadachi 2 місяці тому +69

      @@TechnologyConnectionsthey’re definitely not common. Even for a lot of package units, “low” heat specs are 54K btu. That’s also the smallest furnace I can even get from our supplier, and I’m based in Vegas where we hardly need any heat in the winter

    • @averagejoeprojects2885
      @averagejoeprojects2885 2 місяці тому +28

      Came here to say this too. Down south Furnaces get even more oversized because you may actually need 48kbtu of cooling but only 60kbtu of heat. Well 4 ton drive furnaces start around 80kbtu but most I come across are 120k!

    • @James1095
      @James1095 2 місяці тому

      That has been a frequent source of annoyance. I have installed several dual fuel (gas furnace + heat pump) systems and I found a very limited selection of furnaces that could move enough air for the heat pump without being vastly oversized. At least 2 stage and modulating furnaces are affordable now and help to alleviate this, I replaced the originak 100k btu 80% furnace my house came with with a 60k btu 95% modulating furnace and most of the time it runs at its lowest setting.@@averagejoeprojects2885

  • @itz_premium
    @itz_premium 2 місяці тому +14

    Thank you for stopping and adding the obligatory "69, nice" as is customary proper internet etiquette.
    Love all your videos dude, you are inredibly thorough.

  • @matt65535
    @matt65535 2 місяці тому +24

    HVAC guy is coming out this afternoon to discuss replacing my house's 15 year old AC/Gas Furnace combo. As a fellow midwesterner I was already planning on getting a heat pump specifically due to your previous video, but it was nice for this one to pop up today and give me a reminder.

  • @Livlifetaistdeth
    @Livlifetaistdeth 2 місяці тому +371

    I haven't bought a dishwasher pod in over a year. I couldn't be happier about knowing how dishwasher detergent works. So i will be watching this entire show from beginning to end.

    • @rubenmejia942
      @rubenmejia942 2 місяці тому +60

      Thanks to Alec, I stopped buying pods and stuck to generic powder. Because of the tips in that video, my dishes come out clean every time.
      Technology Connections is one of the most informative channels on UA-cam. It's amazing that a single guy with a lot of passion and dedication can produce higher quality content than anything that corporate media does.

    • @agcons
      @agcons 2 місяці тому +14

      That's the video that showed up in my feed one day and caused me to subscribe.

    • @nokidding152
      @nokidding152 2 місяці тому +14

      It was the toaster for me. Oh to be young again and experience the thrill for the first time.

    • @questionblechoices
      @questionblechoices 2 місяці тому +2

      Same!

    • @surferdude4487
      @surferdude4487 2 місяці тому +7

      I refuse to pay the stupidity tax on pods of any sort. Thanks to Alex, I know what the other part of the dishwasher degergent dispenser is for. My very old, portable dishwasher works better than ever.

  • @woodruffjb412
    @woodruffjb412 2 місяці тому +328

    As a 45 year veteran HVAC company owner, you made a GREAT episode! Also, the pith was outstanding!

    • @Lyrandar
      @Lyrandar 2 місяці тому +10

      Preach those heat pumps to your customers.

    • @ArthursHD
      @ArthursHD 2 місяці тому +8

      Oversizing a heat pump a bit would make sense if a smart thermostat would track power price and local PV production adjusting temp to the allowed wiggle room in order to save money.

    • @RisenThe
      @RisenThe 2 місяці тому +2

      When will we all have geothermal heat pumps? Cold water goes into the ground, 59F water comes up, goes into heat pump. Repeat.

    • @TechnologyConnections
      @TechnologyConnections  2 місяці тому +58

      @RisenThe At this point, I'm not pushing anyone towards geothermal. The constant improvements in cold climate air-source heat pumps mean that the returns on going geothermal just keep on diminishing and the added expense takes _forever_ to be recouped. We can move much faster going air-source and get 95% of the improvement.

    • @James1095
      @James1095 2 місяці тому +4

      Oversizing a heat pump really isn't a good idea. It's even more important than with gas furnaces to get the sizing correct so it doesn't short cycle or resort to excessive use of auxiliary heat. You have to balance heating and cooling as well, in most regions the heat vs cool requirement is not symmetrical. @@ArthursHD

  • @tedkrapf1302
    @tedkrapf1302 Місяць тому +8

    Software engineer here. If someone specs the Manual J Calculation thing, I'm sure I could code it. Thanks for another great and interesting video, Alec!

  • @bhzucker
    @bhzucker 2 місяці тому +21

    Just wanted to say it's been amazing to watch this channel grow in size, success, and technical polish, without budging a millimeter from its principles, its tone, or its sense of humor. Keep up the excellent work!

  • @DeviantOllam
    @DeviantOllam 2 місяці тому +419

    I was loving this video completely the normal amount (which is already a lot, given this channel) but when the holiday lights came out, that was a +3 smile bonus immediately 🎄

    • @phealy3330
      @phealy3330 2 місяці тому +5

      The twinkling really makes it special

    • @SupremeRuleroftheWorld
      @SupremeRuleroftheWorld 2 місяці тому +17

      a wild Deviant appears!

    • @christo930
      @christo930 2 місяці тому +1

      There is no such thing as a holiday light. It CHRISTMAS lights.

    • @petergerdes1094
      @petergerdes1094 2 місяці тому +9

      ⁠@@christo930So what are lights sold in India for Dwiali?

    • @DeviantOllam
      @DeviantOllam 2 місяці тому

      @@christo930 you know that you don't have to reply to every single comment on the Internet that you don't like, right? you can just scroll right on by and it won't hurt your web browser or anything. please feel free to use this helpful tip to improve your future Internet experience. 💚👍

  • @effwrench7524
    @effwrench7524 2 місяці тому +572

    I am a HVACR professional and I now train others in the HVAC industry. This is solid gold. I strive to instill in my trade that we have been constantly oversizing equipment for as long as the trade has been around.
    I converted to what is called a dual fuel setup about 10 years ago that is a heat pump with gas backup heat (lots of boring details as to why I went with that setup)
    When I bought my house it had a 120,000 btuh furnace installed. I now heat the house with a 3 ton heat pump which matches the cooling load on the home it is matched with the smallest furnace I could get that can provide airflow for the HP and has the capability to operate at 40% of its rated capacity. I live in a cold weather climate and with some minor help from the furnace on that colder than cold day once In a while it keeps my home very comfortable.
    Using similar thermostat technology I can track my power and gas usage and typically my furnace runs less than
    15 minutes per day most days. And that runtime is almost all when the heat pump is defrosting.
    My area has incentives from various agencies and organizations will completely if not more hand cover the equipment cost to the contractor for the cost differences in the equipment from AC to HP units. Installation cost differences given modern thermostats is almost $0
    A lot of what someone people will call out as flaws in his analysis are not reading between the lines in his data and methodology. You simply cannot give a masterclass on absolutely everything that goes into this stuff in one hour! Some details are left out.
    Great video
    Anyone who says otherwise is definitely selling something

    • @James1095
      @James1095 2 місяці тому +22

      You sound like one of those that knows your craft. There are a lot of goobers in the HVAC industry, despite all the talk about manual J calculations, I suspect either very few actually run them, or they are not very accurate (garbage in-> garbage out?) because it is very rare that I encounter a furnace that is not grossly oversized.

    • @Steevo69
      @Steevo69 2 місяці тому +8

      I live in Montana, we use a 5 ton equivalent heat punp for heating and cooling, and despite only having 8 inches of fiberglass roof insulation in a valulted ceiling 4000 Sq ft monster. Unless it goes below 0F we don't even need additional heat for it to keep up at 64F at night and 68F during the day.
      Average cost is $270 a month, for heating, hot water, cooling (we love it cold, so 66F during the summer inside) and the geothermal backed heat pump also makes hot water.

    • @MegaLokopo
      @MegaLokopo 2 місяці тому +4

      What if I don't want my furnace or ac running 24 hours a day? Having a house that is comfortable in temperature and noise is a feature not a bug.

    • @Malcontentmatt
      @Malcontentmatt 2 місяці тому +1

      Everyone should know a guy or two like you. I don't know any!

    • @Ralphie419
      @Ralphie419 2 місяці тому +6

      @@MegaLokopo - You must have a noisy one. They aren't all that way. My wife keeps asking me if ours is running because it's quiet enough that we can barely hear it. Sometimes she'll hear something and ask and it's the refrigerator humming instead.

  • @quaidbergo
    @quaidbergo 2 місяці тому +15

    That rant was glorious! "You probably think this video is about you" 😂

  • @Adam90028
    @Adam90028 2 місяці тому +11

    I love your sass on the whole ductwork rant. It cracked me up. As a Michigan resident I salute you sir!

  • @Codexionyx101
    @Codexionyx101 2 місяці тому +915

    This UA-cam channel has made my plans for a mega-mansion _really_ weird.

    • @NXTangl
      @NXTangl 2 місяці тому +103

      Mansions are overrated. Better to have a house just big enough to have all your friends over.

    • @thunderusnight
      @thunderusnight 2 місяці тому +236

      Now you need a well sized heat pump, a commercial dishwasher, a defunct Japanese microwave, very specific christmas lights, and a smart heat controller

    • @hasmond6808
      @hasmond6808 2 місяці тому +4

      Any ideas for any special rooms in your mansion? Like an arcade room and stuff like that.

    • @Codexionyx101
      @Codexionyx101 2 місяці тому +24

      @@hasmond6808 A music studio is definitely on the table.

    • @Codexionyx101
      @Codexionyx101 2 місяці тому +75

      @thunderusnight Don't forget a 1950's toaster!
      Of all the kitchen appliances he's talked about, that's one of the few I actually want.

  • @krn_ndy
    @krn_ndy 2 місяці тому +381

    The delayed "nice" absolutely took me out with laughter. Was not expecting that, but I am absolutely here for it

    • @jeremyjedynak
      @jeremyjedynak 2 місяці тому +6

      He forgot to mention the LTT Store though.

    • @Jarran2R
      @Jarran2R 2 місяці тому +34

      @@jeremyjedynakthe 69 nice joke isn't a linus tech tips reference though

    • @lcgluciano15
      @lcgluciano15 2 місяці тому +9

      Internet rules, you say 69 you have to say "nice", you can also say it after 420 but it's not required

    • @sparkysho-ze7nm
      @sparkysho-ze7nm 2 місяці тому

      Quality humor prevails

    • @FaZekiller-qe3uf
      @FaZekiller-qe3uf 2 місяці тому +1

      @@jeremyjedynakSinus didn't start "69-nice."

  • @Frontofshoe
    @Frontofshoe Місяць тому +4

    I’m a HVAC salesperson in the DC Maryland Area. Old oversized equipment is so prevalent here. And you can take your time explaining to the customer why it’s oversized, but when you have customers who say why change it if it’s worked for all these years and other salespeople just spec what they had. I did that to a customer…had a 3.5 ton ac and a old 150k furnace from the 40s…i put a 70k furnace and 24k heat pump. Row home about 1800sq ft. Customer kept bringing up how this website was saying he needed 4k…we installed it, he loves it. Great video!!

  • @GregDickinson75
    @GregDickinson75 2 місяці тому +11

    Man I feel you about the "inside" unit in the attic. My home is built this way, along with *all* the ductwork going through the uninsulated attic. They even stuffed the water heater up there, so that when it inevitably springs a leak near the end of its life, you get to come home to your ceiling now being on the floor!

  • @TheCrustyCupcake
    @TheCrustyCupcake 2 місяці тому +626

    1 hour video from Technology Connections? It just became movie night! Always a treat.

    • @ubermenschen01
      @ubermenschen01 2 місяці тому +9

      It's my sleepover, and I get to choose the movie

    • @swimheiss
      @swimheiss 2 місяці тому +5

      @@ubermenschen01 Opposite of a sleepover for me. Wife was out to watch basketball, so this was my bachelor's night in!!!

    • @AgentTasmania
      @AgentTasmania 2 місяці тому +11

      And it's about American issues almost totally irrelevant to my Australian arse? I'm in.

    • @beedslolkuntus2070
      @beedslolkuntus2070 2 місяці тому +12

      @@AgentTasmania
      I’m from the Middle East, we have no heaters here, I’m in a damn desert AND I have exams coming up, but I still watch this. Let’s go

    • @krissp8712
      @krissp8712 2 місяці тому

      Yeah, if Alec had an hour of stuff to say this is gonna be good.

  • @gene450000
    @gene450000 2 місяці тому +420

    As a HVAC service tech I have know this for over 50 Years. I was asked to design and install a new furnace and A/C system in a house which was having an addition added. The addition was almost 2000 Sq Ft. The house was built in the 60's had a large furnace 160,000 BTU. I did a precise heat load calculation and added a multi zone damper system to the new furnace. The new furnace was 125,000 BTU 95 percent. The town inspectors said I was wrong and forced me to provide the calculations. They OK'd the system a month later. and it ran great.

    • @QuarterSwede
      @QuarterSwede 2 місяці тому +43

      You’re adding dampers so you’re already ahead of MOST home builders that cheap out on those.

    • @Tupsuu
      @Tupsuu 2 місяці тому +23

      Even that seems quite large. I live in Finland and the recommendation is 75W per m² (24 BTU per ft²) so about 50000 BTU for the 2000 ft². My calculations might be wrong and ceiling height might be much larger in your case but it's still a large difference.
      Edit: I completely missed the part about an addition so it makes a lot more sense now.

    • @diconustra
      @diconustra 2 місяці тому +27

      When I had mine replaced, I tried to convince the HVAC contractor to drop down in size. Old furnace was 100kBTU, 60% efficient, and on the coldest day of the year (-25f) it ran 60% of the time. I figured that the new 97% efficient furnace could be as small as 60k BTU. They insisted on at least 75k BTU, so that's what I got. Based on cycle time on the coldest day, it could have been one size smaller.

    • @frequentlycynical642
      @frequentlycynical642 2 місяці тому +26

      A 2000 sf ADDITION? Welcome to America, where more than enough is never enough.

    • @navb0tactual
      @navb0tactual 2 місяці тому +2

      Well you never know what that person's going to use that space for. Sounds to me like a couple of rooms and a new unit for tenants. Which is respectable.

  • @rangerdoc1029
    @rangerdoc1029 2 місяці тому +8

    HVAC professional for 35 years. You are on the money. Plus installing even a like-sized high efficiency syatem on old restrictive duct work completely negates the benefits of the new equipment.
    I'd say 90% of the equipment out there is grossly oversized.

  • @frankis94
    @frankis94 Місяць тому +4

    You absolutely hit the nail on the head with your criticism of the separation of sales and technicians. While a tradesperson’s primary job is installation and maintenance, not “closing deals” their technical knowledge is utterly necessary to ensure each customer gets what they need. If you ever, EVER want to know what you need, talk to someone who does the actual work and is clearly passionate about what they do.

  • @TheBloodyViki
    @TheBloodyViki 2 місяці тому +348

    I love this dude, he's one of those youtubers where after you watch one video you're hooked.
    Also thanks to him my dishes are cleaner than ever.

    • @davidg4288
      @davidg4288 2 місяці тому +11

      I never bothered with that rinse fluid, I vaguely even remembered there was a place for it in my dishwasher. After watching his dishwasher video I bought some and tried it. It works great, the glasses are shiny now and as a bonus it eventually cleaned the calcium deposits off the inside of the dishwasher.

    • @OperationDarkside
      @OperationDarkside 2 місяці тому +6

      He even cleaned your dishes. What a guy xD

    • @DangerB0ne
      @DangerB0ne 2 місяці тому +2

      ​@@os2developerI feel you. The options in my neck of the woods priced my family out of the older townhouses in the town I work in and into a more rural detached single family home. I'll gladly pay the privacy tax, though. I was tired of hearing domestic spats, rough sex, loud music, and home improvement through the walls at all hours of the night when we rented.
      But to the original comment, my dishes have never been cleaner and, since installing LEDs in all the light fixtures, my power bill has never been lower.

    • @SimuLord
      @SimuLord 2 місяці тому +1

      @@os2developerI share three of my walls plus the ceiling and the floor. I have used my heater exactly not at all for the entire winter.
      As a comment I posted elsewhere in this section pointed out, even in Seattle it got as cold as 12F/-11C at one point this winter! But between my neighbors keeping their own places warm and the beefy gaming PC running beefy games taking up my living room, I've occasionally had to open the window just to bleed off the excess heat where it's gotten as hot as 78F/26C inside, which is the average high temperature for Seattle in July.

    • @DangerB0ne
      @DangerB0ne 2 місяці тому

      @@os2developer Nice! The house my wife and I bought is a bit older, so is in need of weatherproofing and better insulation but it's otherwise fine.
      The swamp cooler will probably be the first major HVAC appliance to go. We live in a desert so they work quite well but I'd rather have a central heat pump/air conditioner with an optional furnace instead. Deserts get mighty cold at night (especially in the winter) so some extra on-demand heat is a good thing.

  • @Gottfried.Leibniz
    @Gottfried.Leibniz 2 місяці тому +370

    "The house didn't burn down" - now that's a motto I can live by.

  • @steebs3e
    @steebs3e 2 місяці тому +4

    I have a 2400 square foot home that was built in the 50’s and is insulated in the loosest sense of the word. I replaced our radiant boiler with ducted 4/5 ton heat pump system (I did all the work myself). My manual J put me at around 42000 btu loss so I got the bigger unit which can be switch to 4 ton mode for higher efficiency. It’s has never let me down in the northern Michigan winters where sub zero temps are regular. I have 10kw heat strips which I've never needed as backup, but they do run during defrost cycles to keep the air warm while the fan runs. this was our 4th winter with the system and i have no regrets.

  • @IwasFRAMEDiTELLyou
    @IwasFRAMEDiTELLyou Місяць тому +1

    I really appreciate the way you split this video up and put it on the other channel, I for one would still be excited for this video if it was twice as long and even more in depth, but I've been looking for a way to get my dad interested in your channel and the condensed version might be exactly what I need for that

  • @TheChipmunk2008
    @TheChipmunk2008 2 місяці тому +347

    You got a mention on HVAC overtime over this video, HVAC professionals agreed with you by and large. Good point well made Alec

    • @autohmae
      @autohmae 2 місяці тому +4

      I don't know anything about the HMAC industry, but I see you are one of the most active commenters on that podcast. 🙂

    • @coyote_den
      @coyote_den 2 місяці тому +14

      HVAC technicians and engineers all know proper sizing.
      HVAC *salescritters* do not care, and in most cases the tech simply have to install whatever the customer was sold.

    • @justSomeUserOnYT
      @justSomeUserOnYT 2 місяці тому +2

      HVAC installers generally pride themselves in their work. Not always, but generally.
      The scummy sales people just try and get the biggest paycheck possible

    • @Squat5000
      @Squat5000 2 місяці тому +2

      🇷🇺🇷🇺🇷🇺🇷🇺🇷🇺🇷🇺🇷🇺🇷🇺🇷🇺

    • @TheChipmunk2008
      @TheChipmunk2008 2 місяці тому +1

      @@Squat5000 Oh aren't you original... RU yes... russia is a good country. Shame about it's government and military

  • @ToxenL30
    @ToxenL30 2 місяці тому +418

    Former HVAC sales rep here. Great video! While attending a hvac training, I was giving a rather shocking Stat, less than 10% of hvac sales in 2022 had a load calculation preformed prior to the sale of a new system.
    I'm not innocent either, as I was never told what or how to preform one of these and became part of the problem. The more I learned in that role the more shocked I was at how much damage and headache I likely caused for homeowners.
    Your comments on the lack of communication between departments is actually rather accurate and something that has, as of late become a much bigger focus for the company. (who I still work for under a different position, in another trade department) so atleast at our national company things are changing and loadcalcs are becoming a much larger focus company wide. The issues of system sizing has been a regular cause of issues, callbacks, and heachaces for us and the customer.

    • @Timeward76
      @Timeward76 Місяць тому +2

      I wonder if it'd be possible to semi-automate the load calc. Some kind of equation that you can input the parameters to (shared walls, insulation, basement or slab, attic, etc)

    • @vidard9863
      @vidard9863 Місяць тому +10

      As a technician working on a wide variety of buildings, load calcs are nearly useless:
      First the customer will not pay for a useful load calculation, so all you get is calculations based on ASSUMED values.
      Secondly, and because of this, the new load calculation almost always causes problems with callbacks and customer expectations. As long as the customer was happy with the previous unit, no major changes happened to the building and you don't notice obvious issues, just put in a unit with the same capacity, no more than a half a ton increase AT MOST.
      Where customers are more willing to pay for a good load calculation, and/or you are replacing both the unit and the ductwork, particularly if you are re engineering the ductwork, THEN load calculations are great, and incidentally you NEED to replace and re enginer the ductwork if you move more than a ton of capacity EITHER way.
      The real problem that I have seen is that technicians are encouraged to upsize units at every turn. That's a problem with management, not load calculations.

    • @vidard9863
      @vidard9863 Місяць тому +1

      ​@@Timeward76they do that, it's industry standard, unfortunately however the results are based on the accuracy of the assumptions...

    • @SoloRenegade
      @SoloRenegade Місяць тому +1

      so, it's not the consumer at fault, but rather the HVAC industry, good to know.

    • @vidard9863
      @vidard9863 Місяць тому +7

      @@SoloRenegade it gets complicated. The consumer drives the industry, and they have rewarded an industry structured to rip them off. Literally one company I worked for was structured old school, and in such a way as to benefit the customer. They went out of business and got bought by a new school company structured to rip people off, and they were rewarded by consumers with more money.
      So as individuals consumers are not at fault, but collectively consumers are too ignorant and short term minded.... But that seems to apply across all industries.

  • @rafaelmarkos4489
    @rafaelmarkos4489 Місяць тому +4

    I find myself continuously amazed by the fact that people in North America are fine with paying north of $200,000 for a house made of wood. Insane.

    • @ChrisUrbinsky
      @ChrisUrbinsky 13 днів тому

      Homes are wood all the way up. Multi-million dollar homes are made of wood.

    • @rafaelmarkos4489
      @rafaelmarkos4489 12 днів тому +1

      @@ChrisUrbinsky I live in a developing country, and we actually use concrete for our houses. Makes them last a while.

    • @synapticburn
      @synapticburn 5 днів тому

      Why? I've worked on plenty of wood homes here over a hundred years old
      There are wood homes in Europe that are centuries old
      Just have to know what you're doing and they ride out hurricanes just fine

    • @jordanledoux197
      @jordanledoux197 3 дні тому

      @@rafaelmarkos4489 In North America, wood is literally cheaper to use as a building material, and faster as well, and can be used to build more types of things and architectures.

    • @rafaelmarkos4489
      @rafaelmarkos4489 3 дні тому

      @@jordanledoux197 My country is closer to the equator, and has poor public infrastructure, so any house built of wood would likely not be able to stand through the first storm that rolled through.

  • @jan-pcro
    @jan-pcro Місяць тому +1

    i realy like these detailed and long videos.
    since i can stop at any time and continue when iam ready for it again 👌🏾😎
    thank you!

  • @user443
    @user443 2 місяці тому +306

    I feel like 29:37 "Through the magic of buying..." was the payoff of one of the longest setups in history. Well done.

    • @raelone55
      @raelone55 2 місяці тому +53

      Christmas lights, HVAC AND Space Heaters in an hour long video. This is truly peak Technology Connections

    • @adora_was_taken
      @adora_was_taken 2 місяці тому +18

      @@raelone55 it's even related to the latent heat of vaporization!

    • @redsquirrelftw
      @redsquirrelftw 2 місяці тому +9

      I laughed IRL at that part. Just the way it pans to all the heaters lol. It was perfect.

    • @the_ratmeister
      @the_ratmeister 2 місяці тому +5

      It doesn't quite beat "Through the magic of buying way too much fucking dishwasher detergent" for me but it's close.

  • @SanguinemLuna
    @SanguinemLuna 2 місяці тому +583

    I'm at the 30-ish minute mark and the volunteer firefighter inside me just cringed really hard... Last night, we had a fire call where someone plugged a space heater into a power strip, burned up the strip, and nearly burned up the outlet... Thankfully no actual fire occurred. Thank you for knowing what you did was unsafe and warning others not to attempt it themselves. Science can be fun but dangerous at times. Love the content.

    • @sean2074
      @sean2074 2 місяці тому +19

      A less dangerous method would be to turn the furnace on fan only mode, and plug one space heater into every circuit.

    • @TechnologyConnections
      @TechnologyConnections  2 місяці тому +222

      @@sean2074 The reason I elected not to do that was because the wattage from the blower motor (which is higher than you might think - typically 200 watts or more) would skew my results. Plus, it was valuable to know which rooms actually have the greatest heating load. But yes - it was a risky setup. I was checking the temps of cords and connections all through the night and had fire extinguishers handy.

    • @LinusBerglund
      @LinusBerglund 2 місяці тому +38

      Why is that? Seriously. I don't have a single outlet in my home that can deliver less than 2300w (10A, 230v). I just went through every power strip and extension cord and they are all rated for at least 3600w.
      The wires in the walls are all girthy enough to not burn before the breaker pops.
      I combined two circuits (total 32A) and I tried a random cheapo extension cord. I stopped after 5700w (didn't dare to go further) and it didn't even start smelling of plastic. The plug got warm though...
      Are American standards that bad?

    • @pyro1324
      @pyro1324 2 місяці тому +54

      @@LinusBerglundIt's because the American grid runs on 120V instead of 230V so 10A is 1200W instead of 2300W.

    • @avernar
      @avernar 2 місяці тому +59

      @@pyro1324 No, the American grid runs on 100+ kV transmission, 5+ kV distribution, and 240V split phase to houses. Most outlets in the home are 120V with a couple 240V outlets for dryer and stove. See his video "The US electrical system is not 120V".

  • @shanejohnson77
    @shanejohnson77 2 місяці тому +4

    Love watching your posts. Always great quantitative and qualitative statements and outcomes. I remember when installing an HVAC in a home that wasn't HVAC to start asking the rep to be sure it was PROPERLY sized and not just guestimated. He spent the time measuring and covering the house, settling on about a 2.5 Ton HVAC system with heat pump. All comparable homes were 5 tons for some reason. I said I wouldn't pay for anything we didn't need and to prove out the math... this was in the 90's. That house maintained 70 degrees year round just fine for me. Best investment I made at the time along with the new properly installed well with pressurization, hardness management, and 5 stage filtration. (Unlike the old system which was well direct water on demand with no pressurization).

    • @shanejohnson77
      @shanejohnson77 2 місяці тому

      That 2.5 was also sized in a way that if we enclosed the garage with insulation & such, it would still have been more than enough. The math showed we could take the hottest/coldest days on record with room to spare. Even added humidifier & higher grade filtration (before the hepa boom) to the mix for ensuring air quality and comfort.

  • @rollymartin
    @rollymartin 2 місяці тому +1

    We always enjoy your insights! We had a heat pump installed on Feb 29 - inspired by the way you interpreted the technology some time ago. This was hybridized with our 2021 HE gas furnace. We get an $800 carbon rebate each year (Canada) - and Ontario's electricity supply is quite low in carbon production. We're not expecting to make money (net), but we'll be content because we are reducing our carbon emissions. With wind turbines to the south, solar installations to the north and a new natural gas 'peaker' plant to the west, the future of energy is always on our horizon. Thanks for all the effort you put into your productions! David, Amherstview, Ontario

  • @antibrevity
    @antibrevity 2 місяці тому +720

    As a (former) licensed HVAC installer and technician, I want to thank you for giving this industry a stern talking to. I did load calculations for my jobs and there was a (short) time where the state required them for every final inspection, but that was abandoned because few of the HVAC people here are intelligent enough too do basic math :(.
    I'm not not kidding as they also had to seriously dumb down the state licensing test in a desperate attempt to help these idiots pass, despite requiring them to have all applicable code books with them during the test! There was such a shortage of licensed workers that homes could not be built and I imagine this has only gotten worse.
    Thankfully, I do know of local HVAC companies that are qualified and very good at their job, but I also know of some that are both incompetent and debatably criminal as they'll overcharge their own mother and then brag about it to other contractors.
    Informing consumers of these issues is very valuable, so thank you. This is perhaps the most important HVAC-related video you've done since the one on stupid portable air conditioners.

    • @RAWBOT301
      @RAWBOT301 2 місяці тому +11

      You really need to do a whole home model factoring location, sun, insulation, volume, etc, and the cost of doing that model is the half the cost of the system. Just makes more sense to do estimates and caution on the side of error in most cases. Ive run models for larger buildings for energy code reasons and the modeling cost around $6k. No single family home owner is going to pay for that unless it is high end and going for LEED certification, which Ive also done... on a $20 million house.

    • @Traxxis03
      @Traxxis03 2 місяці тому +52

      YES! This is so sadly and absurdly true! I asked all four HVAC contractors that bid the house I was building to show me their manual J's load calculations... two said they didn't do one, they based it off my square footage... and astonishingly the other two DIDN'T EVEN KNOW WHAT A MANUAL J WAS!
      Not surprisingly, they all suggested 2 4 ton or bigger units for my 3200 square foot, 2 story insulated concrete home... but after paying $1200 to an outside engineering firm, the ACTUAL numbers called for a SINGLE 3.5 ton. I've been heating and cooling (heat pump) my house for 7 years now with a single unit.
      HVAC contractors are a joke.

    • @FaustsKanaal
      @FaustsKanaal 2 місяці тому +28

      Goes for most skilled labour these days. There are very few capable people, because if you are able to understand all the code as an electrician or HVAC or plumber, you will either start your own business or be promoted away from the field. Either way you end up in an office. I mean someone who can make master electrician might as wel go for electrical engineer. Pay is better. So the people holding the wrenches and screwdrivers will always be the mid to bottom tier.

    • @Connie_cpu
      @Connie_cpu 2 місяці тому +41

      I wish I could shove this comment in the face of anyone who ever said "Why do we need to learn this math in school, we'll never use it in the real world." THERE IS TONS OF MATH TO DO IN THE REAL WORLD.

    • @Sololop
      @Sololop 2 місяці тому +8

      But all they need to do is make an excel sheet once and it's good for forever. Ugh.

  • @iliketurtles6274
    @iliketurtles6274 2 місяці тому +379

    As someone with ADHD who struggles to focus on anything for very long, Alec is one of the only UA-camrs who can make a 1+ hour long video on literally anything and keep me hooked the entire way through

    • @danl6634
      @danl6634 2 місяці тому +38

      The sarcasm goes a LONG way to holding attention; it requires active listening to pick up on the humor. Similar to watching letterkenny & the much more nuanced humor.

    • @nashdashflash
      @nashdashflash 2 місяці тому +12

      Same, severe diagnosed ADHD. I have watched what could be considered very boring topics (why US power strips are unsafe and how they could be much safer, etc.) but I find myself watching all the way through and speaking on it later, lol.

    • @sparkysho-ze7nm
      @sparkysho-ze7nm 2 місяці тому +4

      109%

    • @sixeses
      @sixeses 2 місяці тому +8

      It's his voice, and the volume is very even throughout the video. Other Channels, you might have to adjust the volume 20 times in an hour.

    • @JasperJanssen
      @JasperJanssen 2 місяці тому +3

      Lots of killawatts, manually configurable thermostats, manually resetting at the start of the measurement period… jeez, dude. Smart plugs with built in measurement sensors, hooked onto ideally zigbee or if necessary WiFi, hooked to a computer (raspi is fine) running Home Assistant and all you need then is a bunch of temperature sensors to log that you should have anyway.
      It’s like you’re all about making your life easier - as long as it’s not easier than the 80s or 90s.

  • @humancigarette4307
    @humancigarette4307 Місяць тому

    Hey man I just wanna say you are a daily part of my day I watch you every morning with my morning coffee thank you.

  • @NickCageJesus
    @NickCageJesus Місяць тому

    Just checked my data from the same cold snap. my furnace was still under 12 hours for the day. It was also far colder here and we were home with the heat at a higher setpoint. Looks like once this dies, ill be able to size a smaller unit here too (which I already was planning on) Love the well informing videos on this stuff. Keep it up!!

  • @eamonwinden4404
    @eamonwinden4404 2 місяці тому +200

    I live a little further north than you and basically got this lecture from the HVAC professional I had out to estimate replacing my furnace and ac. He said their standard is to determine requirements and then double it because if they don't people get bothered when the house doesn't heat up immediately in the morning, but he recommended going with the minimum if I was comfortable with the reality. He also said if I wanted to save money I should have a home energy audit and then act on all those recommendations first. Thank you for spreading the word.

    • @dancooper6002
      @dancooper6002 2 місяці тому +29

      Excess capacity is a good thing. It keeps things running longer and with less wear. The small savings of a smaller unit pale in comparison to having to replace it twice as often because it is barely up to the task.
      A relative had an old house with a 100+ year old coal, later gas, fired boiler. And it still ran like a top.

    • @salter1630
      @salter1630 2 місяці тому +48

      ​@@dancooper6002That depends on what it is. Some applications actually experience more wear with constant on/off cycling or cycles of increasing or decreasing heat (computers technically "wear down" worse for being repeatedly turned on and off, and is part of why datacenters can actually maintain insanely high uptimes).

    • @ender25ish
      @ender25ish 2 місяці тому +24

      in the US, Home energy audits are also subject to a federal tax credit up to $150 under the Energy efficient home credit. You can also get a $2000 credit for heat pump installation under the same credit.

    • @dancooper6002
      @dancooper6002 2 місяці тому +3

      @@ender25ish Sure, but the first time the stupid thing fails in a deep freeze you have thousands of dollars of damage done to your home that daddy government is not going to pay for.

    • @dancooper6002
      @dancooper6002 2 місяці тому +3

      @@salter1630 Data centers are not home appliances/equipment. The smaller one will have cost cut everything throughout. And it will cycle just as much, if not more, than a proper unit.

  • @godofplumbing
    @godofplumbing 2 місяці тому +103

    I've been in this trade for 35 years, when I do a manual j, I find the existing heating systems are usually around 33% to big. I have lost several heating system replacements, because the customer say I'm under sizing their system. Because all the other companies said you need to go with the same size. The HVAC industry has its problems, but homeowners like bigger systems in their house. So we either conform, or we die in the wind.

    • @Sololop
      @Sololop 2 місяці тому +23

      Most people are afraid of math, and it's incredibly frustrating to show them data and have them dismiss it

    • @Taskarnin
      @Taskarnin 2 місяці тому +12

      I know as a home owner it would be nice to see two quotes side by side in that case. One with the numbers run and optimized and another with my current system.
      I would like to think that I as an engineer would follow your advice, but if the cost difference is not that great then I can also understand the paranoia.

    • @godofplumbing
      @godofplumbing 2 місяці тому +10

      @@Taskarnin exactly, the prices are usually within a couple hundred dollars. I have actually seen the bigger ones sell for less than the smaller ones, do the supply and demand. Customers think that if they get a bigger system they're getting more bang for their money.

    • @rogerk6180
      @rogerk6180 2 місяці тому +5

      Well, if you offer them a smaller unit that is more appropriate and they incist on a bigger unit there is no reason to not give it to them.
      Then it is on them honestly.

    • @godofplumbing
      @godofplumbing 2 місяці тому +10

      @@rogerk6180 exactly, if I refuse to do the job, I will lose the job, and I'll eventually be out of business.
      So I installed the larger ones. Then I hear from Engineers saying that I'm installing the wrong units. Hvac trade is the problem. It's funny, when I get the new heating system inspected, I point out that the boiler is oversized, I do this to cover my ass from the next homeowner who purchases the house.
      The inspector points out that oversizing a heating system is grounds for failing inspection. Then they tell me, that they are not going to fight homeowners on this.

  • @jamesanderton8817
    @jamesanderton8817 4 дні тому

    51:58 is incredibly satisfying. Having expertise and knowledge pay off exactly as you said it would is the best feeling in the world.

  • @danielvivian3282
    @danielvivian3282 2 місяці тому +1

    Again another great video. Thanks Alec, your fellow energy engineer. I really appreciate the sizing examples.

  • @WarrenGarabrandt
    @WarrenGarabrandt 2 місяці тому +751

    I gave up trying to find an HVAC company that wasn't going to lie straight to my face about heat pumps, so I installed it myself.

    • @jongoode3296
      @jongoode3296 2 місяці тому +85

      This was my attitude about solar and well, almost every other service industry anymore.

    • @RvLeshrac
      @RvLeshrac 2 місяці тому

      Tradesmen lie to you about literally everything. The trades, but *especially* HVAC, plumbing, and electrical, are just wall to wall scammers.

    • @JD-xz1mx
      @JD-xz1mx 2 місяці тому +28

      Why do think they're lying, rather than simply being misinformed themselves?

    • @chadhowell1328
      @chadhowell1328 2 місяці тому +49

      I have ended up doing most installs these days myself because of similar situations. The “pros” these days only want to install what puts the most money in their pocket

    • @aprotosis
      @aprotosis 2 місяці тому +107

      @@JD-xz1mx The alternative is worse. Profit motive is one thing, but do you want to hire a "professional" that doesn't know their craft?

  • @mxss115
    @mxss115 2 місяці тому +150

    Ah yes, an hour long video full of dry humor and technical information, my favorite!

  • @SuperVstech
    @SuperVstech Місяць тому

    So true Alec, I have run my company for the last 20 years, but my dad when he ran it was steadfast with the square feet per ton rule for Hvac sizing.
    The manual J load calc along with the manual D ductwork design, really proves the home load.

  • @youseflatif796
    @youseflatif796 Місяць тому +3

    For the people in cold climates complaining about how heat pumps won't work in winter, get a cold climate heat pump. And seal any cracks so the heat won't escape. It's that simple.

  • @Cryowatt
    @Cryowatt 2 місяці тому +168

    Pro tip: share a wall with someone who likes to keep their house _way warmer_ than you prefer. I used to live in an apartment where I shared all my walls and I never turned on my heat.

    • @matsl89
      @matsl89 2 місяці тому +8

      No windows to the outside at all?🫨😁

    • @jamesphillips2285
      @jamesphillips2285 2 місяці тому +16

      @@matsl89 There is a reason many apartments where I live provide free heat. They don't want people shutting off the thermostat and letting the pipes burst.

    • @jongoode3296
      @jongoode3296 2 місяці тому +29

      That's one critique I have with his townhome test, how much heat was he getting from the neighbors who were most certainly running their heat? Does he share 1 wall or 2?

    • @jamesphillips2285
      @jamesphillips2285 2 місяці тому +25

      @@jongoode3296 I had that same concern: until he revealed 7 space heaters.
      As long as the temperature is close, it won't affect the results much.

    • @elizabethpemberton8445
      @elizabethpemberton8445 2 місяці тому +2

      I lived in a basement apartment that had the building’s furnace on the other side of my wall. Score!

  • @JettKuso
    @JettKuso 2 місяці тому +99

    To someone who’s watched every video on this channel, this video is like friggin Infinity War. All the old favorite characters make an appearance, all it’s missing is some painted white LED Christmas lights!
    Edit: Jesus Christ, I was only halfway through and I was joking about the Christmas lights. Touché, Mr. Connections.

  • @lanceperfect
    @lanceperfect Місяць тому

    Always stoked for your deep dives. Wish I'd known all this before the most recent HVAC work. As a fellow midwesterner and science guy I'm still kicking myself for getting swindled and relying on too much gas.

  • @kbouwman64
    @kbouwman64 2 місяці тому

    What a timely video. I just did a version of your experiment. I work on chillers and bulk milk tank coolers owned by dairy farmers. I have been thinking about my next air conditioner/heat pump/furnace. I live in a home built in 1879 or so. I have replaced all of the windows, siding, and insulation. When I moved into the house 40 years ago it had a 100,000 Btu furnace that couldn't keep up on the coldest three or four days of the year. 20 years ago, after some of the insulation upgrades, I replaced this with a 60,000 Btu furnace. This past January, during the same cold snap you used for the video, I installed temperature probes in the supply and return air ducts and sat with a stopwatch and figured out that my natural gas furnace burner was on 2.5 minutes out of every 13 minutes while the outdoor temperature was minus 21 degrees F. And the house was comfortable. I learned that my home improvements have now made my furnace is five times bigger than it needs to be. I will probably go with a heat pump that is 1/4 the size of my existing furnace for the reasons you mentioned. I would like to be able to catch up a little if it gets behind for some reason. I love your videos...keep up the good work!

  • @mikerutter8168
    @mikerutter8168 2 місяці тому +220

    “avoid complaints”. You finally got there! I design heating systems and you are 100% correct; across the board. You only understate the power of whining, relentlessly unsatisfied and miserable complainers.

    • @timothycox6759
      @timothycox6759 2 місяці тому +33

      So true the amount of times we do things that are technically “incorrect” so we dont get dumb service calls and emails and complaints

    • @TechnologyConnections
      @TechnologyConnections  2 місяці тому +64

      Related to your comment - I think we're gonna need to do a _lot_ of working helping people understand how supplemental heat sources factor into all this. Lots and *lots* of comments now are seemingly ignoring that you can (and probably will) have two heat sources with a heat pump. It's a totally different ball game to having a right-sized furnace with no room for error.

    • @swimheiss
      @swimheiss 2 місяці тому +26

      @@TechnologyConnections Even with a properly-sized furnace in a 110 year old house, I like to keep the house set cool in the winter and run a space heater in the rooms I'm using for like 30 minutes to an hour to be comfortable in those few times where I'm both awake and inactive. In the really cold snaps, the electric blankets come out for TV night. At that point, who cares if the house is 60 when a 50 watt blanket will keep you warm for the 15 minutes it takes to get all the animals on your lap, and you have all the heat you want without even the blanket on? Talk about extracting heat energy from the pet food you have to pay for anyway.

    • @draco10111b
      @draco10111b 2 місяці тому +15

      Not sure what to do about people that are cold from being outside for a few minutes and turn up the thermostat because it's cold outside, and they want to get warmer faster. Even when the heater is already running. Same people that like to run the thermostat at 68 in the summer and 78 in the winter. Sigh

    • @HesderOleh
      @HesderOleh 2 місяці тому +6

      How do I go about finding a HVAC company that knows their stuff? My heat pump goes on for too long and raises the temperature too much above the set point, the company that installed it and then another company I had come in tried telling me this is a feature that it doesn't stop heating as soon as the set point is reached because it is a variable compressor. Waking up in the middle of the night because you are too hot to turn the whole system on and off so that it won't turn on again until it goes below the set point isn't a "feature" though. I have read through the manuals and there are quite a few settings that might help, but I don't want to screw things up.
      I also wanted to talk to a company about venting outside air in through filters as it takes the house quite a while to cool down at night in summer even with windows open and that isn't possible when there are bushfires, and how to go about that, but I don't know how to go about finding a company that would be good at that as I don't want to pay for someone to give me a quote when I have no idea of their competency, but it does make sense that I would have to pay for coming up with a solution to fit my already existing system.

  • @mjengel84
    @mjengel84 2 місяці тому +204

    Hearing you talk about Manual J calculations warmed this old HVAC guy’s heart. Thanks for a great video.

    • @NickiRusin
      @NickiRusin 2 місяці тому +9

      how many J of warmth tho

    • @jboyd85
      @jboyd85 2 місяці тому +12

      @@NickiRusinDepends on the size and insulation of his heart. Probably between 20-40K btu. ;) It warmed, not maintained temperature, after all.

    • @jerrodfine4881
      @jerrodfine4881 Місяць тому

      Think about that heat pump in below freezing ambient air.. I wonder what he will think about his power bill using electric strips…

  • @povilasstaniulis9484
    @povilasstaniulis9484 2 місяці тому

    Thanks for the video. It's interesting to learn what do you use to keep your houses warm on the other side of the Atlantic.
    In my place of the world (eastern Europe), radiator-based and floor heating systems are way more common than airduct-based ones. We pretty much only use airducts for ventilation systems, rarely for heating.
    In my house I have a heat pump that includes automatic electric backup (and even a built-in water heater). The electric backup only runs in really harsh conditions (like -18-20 celsius outside). For backup, we do have a fireplace which is piped to the same circuit, which means the heat pump's electric backup shuts off automatically it detects another heat source. This fireplace used to be the main heat source before we got the heat pump installed. Nowadays, it's mostly used to burn paper waste.
    My system is only slightly oversized (if at all), there's no trend to install oversized heating systems in my place of the world, because it's pretty hard to do with radiator and floor based systems. Well, unless you install way too many radiators.

  • @halfSpinDoctor
    @halfSpinDoctor Місяць тому

    Really insightful video, Alec. My wife and I bought a home in Madison, WI about a year ago, and I have been trying to figure out our HVAC situation. As far as I can tell, our furnace is either perfectly sized or slightly undersized, but the default setbacks on Nest thermostats are ridiculously aggressive.

  • @ntsecrets
    @ntsecrets 2 місяці тому +129

    It was a smart thermostat that led my dad to discover someone was stealing heating oil from his business. A locking cap solved that problem - he has since ditched oil altogether.

    • @TheMrDunker
      @TheMrDunker 2 місяці тому +1

      thank GOD he ditched fuel oil

  • @dave7038
    @dave7038 2 місяці тому +151

    1+ hour Technology Connections episode? Hell yes!
    I hate it so much when someone tells me we're going to do a 'deep dive' on some subject and then can only muster like 25 minutes of content.

    • @headwerkn
      @headwerkn 2 місяці тому +3

      An Alec deep dive requires a dry suit, multiple bottles of Nitrox and a substantial period of decompression afterwards. But you were warned fairly 😂

  • @teresagg9809
    @teresagg9809 2 місяці тому

    Oh the snark! I love it. Thank you sooooo much!

  • @moleisrich1
    @moleisrich1 2 місяці тому

    I installed my own 5 ton heat pumps. Yea that’s right 2 of them! I have a very big house. I never installed a central air before. It was a lot of work but pretty easy. They have been rocking for over a year… when it’s -10 out it’s warm and toasty inside. Ac freezing cold air. Love it.

  • @jessebean13
    @jessebean13 2 місяці тому +220

    Energy auditor here, only 4 minutes into the video but you named off everything on my residental energy audit software. I check everything from the joist spacing to the operating pressures of each register. The Department of Energy are using all the factors you listed in order to weatherize homes. Hope that gives you peace of mind. One of my goals is switching gas furnaces to electric heat pumps. Western Ky here.
    You hit such a huge point at the 25 minute mark. The software we use has a Windows XP face and I think it came out in 2012 and just had updates. I've got a list of DOE approved audit softwares, and they're all a decade and a half behind us. We need to take some of that weatherization money and use it to design a user friendly app, if not just for the professionals. The current system is frustrating enough to make me find another job.
    On the ductwork design rant; almost every house I inspect here has the ductwork in the attic. We spend a few hundred on sealing the ducts with mastic on every job.
    Concerning your garage, is the ductwork in that chase internally lined with insulation? Maybe that could help.

    • @chrisblake4198
      @chrisblake4198 2 місяці тому +6

      Tasks like this are what people should be using AI for. Anonymize the datasets for a few thousands of homes and train the AI to run a questionnaire for the person doing your job until you think all the special conditions are covered and it can generate a reliable result.

    • @jessebean13
      @jessebean13 2 місяці тому

      @chrisblake4198 I actually do use ChatGPT to help me with the absurd amount of formulas I have to memorize. Like to find the minimum required ventilation in cubic feet for a combustion appliance zone.
      It's alot of data input, and they could make it way easier but it's government funded. It's basically a free heat pump and insulation for households under 200% poverty. But the problem is that every house is so different that it would take a while for AI to catch up. AI could handle manufacturered homes no problem.

    • @alexlowe2054
      @alexlowe2054 2 місяці тому +51

      @@chrisblake4198 Software developer here. This isn't a problem that can be solved by AI. Rather, the things AI is good at aren't the things that are the problem. Adding AI to the existing systems doesn't benefit anyone other than Nvidia. Yes, you could build an AI system to do the estimation. But as the results in this video shows, the existing formulas are plenty good enough to get within 5% of the actual value. We don't need an AI system to do the estimations.
      What's needed is a UX designer and a front end developer to build a better more usable interface over top of the existing software. Existing AI tools don't magically fix user interfaces built for Windows XP. All that's needed is a small team of developers and a few months to put together a nice website to run the existing published calculations. In fact, a single software developer could build the whole system if they're a highly competent front end developer who also knows how to manage cloud infrastructure, and they have a few thousand dollars each month to pay for server costs.

    • @knightwolf3511
      @knightwolf3511 2 місяці тому +1

      @@alexlowe2054 also Microsoft doesn't help when they keep breaking software and how not user friendly it is..

    • @NightKev
      @NightKev 2 місяці тому +14

      @@chrisblake4198 Maybe what we should be using AI for is finding a way to properly educate people on what AI should be used for...

  • @kallenbridges8471
    @kallenbridges8471 2 місяці тому +196

    I work in the HVAC industry and appreciate all of the videos you have made on heat pumps. I have always been impressed with the enormous amount of research you have put in as a consumer. I would love to sit down and have a couple hour chat with you on the subject, just because my own hubris makes me believe I could fill in some tiny and I do mean miniscule gaps in your knowledge.
    But I will say this, there is no reason to wait to install a heat pump, if you currently have a 2 ton A/C, there are units on the market that will allow you to simply change the condensing unit outside and nothing else and have a 20+ SEER heat pump.

    • @swimheiss
      @swimheiss 2 місяці тому +1

      Can I join in? I'd love to learn and I'll buy the first round (and probably more)...

    • @knightwolf3511
      @knightwolf3511 2 місяці тому

      kinda there is a reason if your furnace is under warranty and breaks 😅

    • @Sekir80
      @Sekir80 2 місяці тому

      Hey, I'm a curious consumer myself! I have a lot of trouble looking through heat pumps because I know the COP depends on outside temperature, but I can't find the graphs with those data shown. If I'm lucky I get 2-3 data points eg: COP at 10°C, 0°C, -20°C. Where should I look then?
      Edit: as shown in the video at 55:00. Only 3 data points. Or is that really good enough?

    • @Solarusdude
      @Solarusdude 2 місяці тому +7

      ⁠@@Sekir80Those graphs are in the manufacturer’s product catalog typically. Sometimes they are in the installation or O&M manuals. If you can’t find them, you can ask a sales rep to provide it or you can ask them to provide kW estimates over a set of datapoints. You can then use linear regression in Excel to uncover the coefficients in the product’s load curve (provided you know the equation). I used to design building energy models in my day and this was something I had to do occasionally.

    • @Sekir80
      @Sekir80 2 місяці тому +10

      @@Solarusdude Yeah, these are solid advice, thanks. I only find it a bit offensive that I'm constantly handled as an idiot by the product websites giving me mostly nothing and I find it tiring I need to run several circles to obtain documents. Why can't they provide everything with a click? It's like they try to hide the data of given product.

  • @ansonhastings
    @ansonhastings 2 місяці тому

    Same situation with my house in northern NH.
    The heat pump I had installed is a dual-head 18,000 btu/h unit and has no trouble keeping the little single-floor house nice and warm despite the -20 degree temps outside.
    The oil furnace that this replaced was a 120,000 btu/h furnace (with the ductwork in the attic and crawlspace, your favorite :D ). There weren't many times that it ran for more than just a minute or two before shutting off for 10 minutes. Not a short-cycling issue, just that it doesn't take much to heat a 900 sqf house.

  • @1337GameDev
    @1337GameDev 2 місяці тому +5

    9:02 - "Oversized" means the energy needs are greater than it's losses?
    You WANT an oversized furnace then, so it can BEAT your needs, and has to run less often -- which means great durability and hence less issues with it breaking (it running less is less wear and tear).

  • @exobyte0
    @exobyte0 2 місяці тому +87

    This closet conceals an entire FURRRRNACE!

  • @teaumanport
    @teaumanport 2 місяці тому +90

    I'd like to take a moment to note that I really enjoyed the "you're so vain" joke, it was delightful.

    • @timdavison1568
      @timdavison1568 2 місяці тому +2

      This should be the top rated comment 😂

    • @nibirhjawad5689
      @nibirhjawad5689 2 місяці тому +3

      I paused the video to make a comment on that and had to scroll way too far down to see if anyone else had commented on it too.

  • @nangz
    @nangz Місяць тому

    This video is a lifesaver. Nearby IL resident here trying to figure out his heating needs for a furnace on its last legs

  • @KyleFalconer1
    @KyleFalconer1 Місяць тому

    This entire video is incredibly impressive. It’s like a combination of all the themes of your previous videos into a giant exposé of consuming electricity in the most inefficient way possible in order to demonstrate something about efficiency.

  • @unfunk
    @unfunk 2 місяці тому +85

    Fun fact: in Australia we call them "reverse cycle air conditioners"
    Except Tasmanians.

    • @browntea5843
      @browntea5843 2 місяці тому +7

      *splits, techs commonly say we are gonna bash in some splits

    • @herzogsbuick
      @herzogsbuick 2 місяці тому +3

      going through the aussie immigration process was fascinating: they give you all this cultural background, like "tall poppy syndrome", "mateship" and other things i never heard anyone say in conversation. but one thing that stuck with me, and i'm pretty sure it didn't come from immigration but i once heard aussie english and the culture described as: "why call a spade a spade when you can just call it a shovel"
      so i dunno what tasmanians call a reverse cycle air conditioner, but i'll bet it's got far fewer syllables.

    • @herzogsbuick
      @herzogsbuick 2 місяці тому

      @@browntea5843 in tas?

    • @unfunk
      @unfunk 2 місяці тому +5

      @@herzogsbuick well most people refer to them as "aircons" regardless.
      Tasmanians, though, are the only ones that call them heat pumps. I seriously thought it was a weird regional thing when I moved there.

    • @grissee
      @grissee 2 місяці тому +2

      in TC's heat pump video, he say that most american call heat pump RCAC too

  • @MyTrevonne
    @MyTrevonne 2 місяці тому +168

    Your point on sales being separated from installs and service is so on point. It’s happening to every industry though, HVAC, plumbing/water treatment ,automotive , Electrical, and telecommunications.

    • @swimheiss
      @swimheiss 2 місяці тому +18

      So true. A vendor I've worked with for literally decades hired a sales guy a few years ago, and he was really excited to meet with me to tell me about everything they have to offer. I know the industry and his company's offerings better than he does. I told him it was a pleasure to meet him, offered to help him if he had any questions with the nuances of the product line, and if he had any questions on how to help other customers. I really like everyone at the company he works for, and he's a nice guy, so I want them all to be successful. But if I'm gonna spend an hour with him, I'd rather do it helping him instead of pretending he can help me.

    • @JustSnopea
      @JustSnopea 2 місяці тому

      I'm so thankful I moved from working at a large internet RSP with separate sales, provisioning, and customer support (my job there) departments to a small one where the same team handles all of it. The old place was so frustrating, because sales reps would overpromise performance or misguide customers on what their current equipment will be capable of (or upsell them on stuff they didn't need), and provisioning was always unavailable because they were so slammed with work, but we didn't have the permissions to do their job when we were free even though it's really quite simple...
      The new place is great because none of those jobs are too specialized to actually require dedicated teams, and having access to all of it makes everything so much easier. Sometimes we can go from enquiry, to sale, to connection, to router setup all in one call even (which people love hahaha), but most importantly no more "Sorry, this is the wrong department, let me transfer you so you can wait on hold again." or "Yeah, basically someone needs to press a button, but I'm not allowed to, but also that someone isn't available right now." or "The sales rep said WHAT??" 😭
      I wish it was more common, particularly with telecommunications because it would be so easy. So much of sales/provisioning is automated already anyway, so those calls don't take much away from tech support availability, and it just really simplifies things when the staff understand every step of the connection process.

    • @JawzXlives
      @JawzXlives 2 місяці тому +6

      I used to work for an industrial automation company... The separation of sales and tech was the bane of my existence, customer satisfaction, and efficiency.

    • @gregoryclemen1870
      @gregoryclemen1870 2 місяці тому +5

      many hvac companies are geared toward sales rather than service, when I got into this field 50 years ago, it was the other way around. it has always been a practice that sales and service was separate. you had the service techs, and the installation crew, I was on the service side for one real good reason, I got paid more, over what the installers got paid, and installation to me is boring, brain dead work.

    • @Bacteriophagebs
      @Bacteriophagebs 2 місяці тому +4

      I got a quote from an actual HVAC technician that was just as messed up as any of those examples he gave in the video. My house needs less than 24,000 btus of cooling on the first floor, and he quoted me a 48,000 btu system for the first floor, and two 24,000 btu systems for the second. I ended up getting a two 36K systems, and then only because I wanted separate head units in every room and couldn't get any with four heads that were smaller than 36K. If I could have gotten two 24K systems with four 6K heads each, I would have. One of the first-floor head units alone was 24,000 btus and would almost certainly have short-cycled constantly.
      Incidentally, the system he quoted me was almost $45,000 installed because they were charging a 500% markup (to the penny), which I know because he messed up and included the links to the equipment on their supplier's website in the item description. Had he been in sales, he might have known to delete those before printing the quote. My actual system, bought from the manufacturer and installed by a different HVAC company, was under $6500 installed.

  • @DetroitMetroRetro
    @DetroitMetroRetro Місяць тому

    This video pushed me to learn my furnace is about twice what i need! That explains the fire that comes bellowing out

  • @pdelong42
    @pdelong42 2 місяці тому

    "you probably think this video is about you"... Thank you. That totally made my day.

  • @Lambda_Ovine
    @Lambda_Ovine 2 місяці тому +73

    this channel has armed me with all the knowledge i could ever need for the house i will never own

    • @rubidot
      @rubidot 2 місяці тому +2

      Yeah, me too ⚰️

  • @n0tthemessiah
    @n0tthemessiah 2 місяці тому +164

    Fortune Teller:
    -I see a small townhouse.
    -I see you with extension cords and a lot of space heaters.
    -Jesus that's a lot of space heaters.

    • @ashtoncarriveau3880
      @ashtoncarriveau3880 2 місяці тому +3

      LMAOOOOO that's too good

    • @vigilantcosmicpenguin8721
      @vigilantcosmicpenguin8721 2 місяці тому +1

      "Huh, crystal ball must be broken."

    • @shockwave3318
      @shockwave3318 2 місяці тому +2

      Honestly if a fortune teller predicted this and it came true. She might actually be legit.

    • @technicolorskies5432
      @technicolorskies5432 Місяць тому

      -I see that 100ft extension cord coiled up on the ground acting as an inductor and getting very hot

  • @notelliot70
    @notelliot70 2 місяці тому

    I just realized my studio apartment with the hotel style heating/AC unit is probably already a heat pump. Neat! Explains why it got a bit chilly in here during the cold snap

  • @baddog9188
    @baddog9188 2 місяці тому

    this man is the definition of "above and beyond"

  • @harriehausenman8623
    @harriehausenman8623 2 місяці тому +132

    That hour went by so quickly. I literally thought: What, it's over already?
    how can one person explaining HVAC be more entertaining than all of Hollywood combined?!
    Thank you so much Alec! 🤗

  • @wichtel1805
    @wichtel1805 2 місяці тому +120

    "But you may have noticed the runtime"
    *moves mouse over the video and is shocked by the runtime*
    "Yeah, we're covering a lot"
    That... was a very nicely timed pause there. At least it was for me. 🙂

  • @MARKE911
    @MARKE911 2 місяці тому

    Fantastic work sir. Well done

  • @finbarr69
    @finbarr69 Місяць тому +1

    Fascinating! Amazed that your furnace doesn't also heat your water. We have a 32KW gas boiler for a small 3-bedroom house. It is specified so that it can heat sufficient water to be able to run two showers simultaneously (there is no hot water tank). Also, an explanation of what HVAC stands for would help your international viewers. It stands for High Voltage Alternating Current here in the UK. 😀

  • @XanderKyle
    @XanderKyle 2 місяці тому +241

    I absolutely admire your commitment and dedication to consistently spelling out "H-V-A-C" every single time instead of just saying "H-Vac" like everybody else does.

    • @LittleMopeHead
      @LittleMopeHead 2 місяці тому +47

      Imagine him saying the words "heating, ventilation, and air conditioning" every time.

    • @PunkrockNoir-ss2pq
      @PunkrockNoir-ss2pq 2 місяці тому +6

      autism?

    • @robertide5182
      @robertide5182 2 місяці тому +3

      Why?

    • @D.R.Miller
      @D.R.Miller 2 місяці тому +3

      Then theres H-Vacr with refrigeration added on

    • @jonaut5705
      @jonaut5705 2 місяці тому +5

      @@PunkrockNoir-ss2pq what

  • @lordchutney9000
    @lordchutney9000 2 місяці тому +41

    "These allowed me to control the space heaters, and Christmas lights, with precision" - great phrases of our time.

  • @Brewdog2001
    @Brewdog2001 Місяць тому

    I was surprised 2 years ago when I replaced my old heat pump system with a new one. The old one was on its last legs and was 26 years old. When talking with the sales person, they actually asked to check my attic and they measured my rooms along with checked where my registers were as well as measured my air return ducts too. Then he asked questions about how often the old system would cycle and how it was as far as cooling and heating and how long things ran. Once that was done he presented me options, and told me I actually needed more cooling than heating to ensure the system would ever make it to the desired indoor temperature. The new system uses a proprietary thermostat but honestly it works really well and as the system is variable speed system. If the weather is between 40 and 60 my system barely every runs, once it gets below 40 it does run more and once over 60 it runs more as well, especially when its dehumidifying the air.

  • @Jacob-bm6wb
    @Jacob-bm6wb Місяць тому

    Im going into hvac so this is useful, I assume I haven't actually watched the video yet but Im a long time fan

  • @energitrimmeren
    @energitrimmeren 2 місяці тому +91

    A tale from Denmark🇩🇰 Changing from gas to HVAC, I’ve calculated 6 kw needed. Asked for quotes in HW price, extras and man hours. Took me 12 quotes with 8-16 kw pumps, before one supplier, 200 miles away made the right quote with 7 kw HWAC. You’re so spot on the problems, and not alone. 🇩🇰😎

    • @SeanAlcorn
      @SeanAlcorn Місяць тому

      The companies that quoted 16-18kW knew what they were doing. The guy that quoted you 7kW had no clue. A Heat Pump should only operate 1/3 of the day. Not all day. Good luck!

  • @resilientspring
    @resilientspring 2 місяці тому +63

    Totally unrelated to the video topic, but my husband wanted to watch this video with me so he asked me if I wanted to watch 'the guy with the brown' and I knew what he meant 😂

  • @jmi967
    @jmi967 2 місяці тому +1

    I think there’s a few other things that are taken into account:
    • longevity of the equipment (high duty cycles cause faster wear)
    • overspeccing for lower efficiency as the unit gets older
    • not knowing the insulation value for the house (hard to do)
    • overspeccing for margin
    • hvac planners not knowing how to calculate things and just going at the charts like a bible or just not caring

  • @colinwilmes8318
    @colinwilmes8318 Місяць тому +1

    Just purchased mini splits for my entire home partially because of this video series. I live in the PNW and do not have central AC I also use baseboard heat so they will dramatically lower my heating bill.

  • @scottburbridge1451
    @scottburbridge1451 2 місяці тому +56

    The whole 'Heat pumps are just air conditioners, but they don't want you to know!' part made me chuckle a little. Down here in Aus, they've just been called 'reverse cycle air conditioners' for as long as I can remember, so there is no big mystery.

  • @per7898
    @per7898 2 місяці тому +92

    HVAC contractor here. We UNDERSIZE always. Here in EU, especially Scandinavia, we recommend to install a heat pump that is 80% of the whole heat load of the house/apartment with 20% as auxiliary. This is a common practice and knowledge of any good professional in this field here. This is because it will lead to; higher efficiency, longer lifespan, cheaper investment cost, cheaper running cost, less start and stops, quieter. This is all because a undersized will do fewer start and stops, running longer intervals and more continuously during the whole year as it have to run longer to keep it warm, as in video "struggle longer" but that is a good thing as it will run as it optimal capacity for the building as long as possible and not shut off and start that take more energy each start cycle and also do more wear and tear on components, it will lead to that an undersized heat pump being more efficient, better SCOP, and as more longevity, less maintenance or replacements. Also The coldest days is few per year. For only couple of days to maybe one week it will be coldest or mostly at night, so you can use auxiliary heat source such as a direct electric boiler/heater. The majority of the year you don't need that much heat, like 90% of the year you need only 80% or less of the whole target heat load (80% of the heat losses that the house has). We all here in Scandinavia know here from 50 years of experience of heat pumps that a heat pump that is not having too much start stops and use aux electric heat for the coldest nights will have a life of 25-30 years if you are lucky, average 18-25 years. An oversized heat pump will last only 10 years. So 80% is our best recommendation for your wallet. And remember 1 degree colder heating will save you 5-10% of your electric bill and will get you some more years of the heat pump, also keep you more active and healthy :) But need to be said as last thing, now all heat pumps here are inverters with frequency variable speed controlled, so now the heat pump tries to never shut off the compressor and goes down in speed and up in speed depending on the load is needed and the outdoor temp, So now we just buy one size almost that fits all, but still you don't want to over size here, as it will remove the benefits then that it cant go down in enough low frequency speeds, so it will act if oversized more like a on-off heat pump and then you loose the whole point why you bought a inverter variable speed heat pump. So don't oversize, always better to undersize with 80-90% of the whole heat load, even if inverter aim for as close to 100% as possible, the lower speeds will be active all spring, summer, fall, only coldest winter will need full heat capacity. UNDERSIZE IS KING!

    • @allareasindex7984
      @allareasindex7984 2 місяці тому +23

      Undersize is king! I have to show this to my girlfriend!

    • @odioreviews4829
      @odioreviews4829 2 місяці тому +7

      @TechnologyConnections should talk about this, I didn't know this

    • @SVIKPolRiks
      @SVIKPolRiks 2 місяці тому +6

      I will show that to my installer

    • @swimheiss
      @swimheiss 2 місяці тому +1

      I was going to ask about VFD's on another comment, but yours pretty much answered it. Where I am, power outages are fairly rare but happen enough that I'd be inclined to keep my gas furnace just for those occasions where I could run it on battery or generator power and still have heat. Every time our local power has gone out we've still had gas pressure, and it wouldn't take much power draw to keep the place warm.

    • @fionafiona1146
      @fionafiona1146 2 місяці тому +1

      My parents are getting quotes these days and the list of considerations is similar in Germany (the insulation significantly improved since installing the previous heat)

  • @creepinwhileyousleepin
    @creepinwhileyousleepin Місяць тому

    I learn so much from this guy, my second favorite Illinois based techtuber :]