York YS Chiller Bad Sensors
Вставка
- Опубліковано 7 вер 2024
- York YS screw chiller has 73k starts but only 2k run hours. Looking into sensors I found both a chilled water and condenser water sensor was out of calibration making chiller think water temp was 8F lower than it really was.
You can contact me at Hvactimetx@gmail.com
You can also follow me at,
Instagram
/ hvactime
Facebook
/ hvactime venmo.com/code...
I have a problem in my York chiller Ylaa0300He.. It tripped over suction pressure limiting signal..
Hey guy can I ask you some questions about tools for pulling a vacuum on these chillers.
Does the chiller need to be off to change the sensor ?
Yes
Is that a York YS chiller?
Yes
I would expect more system issues to be found in the future with starts to run hours that lopsided. I feel like at an absolute minimum run hours should double starts. But it's the real world so.... ya know lol.
There is. The automation control of building and plant loading is in poor shape and outside of original design. Im just scratching the surface of issues here.