Working on a 3 Phase ‘Widow Maker’ | ØY38

Поділитися
Вставка
  • Опубліковано 26 гру 2024

КОМЕНТАРІ • 299

  • @corymac
    @corymac  10 місяців тому +4

    50% off the Gilet from the video - unilite.co.uk/product/gilet/?dynamo=oy&ref=4339

  • @B0jangle5
    @B0jangle5 9 місяців тому +84

    360 degree headcams will never stop being funny.

    • @justin8894
      @justin8894 9 місяців тому +4

      Celsius or Fahrenheit?

    • @mrtechie6810
      @mrtechie6810 8 місяців тому +1

      ​@@justin8894Kelvin. Obviously!

  • @TradifyHQ
    @TradifyHQ 9 місяців тому +6

    Appreciate the shoutout, Cory! Great to see our job management software is benefitting your business!

  • @bavarianmonkey8326
    @bavarianmonkey8326 9 місяців тому +30

    It is quite funny. On the one hand, there are single insulated conductors carrying 100A (?) of current that are bolted directly to a wooden substructure without any additional protection against touching. On the other hand, you are using metal conduit for the new wiring.
    Meanwhile in Germany we use a lot more plastic stuff that does not require drilling into metal, lockrings and that is insulated in itself...on the other hand, running 5x25mm² as a multi core conductor certainly is less fun than what you are doing with individual single conductors...

    • @RandomUser2401
      @RandomUser2401 9 місяців тому +2

      the widow maker shown is pretty standard in Europe in every house.

    • @JonSenior
      @JonSenior 9 місяців тому

      @@RandomUser2401 Not in the French part of Europe it isn't! It's either way neater and safer, or (pre 1980s) absolutely terrifying. ;-)

    • @mariospanna8389
      @mariospanna8389 8 місяців тому +1

      @@JonSenior I hope your not praising french electrics...

    • @JonSenior
      @JonSenior 8 місяців тому

      @@mariospanna8389 Modern wiring to the current standards is not bad. The standard seems mostly well thought out, although I put a lot of time in pulling CAT5 cable everywhere to meet the standard, only to find that by the time I can to actually use it, we were all using mobile devices with wifi and no LAN sockets!
      Older French wiring is something else though! Braided sheath cables with push button switches just hanging from the ceiling which make your arm tingle when you touch the cable. Spurs installed on spurs, with no earth connection. Cables spliced with a choc block connector under enough tension that the connections pulled apart when the temperature dropped.

    • @mariospanna8389
      @mariospanna8389 8 місяців тому +1

      @@JonSenior I stand by statement as having worked and lived in a number of regions of France, and worked with french film electricians. NO thank you. You can't change my mind i have seen their work and what it happens as a result from it.
      I am not talking pre 1980 aswell i worked out there in the 90's up untill about five years ago...

  • @derekmay8427
    @derekmay8427 9 місяців тому +8

    Cory I find your channel compelling, as a retired Sparks with a lifetime in the industry, you would think I would have had enough! But it is fascinating to get a modern perspective! The basics still remain! Love the humour 😎👍🏻

  • @IanFarquharson2
    @IanFarquharson2 9 місяців тому +22

    Great episode. Insulated sharpie is fine, metal tape measure not a great pointing tool ⚡️😁

    • @Michael-xs5ef
      @Michael-xs5ef 9 місяців тому

      Coffee mug on top of the Main Breaker - what could possibly go wrong....... ?

  • @dcallan812
    @dcallan812 9 місяців тому +23

    Interesting video 2x👍
    I work for 6 months in a power station, that was truly "widow maker" power. Parts of site you needed special overalls with no metal. You could feel the power just walking past outside the room.

  • @christopherleubner6633
    @christopherleubner6633 9 місяців тому +7

    Worked on a Coherent Everlase CO2 laser that was a literal widow maker. At its heart it had a large 3 phase transformer that took 480 in and put out plus and minus 40kv with filter capacitors that were fed to the lasing tube. It was current regulated on the ground side with 4 big glass transmitting tetrodes. The widow maker part was the mirror mount that needed adjustment occasionally was floating at 45kv at whatever current the transformer could source through your body. The laser had to be running in order to adjust the optimum alignment. Working on it was a bit of pucker factor, to add to it, the tubes were supported on a large granite slab so it has the tombstone built into it. Was very relieved when we retired it and upgraded to a Truamph slab laser that used RF. 😂

  • @cinemasbyjames
    @cinemasbyjames 9 місяців тому +12

    Pretty sure those old federal boards arent even classed as protective devices anymore just isolators. Always pray they re-engage when switching on/off. Had a few not turn back on after a shutdown

  • @trailswithted6024
    @trailswithted6024 9 місяців тому +20

    With the Henley blocks it looks like they have single insulated cable outside of containment or enclosure

    • @corymac
      @corymac  9 місяців тому +9

      Bingo!!!

    • @joshuabest100
      @joshuabest100 9 місяців тому +2

      Also they are upside down which takes away the ip rating

    • @adamjwhite50
      @adamjwhite50 9 місяців тому

      @@joshuabest100what ip rating ?

    • @joshuabest100
      @joshuabest100 9 місяців тому +2

      @adamjwhite50 yes Henley blocks ha a ip rating believe it or not

    • @jan-dr1xl
      @jan-dr1xl 9 місяців тому +3

      However going by the colour of the conductors this would have complied with the regs that were in force at the time of installation,and so whilst not ideal,its still compliant.

  • @marktubeie07
    @marktubeie07 9 місяців тому +10

    Oooh, intros now mate! Damn you make quality vids Cory - next level stuff. Also Cheers to your editor/producer/ crew etc. Superb, oh and damn hilarious in parts. 😂😂

  • @three-phase562
    @three-phase562 9 місяців тому +6

    The Copper Development Association produce a document on busbar design that gives torque settings for various bolting configurations.

  • @matthewbrunk6262
    @matthewbrunk6262 8 місяців тому +3

    A fellow sparky here. Over here in the US, we just say it has been "farmered". Sometimes even in front of said farmer.

    • @corymac
      @corymac  8 місяців тому

      That checks out 🤣🤣🤣

    • @Mixolixplosion
      @Mixolixplosion 7 місяців тому

      The entire american electrics have been farmered tbh 😅

  • @mbainrot
    @mbainrot 9 місяців тому +6

    Nicely done Cory, remember, don't lick the tasty bus bar

    • @corymac
      @corymac  9 місяців тому

      🤣🤣👍🏼

  • @jk-8761
    @jk-8761 9 місяців тому +3

    Entertaining. Educational. Excellent

    • @corymac
      @corymac  9 місяців тому

      Thankyou!

  • @dessilverson161
    @dessilverson161 9 місяців тому +9

    You got that easy, able to turn it off, a luxury. I was a sparks on the docks in the late seventy's. It cannot be turned off as it costs a very lot of of money. Buss bar chamber live 2000A fuse behind it. Drill the solid copper bars, connect up the cables with nuts and bolts, that means one arm is up behind the bars with a spanner and a bit of tape round it. The same for the bolt head at the front. Put lid back on and jobs a goodun. I hardly ever worked with the power off unless the crane or whatever was down for maintenance.

    • @barteklewandowski4211
      @barteklewandowski4211 9 місяців тому +3

      Glad you're here to tell the tale but let's not don't glorify working live, it's not worth becoming a statistic to save someone money

    • @DesSilverson
      @DesSilverson 9 місяців тому +1

      Its what you get used to I suppose. Even when a circuit could be turned off, I was so used to working live nine times out of ten I didn't bother. When I think back some of it was a bit iffy like the cranes only fed with three wires red, yellow (or white) and blue. 240v for the lights meant two in series across two of the phases etc. The office block even still had capping and casing and bare wiring!!

    • @robertmather7696
      @robertmather7696 9 місяців тому

      I used to open these up live to do thermal surveys in gloves and an arc flash suit, the ones in switchrooms on Liverpool docks were deffo still the ones from the 70s or even older!

    • @GregNow
      @GregNow 9 місяців тому

      🥶

    • @UKsystems
      @UKsystems 4 місяці тому

      That’s why boss bar Chambers are becoming increasingly less common when work is replaced or new installations are done

  • @kevint1910
    @kevint1910 9 місяців тому +1

    1:40 those are stab lock configuration brakers...wow what brand is that over there? those things are ancient second generation stuff. one step up from pillow block brakers they were good for their day but did not last long in the US market i think they went out of business in the late fifties early sixties iirc.

    • @18in80
      @18in80 9 місяців тому

      They're Federal Electric Stabloc MCBs. That installation was probably done in the late '70s or early '80s.

  • @RossTheSpark
    @RossTheSpark 9 місяців тому +5

    Whether you did or didn’t know Cory. Those old black cutouts / fuse holders can be made from a material that becomes phenolic overtime (degrades and becomes conductive) it’s not been uncommon for people to have tingles from them. Meter fitting companies etc generally use a Martindale VT7 to check these. I can send you one if you like ?

    • @Gpbattersby
      @Gpbattersby 9 місяців тому +2

      They don’t “become” phenolic. They are manufactured from a material called phenolic resin, essentially a type of plastic

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 9 місяців тому

      They get damp and become slightly conductive 😊rare...but it happens!

  • @billrimmer5596
    @billrimmer5596 9 місяців тому +1

    I love your vids. Your camera person does a fantastic job. I live in Los Angeles and the terminology is very different. Not only do u really know your stuff, u have a great sense of humor.

    • @corymac
      @corymac  9 місяців тому

      Thanks for watching!

  • @PublicMeetings
    @PublicMeetings Місяць тому

    great idea tapping on things IN AM ELECTRICAL WORK AREA with a metal tape measure in your hand

  • @Lenny-kt2th
    @Lenny-kt2th 9 місяців тому

    Some curious things I realised, working for a Dutch DNO, is that in our part of the grid, we kept the old UK colour coding, i.e. red, yellow and blue (the consumer side does use brown, black and grey). One other thing is that - as the story goes - these colours were sometimes painted in the wrong order on the bus bars inside distribution stations. The pragmatic approach was not to redo everything but just supply either a right rotating or a left rotating field to the customer. From there on it is up to the electrician of the consumer to wire the devices in the right rotation. So, when changing a meter, we have to check the rotation twice to make sure before and after are the same, it's easy to swap wires (and actually simulated during training and examinations). Some devices won't work on the wrong rotation, but some will just go the other way around, as you mentioned, possibly damaging or destroying things.

    • @corymac
      @corymac  9 місяців тому

      That’s interesting!

    • @corymac
      @corymac  9 місяців тому

      What do you prefer?

  • @MrSuperBrite
    @MrSuperBrite 9 місяців тому +2

    Your video editor is phenomenal.

    • @corymac
      @corymac  9 місяців тому +2

      He is indeed 👌🏼👌🏼

  • @tschubb1992
    @tschubb1992 9 місяців тому +2

    The block are upside down so the IP rating will not be to standard? and some single insulated cables where they have been stripped back.

  • @UnimportantAcc
    @UnimportantAcc 9 місяців тому +6

    7:17
    new channel icon?

  • @PavelMikhalkov
    @PavelMikhalkov 9 місяців тому +2

    9:34 10:27 - this is not 3-phase grid that makes widows, that's you, who works without gloves and with non isolated tools on lines that are not grounded.

    • @corymac
      @corymac  9 місяців тому +1

      Fair point!

    • @UKsystems
      @UKsystems 4 місяці тому

      Actually, it’s also the grand because you shouldn’t be working on it anyway even with insulated tools unless it’s necessity which you have the option to isolate the supply here

  • @mxslick50
    @mxslick50 9 місяців тому +4

    FPE Electric... = Fire Prone Equipment (at least here in the US.) The "Stab Loc" line is extremely dangerous.. and there were thousands of the industrial breakers that were prone to failing by emitting smoke, sparks or exploding..and FPE's solution? They issued stickers saying don't touch it, and call a 1 800 number....🙄
    I personally worked on several Stab loc panels, and a few of the industrial panels...and hated them with a passion.

  • @wvziccardi
    @wvziccardi 9 місяців тому +2

    All farm electrics are a little heehaw 😂 great video as always

  • @tjairicciardi9747
    @tjairicciardi9747 9 місяців тому +1

    appreciate your videos, great content and excellent production quality

  • @0liver0verson9
    @0liver0verson9 9 місяців тому +6

    Most electricians seem to think it's a strict requirement to show visible inner insulation.

    • @lewis94uk
      @lewis94uk 9 місяців тому +2

      Yeah when I was an apprentice the old boy would strip them back for identification

  • @tzm1843
    @tzm1843 8 місяців тому

    Shouldn't you turn away from the panel when flipping breakers?
    What if something was accidentally shorted?

    • @corymac
      @corymac  8 місяців тому

      That’s why we test before we switch on 😁

  • @samfish6938
    @samfish6938 9 місяців тому +1

    clean up the shavings before pulling wires shavings can cause arc flash

    • @corymac
      @corymac  8 місяців тому

      We vacuum 😁

  • @GregNow
    @GregNow 9 місяців тому

    6:37 "those days are gone" 🤣

  • @titmando1199
    @titmando1199 9 місяців тому

    Henley blocks have single insulation outside of the enclosure, they also have black tape covering one of the entries still get a finger or tool inside it, they are also upside down. If they only needed three ways they should of swapped it for a three way Henley block instead of taping over one way.

  • @klarnorbert
    @klarnorbert 9 місяців тому +2

    I just need some popcorn :P Awesome content as always.

    • @corymac
      @corymac  9 місяців тому

      Thank you!!! 🤩

    • @corymac
      @corymac  9 місяців тому

      The question is, which flavour 🍿

    • @klarnorbert
      @klarnorbert 9 місяців тому

      @@corymac Butter obv :D

  • @raychambers3646
    @raychambers3646 9 місяців тому

    I worked a lot telephone exchanges there was equipment that would melt your saw , other that would blind if you looked down it, also a lot equipment you couldn't turn off without about3 weeks notice and then at 3 oclock in the morning .

    • @corymac
      @corymac  9 місяців тому

      😅😅😅

  • @brianatkinson4484
    @brianatkinson4484 9 місяців тому

    Brings back memories did metal trunking by the mile still got the scars from the sharp edges

    • @highkicker11
      @highkicker11 9 місяців тому

      metal trunking is only going to cut you if you are care less, just like building a pc in a really small case, the first few times you have cuts then you know to put on gloves

  • @rabokarabekian409
    @rabokarabekian409 9 місяців тому

    I once warned a supposedly senior electrician to turn off and meter the 440vac before removing starter arc chutes. After his first grab and shock, he opined that was just static. Then he grabbed it a second time. I told him I was going to shut off the breaker while he recovered.
    A different time, a three phase disconnect was positioned off, but one of the switches broke off the actuator bar, leaving one phase still hot.
    Yeh, I also ohms check the meter leads before every voltage check.
    "440 don't like to let go of you." is the folk saying.

    • @corymac
      @corymac  8 місяців тому

      Crazy! Was he injured after?

  • @jamiekent1970
    @jamiekent1970 9 місяців тому +1

    A 3phase isolator / switch fuse would have been great as you tapped off the busbar. You are essentially making those sub-main cables an extension of the busbar chamber, even though you have 3 phase isolator/ main switch in the DB😮

    • @corymac
      @corymac  9 місяців тому

      If I was going more than 3m with my tails, I’d have been more concerned about doing that. But as it’s such a short run, I’m not as worried

    • @jamiekent1970
      @jamiekent1970 9 місяців тому +1

      @@corymac ok, if you are sure. But to work or change the new 3 phase DB would need another shut down. But I do love your work Cory ❤️

    • @corymac
      @corymac  9 місяців тому

      It’s a good shout mate. Thank you 🙏🏼😁

    • @corymac
      @corymac  9 місяців тому

      It’s a good shout mate. Thank you 🙏🏼😁

  • @residualelectrical
    @residualelectrical 9 місяців тому +7

    Another great video bro! ❤

    • @corymac
      @corymac  9 місяців тому +1

      From the man himself 🙏🏼🙏🏼🙏🏼❤️

  • @Stoeckermann
    @Stoeckermann 9 місяців тому

    How does the insulation hold up against possible sharp edges in the metal conducts? In germany im used to working with plastic"rails"

    • @corymac
      @corymac  9 місяців тому

      There’s no sharp edges 👌🏼. It’s all either filed or smooth grommets

  • @jamesgreen4008
    @jamesgreen4008 9 місяців тому

    I love that Milwaukee wrench

    • @corymac
      @corymac  9 місяців тому

      Us too 🤤

  • @gordslater
    @gordslater 9 місяців тому

    Careful with the Sharpie. You don't have a 5 inch long insulator, you have a thinwall plastic tube with a liquid ink wick up the middle of it.
    The vapour aspect of the ink and solvent is unpredictable and may depend on the colour of the ink but I know from experience that sticking a Sharpie in a HF radio amplifier with 1500VDC on the top of the bottles is a bad plan and caused a hell of a lot of paperwork and several clipboards turned up.
    It broke down in a split second and all our bowels leaked out.

    • @corymac
      @corymac  8 місяців тому

      That’s insane!!!

  • @prodjevnt1092
    @prodjevnt1092 10 місяців тому +3

    Reason the henly blocks are non-complinent they've being installed upside down

    • @residualelectrical
      @residualelectrical 9 місяців тому +4

      You can actually install them any way you like, but the seal needs to be IP4X, if you drill them out perfectly I can be done or you can fit a grommet 👍🏼

    • @Jay369
      @Jay369 9 місяців тому +5

      Issue is with the single insulated cables

    • @mikethemask1525
      @mikethemask1525 9 місяців тому

      Issue is the Line conducter is nearest the opening lide

  • @joejames8146
    @joejames8146 9 місяців тому

    4:05 C2 single insulated conductors showing

    • @corymac
      @corymac  9 місяців тому

      That’s right!

  • @djgeorgevdg
    @djgeorgevdg 9 місяців тому

    Great Intro and Videography as always 👍

  • @guygfm4243
    @guygfm4243 9 місяців тому

    Omg it’s like going back 30 years did loads of work on this stuff, up grades from 100a to 400a

  • @majorintherepublick5862
    @majorintherepublick5862 8 місяців тому

    Federal pacific breaker panel is a fire waiting to happen

    • @corymac
      @corymac  8 місяців тому

      Yeah!! I hate those things, I’ve recommended an EICR on the rest of the system.

  • @justme5384
    @justme5384 9 місяців тому +2

    400V? You mean everyday domestic electric work? I happen to live in northern Europe so almost everywhere is three phase 400V. Only old apartment buildings are 230V single phase. Or well they're single phase in the flat, but three phase on the basement distribution room

    • @corymac
      @corymac  9 місяців тому +1

      We’re a little behind here haha

    • @justme5384
      @justme5384 9 місяців тому +1

      @@corymac I know right... But you've been to our neighbour so you've gotten a hand on our Nordic system. You just need to get the UK to follow... Conduits and singles all the way

    • @thorstenjaspert9394
      @thorstenjaspert9394 9 місяців тому

      Same in Germany. 3 Phases are standard in private houses and flats everywhere. Only in very old houses you find 1 phase supply. They are very rare.

  • @JensenPGATourDriven
    @JensenPGATourDriven 9 місяців тому

    Always great to watch and learn from you Cory ⚡️👊

  • @richrowley8355
    @richrowley8355 9 місяців тому +2

    Nice one Cory

  • @Klekkus
    @Klekkus 9 місяців тому

    Question from Norway: Why are not the meter box and main fuses from the grid inside a enclosure?

    • @UKsystems
      @UKsystems 4 місяці тому

      First of all this is not why would generally be done generally speaking there’s a main cable coming in and there’s a plastic box with the fuses on the front. That’s all sealed up too can’t get a shock then it goes to the meter generally on a new install, it’s on a plastic cabinet on the side of the building, cables that carry on the phases and neutral are double insulated

  • @chrisfs150
    @chrisfs150 9 місяців тому

    How many other electricians know their nipple heights?
    For instance mine are the typical reg max height of light switches and as a bonus the bottom of my kneecap is the typical recommended height for socket outlets from the floor.
    Makes marking out a doodle...

  • @AlejandroTaylorEscribano
    @AlejandroTaylorEscribano 9 місяців тому

    Why don’t you use black and grey for the L2 and L3 lines?

    • @UKsystems
      @UKsystems 4 місяці тому

      Generally speaking, that’s done, but as long as the conductors are appropriately identified, it should be okay

  • @electrician247
    @electrician247 9 місяців тому

    VFT is the best torque lol. Top video with some very cool editing! Keep it up.

  • @tzm1843
    @tzm1843 8 місяців тому

    "This is a widowmaker."
    Turns off the main breakers. "Not any more."

    • @corymac
      @corymac  8 місяців тому

      😂👌 - only trouble is, I’ve actually had them lock into the on position before!! So they wouldn’t turn off ( check episode 3 I think it is! )

  • @maximilianreichelt9717
    @maximilianreichelt9717 8 місяців тому

    Why don't exchange it for a modern 3 phase busbar with clip on fuse switch disconnector?
    And why are the neighbours tuned off? Isn't the big main switch to turn off the busbar?

    • @corymac
      @corymac  8 місяців тому

      It wasn’t in our scope of work 😄

    • @maximilianreichelt9717
      @maximilianreichelt9717 8 місяців тому

      @@corymac Like always: "I want solar system to save money, but i don't wan't to invest in a good electric installation to carry the solar energy."

    • @UKsystems
      @UKsystems 4 місяці тому

      @@maximilianreichelt9717 the government government issue grants generally quite heavily towards the installation of solar system something like farms

  •  9 місяців тому +1

    Majority of agricultural installations are rougher than 2 grit sandpaper

    • @corymac
      @corymac  8 місяців тому +1

      That’s a good analogy 😂

  • @craigbutler6243
    @craigbutler6243 9 місяців тому

    Can't work out why the db wasn't terminated before the bus connections? Would have been much quicker?

  • @imark7777777
    @imark7777777 9 місяців тому

    Wow you got done early and got the outro done amazing.

  • @andrewrussack8647
    @andrewrussack8647 9 місяців тому

    Nice vids. I would have preferred if you had ‘brushed bright’ before making the connections to the bus work! 😮

    • @corymac
      @corymac  9 місяців тому

      Next time! Good call

  • @ariebastiaanse3423
    @ariebastiaanse3423 9 місяців тому +6

    Nipple heigt... As if the British scheme of measurement units isn't confusing enough.

    • @mxslick50
      @mxslick50 9 місяців тому +2

      We use willy length here in the US for the amount of wire to leave sticking out of the box....at least that's how it seems on some jobs, and many are obviously lacking...😁

    • @UKsystems
      @UKsystems 4 місяці тому

      The metric system is very standardised and converting between millimetres centimetres and metres is quite easy

  • @18in80
    @18in80 9 місяців тому

    15:53 is 3,2,1 with Ted Rogers. You win Dusty Bin.

  • @jeremykemp3782
    @jeremykemp3782 9 місяців тому +2

    You could have checked one of the other existing lugs to see what they were torqued too!!! And its prospective earth fault current, not potential. You had the potential to check the existing lugs for torque values : )

    • @corymac
      @corymac  9 місяців тому +5

      Now that’s a move a smart man would make. I don’t claim to be a smart man, but I know what love is…

    • @jeremykemp3782
      @jeremykemp3782 9 місяців тому +2

      @@corymac
      Ps, I do love your channel x

    • @martinbateman2467
      @martinbateman2467 9 місяців тому

      @@corymacmaybe you could tell these guys ua-cam.com/video/r3Pr1_v7hsw/v-deo.html

  • @lewiswills5370
    @lewiswills5370 9 місяців тому

    Good vid as always, learned a lot from this

    • @corymac
      @corymac  9 місяців тому

      Glad to hear it!

  • @tomaskopic2469
    @tomaskopic2469 9 місяців тому

    What color of phases do you have? Red, Ylw, Blu? the blue one is kinda misleading, innit? In heart of europe we used to have black/brown/black (or all black/brown) (with labels U V W) and nowaday using brown/black/grey (labels L1 L2 L3)

    • @user-super-user
      @user-super-user 9 місяців тому

      not really the old phase colours used to be red,yellow,blue and black for neutral

    • @UKsystems
      @UKsystems 4 місяці тому

      We do use the harmonise European colours. You just need to identify the phases so technically using all brown would be considered probably okay because that’s fine. You technically could use all the same colour and just label them at the end but obviously obviously using a neutral colour for a phase would be a bit stupid.

  • @tahseenashfaq
    @tahseenashfaq 9 місяців тому +1

    Alway love your videos, honestly carry on the great work 👍🏼👍🏼

    • @corymac
      @corymac  9 місяців тому

      Thanks man!!

  • @some-idea
    @some-idea 9 місяців тому

    Great video. Would love to see the ground source install

    • @corymac
      @corymac  9 місяців тому

      Coming soon!

  • @HSilver341
    @HSilver341 9 місяців тому

    Keep smashing it😂🎉🎉🎉

  • @jameshunt2141
    @jameshunt2141 9 місяців тому +2

    what I don't understand is that Makita's best combi drill is more expensive then Milwaukee's and has a much longer service life yet people still think Milwaukee is better.
    I'm using a Makita 3/4 impact wrench that is still going strong for 8 years of daily abuse that has outlasted 3 Milwaukee 3/4 guns. just why are people defending this TTI crap.
    the only Makita product from their top line that I have to replace so far is batteries after 5 years of hard use as a agricultural mechanic. ive been at it 14 years and the batteries do wear out unsurprisingly.
    There is one exception... The torches and multi postilion lights fall apart
    buy the Makita top of the line whatever tool you need and it pays for itself

    • @UKsystems
      @UKsystems 4 місяці тому

      Do you think Makita is better? However they’re batteries last less in terms of years due to how their battery management is and they are more difficult if you have an issue.

  • @tomwinkley3536
    @tomwinkley3536 9 місяців тому

    Hey Cory
    I hope all is well I’ve got to ask do you do much work in sheffield ? I am willing to introduce Pringles more if this helps

  • @jamesclark3090
    @jamesclark3090 9 місяців тому

    Got the new DB isolator on with busbar stabs live and exposed, no need to have isolator on for the tests you carried out .... nice vids....but be careful

  • @iwmpwc
    @iwmpwc 9 місяців тому

    I noticed your using a tool to check that your multimeter is working, then you check your line, then you use that tool again to confirm... what is that tool?!? ive never seen one.

    • @corymac
      @corymac  9 місяців тому

      It’s called a proving unit 😁👍🏼

  • @grantmccallan8136
    @grantmccallan8136 9 місяців тому

    Would it not of been quicker getting the DB all terminated before shut off?

    • @corymac
      @corymac  9 місяців тому

      Trouble is, I couldn’t get the tails in until the trunking was in, and I couldn’t get the trunking in until I’d drilled a hole, couldn’t drill the hole til the power was off.

  • @Krmpfpks
    @Krmpfpks 9 місяців тому

    Do you sell those insulator sharpies? They should be in everyone’s toolbox!

    • @corymac
      @corymac  9 місяців тому

      They’re going in for patent

  • @jussikuusela7345
    @jussikuusela7345 8 місяців тому

    12:30 teught like a teuger!

  • @tcpnetworks
    @tcpnetworks 9 місяців тому

    @4:55 so will the brand of shoes you are wearing.....

    • @corymac
      @corymac  9 місяців тому

      True 😅. Measure with boots on! Stick with said boots

  • @Pieman2008i
    @Pieman2008i 9 місяців тому +2

    Those MEM busbar chambers are scary as fook never liked doing them.

  • @jonathanireland2913
    @jonathanireland2913 9 місяців тому

    Hi Cory great video as always. Would this need a Type 1 Surge Arrester on account of Over-ground power lines? I would assume the HV lines are over-ground as well as LV.

  • @protectiongeek
    @protectiongeek 9 місяців тому

    Is there no requirement to IR test the new tails and the supply side of the 4-pole isolator on the new DB *before* energisation?

  • @carlmarquardt994
    @carlmarquardt994 9 місяців тому +1

    Top job

  • @Yaki-2505
    @Yaki-2505 3 місяці тому

    See min 10:12 damaged conductor!! Have you replaced it??

    • @corymac
      @corymac  3 місяці тому

      Good eyes, that is actually tape on the cable I believe, however, yes it would have been pulled through anyways as we ended up with about 4 meters too much cable!

  • @patrickd9551
    @patrickd9551 9 місяців тому

    Oh the many accounts I have had with busbar widowmakers. My "favorite" one is the busbar with the bottle fuse holders bolted on top of them. Last one I did even had a fuse holder that was loose, basically just rattling around. But I was originally trained with those systems some 25 years ago. Let's just not recount the times I've done stupid things 🤐
    You say that fusebox is janky, at least your customers can't easily swap out the fuse size limit ring to a higher value, because "the fuse kept popping". Now I don't know about the specifics of UK DBs but I'll take any DB with resettable fuses over those bottle type DBs to be honest :D Sadly we can't choose what we get ;) That's why I've gotten into IT. Much safer job 🤣

    • @Ragnar8504
      @Ragnar8504 9 місяців тому

      In theory bottle fuse holders should have screws or sleeves that limit the fuse size (screws for the D type, sleeves for the D0 ones) but especially the sleeves for D0 holders are rare as hens teeth in the real world. The only time I've ever seen them used was in a block of flats where some git installed blue ones (20 amp) on a 6 mm2 supply to a flat for no apparent reason. I upgraded the supply to 10 mm2 as the original 1960 one relied on a 1.5 mm2 earth coming off of the water mains in the kitchen but couldn't change the fuses to 25 amps because I don't have the tool for removing those sleeves and didn't want to start messing with needle nose pliers and screwdrivers in live fuse holders. 20 amps seem to be fine though, that was almost ten years ago and I haven't heard of any blown fuses.

    • @patrickd9551
      @patrickd9551 9 місяців тому

      @@Ragnar8504That was what I was referring to. Those screws you can insert to limit the fuse size. I don't know where you live, but around here I can buy that tool for like 5 euro in the hardware store. Together with limiters. And sadly I've seen a few alterations in my life. The last one was about 4-5 years ago, I had to rebuy the tool, because I couldn't find my old one. But things needed fixing, so 5 euro it was :D

    • @Ragnar8504
      @Ragnar8504 9 місяців тому

      @@patrickd9551 The spanners for the screws (DII and DIII holders) are everywhere but the pliers for unclipping the sleeves in Neozed (D02) holders are rare as hens teeth. They're only about tenner online but I've never seen them in a shop (in Austria). And as I mentioned, I've only needed them once in my entire life. You can insert the sleeves without the pliers, just removing them is annoying. Besides, our network operator now requires switch fuses for all new or altered installations so Neozed fuse holders are getting less common.

    • @patrickd9551
      @patrickd9551 9 місяців тому

      @@Ragnar8504I must confess I have never seen those sleeved types, So i believe you :) And thank god that any type of bottle fuse is getting less common. They are a pain in the butt to service.
      But most probably even the spanners will go extinct in shops somewhere in the coming years as those installs are getting rare too. No need for shops to have them in stock anymore.
      At least we both our countries share the love for proper Shuko outlets as compared those UK terror plugs ;)

    • @Ragnar8504
      @Ragnar8504 9 місяців тому

      @@patrickd9551Yeah, fuses are likely to get less and less common. Austria still uses main fuses because it's difficult to ensure discrimination (selectivity) with MCBs but that's about it. Germany mostly switched to type E main MCBs at least 15 years ago.
      My main pet peeve with BS1363 plugs is the lack of an equivalent to the Euro plug, so even the smallest devices need a bulky three-pin plug. The amount of brass used for the pins is also slightly excessive for a domestic 13 amp plug.

  • @declang565
    @declang565 9 місяців тому

    Great video, but thought farm buildings were exempt from being connected to PME TNCS Earthing arrangement, so earth rod would need to be divorced from PME earth.

    • @corymac
      @corymac  9 місяців тому

      Correct, however this is a separate supply from the farm 😁

    • @corymac
      @corymac  9 місяців тому

      Also, it will be divorced anyways when we install the solar

  • @JohnDuffell
    @JohnDuffell 9 місяців тому

    everyone's said unsheathed cables on show on the henley blocks which is fair enough, but what's that insulating tape doing? If you can get it off without a tool then it better not be covering anything important!

  • @OGVElectrical
    @OGVElectrical 9 місяців тому

    Massive fan Cory been watching since the early artisan days, just wondering why when you are testing the new DB you are testing with the main switch on? Could have gave yourself a nasty one on the busbar

  • @aharonstubbs4089
    @aharonstubbs4089 9 місяців тому +1

    Should you not of fitted a 300 mA rcd with it being a farm ??

    • @aharonstubbs4089
      @aharonstubbs4089 9 місяців тому

      Or do you not need to because of the solor inverters ?

    • @corymac
      @corymac  9 місяців тому +2

      The whole thing will eventually be on TT and 100ma. It’s also not actually part of the farm, but a separate commercial unit

  • @tiemanowo
    @tiemanowo 9 місяців тому

    3:44 "insulated sharpie" sure, and few seconds ago you were poking those fuses with metal measuring tape ;)
    ps. nice video anyway :)

    • @corymac
      @corymac  8 місяців тому +1

      My bad 😂😅

  • @fire_stick
    @fire_stick 9 місяців тому +1

    Single insulated cables out side of an enclosure

  • @Spark101.
    @Spark101. 9 місяців тому

    Were those tails damaged? 😟

    • @corymac
      @corymac  9 місяців тому +1

      Nope 😁👍🏼

  • @duncanmast
    @duncanmast 9 місяців тому

    What's the company you are working with ? Onton Energy Wonton energy? No links in the description?

  • @franks_nl
    @franks_nl 9 місяців тому

    Surprised you didn't put a lock through those switches to prevent them being knocked on accidentally.

    • @UKsystems
      @UKsystems 4 місяці тому

      These big high current switches could be knocked on in theory, but you’re going to have to really put in a lot of force and effort generally

  • @tilidie5272
    @tilidie5272 9 місяців тому

    the other guy said it first but henley blocks should be facing downwards or maybe side ways, i think its something to do with IP rating? not 100% tho..

  • @robertmcdermott7526
    @robertmcdermott7526 9 місяців тому

    That's a spicy meatball

    • @corymac
      @corymac  9 місяців тому

      🤌🏼

  • @mouldyboats
    @mouldyboats 9 місяців тому

    Cory: It's a farm everything is just eh "hashed in"
    Also Cory: uses his nipples for mounting boxes.

    • @corymac
      @corymac  9 місяців тому

      They’re as reliable as the sun

  • @louis.reid1
    @louis.reid1 9 місяців тому

    i learnt that your normal sharpie is “insulated” 😂😂

    • @corymac
      @corymac  9 місяців тому

      😂😅

  • @stevo8629
    @stevo8629 9 місяців тому

    HI Cory, I am in need of some help with my solar installation. I want an EPS environment on my existing solar and need help with earthing. do you know anyone who can help me with that? thanks in advance.

  • @memamu0
    @memamu0 9 місяців тому

    Uff... Nice intro.

  • @waithereivegonetogethelp3240
    @waithereivegonetogethelp3240 9 місяців тому

    Why didn't you put the DB in, get the tails and everything set up, *then turn off the power and tap into the buzz bars? You'd only need the power off for a couple of minutes. Also for the PFC, you have a modern MFT there, you could just test phase to earth, neutral to each of the phases and phase to phase to get a true PFC.
    Love your work btw!

    • @corymac
      @corymac  9 місяців тому

      Trouble is, I couldn’t get the tails in until the trunking was in, and I couldn’t get the trunking in until I’d drilled a hole, couldn’t drill the hole til the power was off.
      Thanks man!

  • @timothyroper1897
    @timothyroper1897 9 місяців тому

    Sorrry cory i need to clarify my "slow down" comment as i mean the time pressure in the vidio is not what i mean what i mean is.. like a flash of the.. henly block man could do with longer to laph at the intro is funney just to short and you could do one at the end? hope that this is helpful to your chanal and not hipper critical. thankyou cory for all the great vidos.

  • @davidanderson7015
    @davidanderson7015 9 місяців тому

    100A block with 160A fuses