HVAC Delta T Explained! What Temperature Should it be?

Поділитися
Вставка
  • Опубліковано 5 вер 2024
  • In this HVAC Training Video, I Explain what Temp the Target Delta T Should Be for Single and Two Speed Air Conditioning Systems as well as Minisplits and Gas Furnaces! I Show how to Measure the Delta T. I also Explain How to Use Delta T measurements for Troubleshooting HVAC Units! Make sure to use Test Holes within a few feet before the unit in the Return and a few feet after the Unit in the Supply Duct. Supervision is needed by a licensed HVACR Tech while performing tasks as Experience and Apprenticeship garners Wisdom and Safety.
    Tools Used In The Video
    Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our Related Videos/Articles
    • HVAC Temp Rise Formula...
    • HVAC Thermal Limit Swi...
    • HVAC Quick Reference C...
    • Why Measure Both Super...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
    All Our Educational Products on Our Site: www.acservicet...
    All Our Educational Products on Amazon: amzn.to/48pDd82
    Mini Split Book and E-Book on Our Site- www.acservicet...
    Mini Split Paperback on Amazon- amzn.to/3ytHJSs
    Mini Split Paperback on TruTech Tools- www.trutechtoo...
    Refrigerant Charging Book and E-Book: www.acservicet...
    Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Online Resources!
    Our HVAC Calculators: www.acservicet...
    Our Newest Articles: www.acservicet...
    Try our HVAC/R Quizzes! www.acservicet...
    Our Other Resources: www.acservicet...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Tools Used in Our Videos!
    Tool Links on Our Site: www.acservicet...
    Our Tool List on Amazon: www.amazon.com...
    Support the Channel by purchasing tools through TruTech Tools!
    Use this link www.trutechtoo...
    Save 8% at checkout using code "acservicetech"
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Follow Us On Our Social Media & Podcasting Channels!
    Patreon: / acservicetech
    Facebook: / acservicetech
    Instagram: / acservicetech
    X: / acservicetech
    LinkedIn: / ac-service-tech-llc
    Tiktok: / acservicetech
    Spotify: open.spotify.c...
    Apple Podcasts: podcasts.apple...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    ⚠️ Disclaimer:
    Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided. ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    #hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #oil #thermostat #deltaT #temperature #gasfurnace #troubleshooting
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

КОМЕНТАРІ • 129

  • @acservicetechchannel
    @acservicetechchannel  4 роки тому +3

    Polystyrene "HVAC Quick Reference Cards for Refrigerant Charging & Troubleshooting"!
    Available at www.acservicetech.com/store
    Available at www.amazon.com/shop/acservicetech
    Get a Discount at "acservicetech.com" when you Bundle the Cards with the Paperback & Ebook!
    Get $5 off- Purchase the Cards and Paperback, use the Discount Bundle Code: "Dec19CP"
    Get $5 off- Purchase the Paperback and Ebook, use the Discount Bundle Code: "Dec19PE"
    Get $10 off- Purchase the Cards, Paperback, and Ebook, use the Discount Bundle Code: "Dec19CPE"
    These three HVAC quick reference polystyrene cards are double sided and designed to be used with Air Conditioners and Heat Pumps to measure the refrigerant level in a unit, charge refrigerant, troubleshoot refrigerant based problems, and measure heat transfer to determine if there is a problem during cooling mode.
    The Cards are each 5.625" by 8.85" and are made from Flexible Weather and UV Resistant Polystyrene. The print job and cards have been tested from 0°F-130°F. The cards have also been tested with exposure to common refrigerant oils.
    The Cards Contain:
    -Finding the Target Subcooling for Systems with a TXV Metering Device
    -Initial Steps Before Measuring the Refrigerant Charge with Subcooling
    -Measuring Subcooling to Determine if a System is Undercharged, Correctly Charged, or Overcharged
    -Example of System Measurement Locations for Measuring Subcooling
    -Finding the Target Superheat for Systems with a Fixed Orifice Metering Device
    -Initial Steps Before Measuring the Refrigerant Charge with Total Superheat
    -Measuring Total Superheat to Determine if a System is Undercharged, Correctly Charged, or Overcharged
    -Example of System Measurement Locations for Measuring Superheat
    -Measuring Delta T and Determining if the Temp Drop is Correct
    -P/T Chart for R-22, R-410A, R-407C, R422B (NU22B), and R438A (MO99)
    -Instructions for Finding the Sat Temp of R-22 and R-410A
    -Instructions for Finding the Dew and Bubble Sat Temps of Blend Refrigerants
    -Refrigerant Weight Per foot Chart
    -Instructions for Adding the Full Amount of Refrigerant needed
    -Instructions for Adding Refrigerant into a Running System
    -Example for Determining the Correct Amount of Refrigerant Needed in an Off, Empty, and Vacuumed Split System
    -Troubleshooting Guide for Systems with a Fixed Orifice or TXV
    -Use Measurements such as Superheat, Subcooling, Delta T, Vapor Sat Temp, Liquid Sat temp, Compressor Amps to Determine the Problem.
    -Use the Guide to Determine Problems such as a Liquid Line Restriction, Low Indoor Airflow, Contaminated
    Refrigerant, Low Outdoor Unit Airflow, Undercharged, Overcharged, TXV Bulb Charge Lost, Detached or Uninsulated
    TXV Bulb, Weak Compressor Valves, Reversing Valves Bleeding across the Tubes.
    -Step by Step Guide for Troubleshooting a Frozen Evap Coil on an Air Conditioner or Heat Pump in Cooling Mode.
    -Instructions to Determine if the Problem is a Low Refrigerant Charge, Low Airflow, or a Liquid Line Restriction.
    Check Out The Full Outline of our Book Including Sample Pages at: www.acservicetech.com/the-book
    Here is the Video Explaining What is Included in the Paperback and E-Book: ua-cam.com/video/Eb9p1DUNgeY/v-deo.html
    You can also support our work by purchasing tools and other items after entering amazon through our link at
    www.amazon.com/shop/acservicech
    You can support our continued work in making HVACR videos by joining www.patreon.com/acservicetech
    Thank you for all of the kind and uplifting words in each of your comments! I love to hear your stories and about your journey as you continue to grow in the HVACR field! We are all learning and growing all the time! Thanks to all of our supporting Patrons at www.patreon.com/acservicetech ! I really hope that the book and quick reference cards help each and every one of you in your journey to becoming an invaluable service technician in our industry!

  • @deanmartin1966
    @deanmartin1966 4 роки тому +9

    Nothing better than Sunday morning coffee and Hvac videos. Thanks for sharing.

  • @cam94cb
    @cam94cb 4 роки тому +10

    I have your book and I went to ivy tech for a Tech degree. I will say you put it in words that I understand. Thank you.

  • @rodgraff1782
    @rodgraff1782 3 роки тому +8

    The delta T you will get in the air conditioning mode depends on the entering air enthalpy (sensible heat + latent heat, or in layman’s terms, return air temperature + return air humidity, plotted on a psychrometric chart). This is the reason you have to take a wet bulb temperature at the return air to determine what the DeltaT should be. Delta T can run from 16-26 degrees on a normally running system, depending on return air enthalpy. The old way of calculating heat pump delta T, without running strip heating in the old days was called the output rule. The rule stated that at 70 degrees outdoor temperature, a heat pump would produce 30 degrees Delta T. For each ten degree drop from 70 degree outdoor temperature you loose 3 degrees on the Delta T, so at an outdoor temperature of 50 the delta T would be 24. This rule applied to the old R22 systems. I do not know if it is applicable to the newer systems, it was a good rule of thumb, that I used may times, when I did not have the manufacturers specifications.

  • @broncheemims8493
    @broncheemims8493 4 роки тому +5

    As a HVAC instructor your book is really great. Keep up the good work.

  • @strangefeline2799
    @strangefeline2799 3 роки тому +2

    Thank you AC Service Tech LLC. Your videos are a huge help in learning the trade. You are my go to resource along with a few books and technical manuals. I wish you all well for the services you provide us. Respect from an HVAC/R apprentice in Virginia.

  • @broncheemims8493
    @broncheemims8493 4 роки тому +2

    I bought your book and as a HVAC instructor you explain everything really well my student really like your book

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      That's awesome, thanks for letting me know! Is the book something that you may choose in the future to use for your students in the classroom? Thanks!

  • @robbrown3941
    @robbrown3941 4 роки тому +1

    It seems you have a video for something I’m worried about not fully understanding. It’s uncanny and amazing. Thank you sir. I’m going to send you a check when I make some real money in the business , for all the help you’ve given me. 🙏🏾

  • @stevengao8345
    @stevengao8345 4 роки тому +3

    at 0:50 , the equation is wrong, i believe the supply should always be colder than return, because the air go through the vapor coil ? shouldn't be return air - supply air = 19 , is it the calculation left/right position wrong ?

  • @don5176
    @don5176 2 роки тому

    Honeywell has an online essay, “Why Delta T is the Magic Number.” My 2010 edition of AHRI’s Fundamentals has a simple graph on page 662 adjusting return dry air for RH, and on page 668 makes the straightforward observation that a low Delta T indicates heat removing capacity has been reduced.

  • @marcusdarnell3348
    @marcusdarnell3348 4 роки тому +11

    Thanks man for sharing your knowledge! You are the best!

  • @tylerfabish5578
    @tylerfabish5578 4 роки тому +1

    Another thing to take note of is that an evaporator delta T is also related to the Sensible Heat Ratio in your area. Having a high SHR (0.85 or above) means most of your heat in the home is just sensible heat, and you would have a larger delta T and less condensate. A lower SHR (0.75 or even lower) is an indication of your home having lots of humidity. The coil will remove more heat from water vapor in the air, so more condensate, but less delta T. These values can be found in the literature provided with your equipment, and are used when doing a Manual D or Manual S.

  • @jesuscuh5118
    @jesuscuh5118 3 роки тому +1

    Watching this during my test

  • @reelheel5919
    @reelheel5919 Рік тому

    Ive been doing this kind of work over 20 years including 2 years of trade school and I have never heard the term delta t until today. I was taught to call it the differential or differential temperature. 🤷‍♂️

  • @publicmail2
    @publicmail2 4 роки тому +13

    How about a new video like this one on static pressure. Also, what percentage of calls do you find SP within spec. One of the most overlooked measurement drastically killing SEER ratings.

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +3

      Yes I am planning to do one in the future, thanks a lot AD and it's awesome that you are looking at the details! They all add up for sure!

    • @samuelsech2278
      @samuelsech2278 4 роки тому +2

      80-90% of the time I find high static pressure...

  • @MtPockets14U
    @MtPockets14U Рік тому

    Had one last week, leaky ducting, sucking air from wall cavity and attic space. Cut inspection hole under unit, spray foamed and sealed best I could and temp came right back up. Had to recover some juice from it also being over charged, without thinking it through first 2 other techs condemned the 7yr old unit.

  • @BartSimpson-nr1dy
    @BartSimpson-nr1dy 2 роки тому +1

    Absolutely priceless information you offer in this video. You are the best

  • @kennethblau3978
    @kennethblau3978 Місяць тому

    I have a 18,000 BTU AC in the gym at my apartment building complex. It is out puting at the air ducks vents 43 deg. And the air return is 74 deg.That tells.me that my Delta Temp is 30 degs. Not 20 or 23 deg! As you mentioned. When you compare the out side temp to the temp of the liquid refrigerant being condensed from a 100?% vapor to a 100% liquored. And the condensers temp is 135 deg and the out side temp is 100 deg hot day. The split delta T is 30 deg. So what is the lowest sub cooling that you could read at the end of the condenser coil? And it is being cooled with a big fan? Answer 100deg is the new temperature of that liquored line. You can not remove more heat from a liquored then the ambiance.temp that the fan is getting its cooling from. This is how I was educated on refrigeration systems.

  • @electricboogie709
    @electricboogie709 4 роки тому +2

    Craig. Great video. It’s well outlined. For a moron like myself, any way to add graphics with each point presented. Thank you for all you do.

  • @WilliamVG
    @WilliamVG 3 роки тому

    Just did a Delta T check on a old R22 unit with my new ST4 , only a 6 degree drop, lol.

  • @sheetmetalwork
    @sheetmetalwork Рік тому

    Great tutorial Craig.

  • @AJ-ox8xy
    @AJ-ox8xy 2 роки тому

    Yep I've had that happen to me where the temp split is 10degrees and everything was installed fine. It was just ridiculously hot. Outside was 118 and inside was 99. The system was able to level off by the time night came around and cooled off to 95 outside where inside settled around 75.

    • @ACommenterOnYouTube
      @ACommenterOnYouTube Рік тому

      my heat pump alone just gives a 10-12 deg difference. Inlet gets 65F and out the vents is like 75-77F ..... while its 45F outside.

  • @lilinamanda5299
    @lilinamanda5299 4 роки тому +3

    Could you please do a video of combustion analyzer of roof top package unit ? Thanks you

  • @joecrack7
    @joecrack7 4 роки тому +1

    Buddy you are the best! I did 2year program for hvac and have learned more watching your videos.
    I am full time licensed sheet metal. I do furnace swaps occasionally some gas lines and a little service for furnaces . But have wanted to get more into the refrigeration side.
    What would you recommend for simple basic gauges and first tools to buy . For new installations and some servicing on the side.
    Thank you !

  • @krisbumsted7628
    @krisbumsted7628 2 роки тому

    Would you please turn the captions on for this video. It makes it easier to follow for those that want captions. Thank you!

  • @hashimwaheed4906
    @hashimwaheed4906 4 роки тому

    This guy explains the best!!!! Thank you Sir!

  • @AJ-ox8xy
    @AJ-ox8xy 2 роки тому

    20 degree split is always what I aim for.

  • @bayouflats5054
    @bayouflats5054 3 роки тому

    Always clear and concise.

  • @dunckeroo1987
    @dunckeroo1987 4 роки тому

    Mass air density will be influenced by air temperature. Denser air can absorb (or reject) more heat per unit volume. So correction factors will attempt to measure heat change for a given mass such as BTU gain per pound of air. One might also want to measure the change in humidity to determine how much water was condensed (or vaporized) and include that heat too. Ah sensible heat and latent heat. Drying the air will reduce its volume 2 to 4% or total mass by 1 to 2%. or about 44 BTUs per cubic meter to reduce humidity 50%.

  • @pierre-oliviergauvreau8272
    @pierre-oliviergauvreau8272 3 роки тому +1

    Great stuff, very explained !

  • @jimbola77
    @jimbola77 4 роки тому +1

    Excellent video partner thank you for sharing!!!!!.

  • @Pretzel114
    @Pretzel114 4 роки тому

    Great instruction Craig! Helps me a lot.

  • @angelhernanadez6422
    @angelhernanadez6422 4 роки тому +1

    I have your book it’s great ! Bu when is a furnace book coming ?

  • @viper22304
    @viper22304 4 роки тому +5

    Thanks for great video.. I have a question? how do you set only the electric heating strip? do you set the tstat in emergency heat.

  • @jhaipaulramnarine8845
    @jhaipaulramnarine8845 Рік тому

    Hey love your stuff bro…can you tell me what is meant by start up process when installing a new unit

  • @TheRealoldcar
    @TheRealoldcar 4 роки тому +1

    Can you confirm the formula shown at 51s. It shows supply minus return.

  • @texture6
    @texture6 4 роки тому

    The Delta-T is a relationship to the TXV or Fixed Piston of Air Flow

  • @abazism
    @abazism 5 місяців тому

    What’s the difference between the E book and the other book that looks like it ?

  • @theresapaz77
    @theresapaz77 4 роки тому +3

    What do you use to cover the holes that you drilled into the Return and Supply Ducts in order to check the Delta T?

    • @christopherwallace2711
      @christopherwallace2711 4 роки тому

      Hard cast, pookie, or both

    • @eclipse369.
      @eclipse369. 2 роки тому

      Juicy fruit, he likes yellow 😆

    • @joshuabass8953
      @joshuabass8953 Місяць тому

      Silver tape that way next time you’re up there for a seasonal check you don’t drill more holes

  • @dapperdon7212
    @dapperdon7212 3 роки тому +1

    Quick question what happens if your sub & superheat are good, pressures are good, but you're only getting a 13 delta T? I ran across this twice both were rheem units.. heat strips weren't on either

    • @acservicetechchannel
      @acservicetechchannel  3 роки тому +1

      It could be the airflow is set too high or there is too much humidity in the building or both, thanks!

  • @kennethblau3978
    @kennethblau3978 Місяць тому

    Hi I am really confused to how you could only get a delta T Of only 23 deg.That would mean that when I first turn on my AC and the room is 88 deg. The evaporator coil is 66 deg. Not 55 deg. And when the room cools down to 75 deg my evaporator is down to 55 Deg. So when is my evaporator in my air handler going to be 45 deg@ 74 psi for R22 on my low side gage? Because that would make the inside air temp. 65 deg. And you could never get a 1.5 ton or 3. ton 36,000 btu AC to cool your home to 65 deg If the out side temp is 86 deg.I am reading a delta T of 30 deg a 55 deg evaporator is giving my home a 75 deg cooled room! Please reply back to me. Thanks ken

  • @wonyoon1931
    @wonyoon1931 4 роки тому +1

    I think the Supply temperature and Return temperature is reversed for AC mode.

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      Yeah it doesn't matter about the negative sign. You are just taking a differential and once you get it, it would be referred to as a positive number. I just didn't switch the two probes when moving from heating to cooling, thanks!

  • @donnierobertson3088
    @donnierobertson3088 3 роки тому

    Nice job and video

  • @tdok
    @tdok Рік тому

    So for cooling, is it bad to reduce fan speed to increase the delta temp to be within range?

  • @ejcsds
    @ejcsds 4 роки тому +3

    Question: Is the temp rise in a gas furnace the same for both stage 1 and stage 2? Hope I am asking this right?

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      In a gas furnace yes they are usually close temp rises since both the gas output and airflow speed both reduce but will depend on airflow speed and most use a variable speed. The most important thing to watch for is that the temp rise does not continue to rise as the furnace runs indicating low airflow, thanks!

  • @samuelsech2278
    @samuelsech2278 3 роки тому

    Best on youtube....

  • @stevemathey5316
    @stevemathey5316 2 роки тому

    Part number for the 3/8" rubber plugs to cover the holes in ductwork?

  • @ilovenythismuchilovenewyor5801
    @ilovenythismuchilovenewyor5801 2 роки тому

    so the true delta T is to be measured at the return and supply duct at the unit itself now at the return grill or any supply grill??

  • @imlon2
    @imlon2 Рік тому

    If you run a small duct from the supply back to the return lowering the temp of the air going back into the return will that lower the air temp even more coming out the supply?
    I get 20° but was curious if I was to do this if it would lower the temp by doing this.

  • @pizzle1011
    @pizzle1011 4 роки тому +1

    👍🏾👍🏾 another great video

  • @David-yy7lb
    @David-yy7lb 3 роки тому

    Excellent explanation but what's opinion on my delta T my return temperature is 73 and the supply is 48 so that's a 25 degree delta T but I have my thermostat on 72*, and the outdoor temperature is 84* today

    • @acservicetechchannel
      @acservicetechchannel  3 роки тому

      If its a standard single speed unit and not a minisplit, the high delta T likely means low airflow.

  • @DavidDachauer
    @DavidDachauer 3 роки тому

    Thanks for this video. I have a 4-head Mitsubishi mini-split system. Delta-T varies at each head: 13, 14, 15, and 20 degrees. Less than a year old. Last year, a week after initial installation there was a leak in one of the lines found (I spotted oil from the leak running down the exterior of the house). The tech fixed it but said there was plenty of refrigerant and so didn't add any after the incident. Should I be concerned?

  • @zekenzy6486
    @zekenzy6486 4 роки тому +2

    Now I know what is Delta T , my company everyone keep call TD ^_^

    • @Oscarbm1234
      @Oscarbm1234 4 роки тому +2

      They mean Temperature Drop. My company use to say the same thing.

    • @BartSimpson-nr1dy
      @BartSimpson-nr1dy 4 роки тому +1

      ZE KENZY - actually TD refers to temperature differential which is the the same as delta t. Just another way of saying it. As the Greek triangle (Delta) means “change in”. Thus the equation DeltaT= T2 - T1

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +2

      I read that too fast. TD is different than Delta T. TD is the temperature difference between the return air db temp and the saturated refrigerant temp in the evap coil. Example: 70 degree return air minus 40 degree refrigerant sat temp= 30 DB. The higher the TD, the more humidity will be removed from the building. The word difference being used means the temp of two different mediums where as Delta T is the change in temp of one medium. DB is common for refrigeration when talking about humidity levels needed to store different types of products. Thanks and great question!

    • @BartSimpson-nr1dy
      @BartSimpson-nr1dy 4 роки тому

      AC Service Tech LLC - amount engineers, TD is the same as Delta T.
      Temperature Differential

    • @junkyardjedi7706
      @junkyardjedi7706 4 роки тому

      My old co. Called it "the split" 😃

  • @curtish.128
    @curtish.128 4 роки тому

    I just have a question, do you use a wet wetbulb sock while doing a delta T measurement?

  • @serialseatsniffer5610
    @serialseatsniffer5610 Рік тому

    For some reason this season, I’ve come across numerous package units pulling 30 degree dT’s. With proper charge, fixed speed fan, is there anything else besides airflow to rule out?

  • @adandridsr
    @adandridsr 4 роки тому

    I have a heat pump. In heat mode the out door unit shuts down on high pressure safety according to a HVAV technician. He checked air flow across indoor coil and said it was ok. His conclusion was that systems with R410A should not be ran in heat mode when outside air temp is 65 deg or above. Is this true?

  • @TsuyoiTCG
    @TsuyoiTCG 2 роки тому

    Where can I find the Delta T values for mini split units?

  • @danielventurini7513
    @danielventurini7513 3 роки тому

    Can you do this same calculation on a furnace or is it only meant for air conditioning?

  • @JM-gx7iv
    @JM-gx7iv 3 роки тому

    Hi Craig, I was wondering how to measure return temperature on a handler that has no return duct. It's an upflow in a closet (louvered door). Would I measure at the bottom opening of the handler (where filter is located) or should I stick my temp probe through the louvered panel? The supply duct is easily accessible and I can measure that one fairly easily. But unlike in this video, there is no return ducting, the return is the door itself (in a centralized location). Just curious, any tips to help this new tech would be appreciated.

  • @WillieMakeit
    @WillieMakeit 4 роки тому

    Hello Craig, I tried to find a email to you but could not. Off topic question if you don't mind. Would you have a long form of a manual J you would copy and sell? and What manual J program would you recommend buying for heat gain and heat loss calculations? Is there a good app out there that makes this easier. Thanks in advance. Great book by the way.

  • @davidarroyo1375
    @davidarroyo1375 4 роки тому

    Can you measure temperature difference comparing ambient temperature vs outdoor condenser temperature?

    • @davidchipman6573
      @davidchipman6573 4 роки тому +1

      David Arroyo measure inlet ( thermometer on side of condenser), then measure outlet ( thermometer measuring the air coming out of the top of the condenser) should be about a 10 degree difference. I.e. 90 degree inlet, 100 degree outlet

  • @RobRocker09
    @RobRocker09 3 роки тому

    would the delta t be off with a mismatched unit ?

  • @largenj
    @largenj 2 місяці тому

    causes of LOW delta T?

  • @muhammedameen1818
    @muhammedameen1818 4 роки тому

    Hey Craig how can I get your book. Right now I'm in UAE

  • @mark.r8900
    @mark.r8900 4 роки тому

    hi, for fixed orifice system. high heat load would caused high superheat. high super heat would caused high pressure on the high side. wouldn't this high pressure on the high side PUSH MORE refrigerant into the evap to compensate? so the amount of refrigerant going through the orifice varies/changes based on pressure differential between high side and low side. please help me to clarify this concept because you're saying the orifice ALWAYS ALLOWS the SAME amount of refrigerant through and this is where i get confused. your book is just amazing. Thank you.

    • @eclipse369.
      @eclipse369. 2 роки тому

      It seems you answered your own question?
      For it not to always allow same amount would seem to me to be the case of severe undercharge, restriction before orifice, faulty compressor.
      Think of it like water through a pipe that had a cap midway with a drilled hole in it perhaps?
      Only a certain amount of water could go through the hole regardless of pressure granted it meets the minimum

  • @159357ahmed
    @159357ahmed 4 роки тому +1

    are there similar rules for condenser unit Delta T

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +1

      We usually don't because the fluctuation in the outdoor db temp is much higher than the indoor. The indoor db temp may be 68 to 78 degrees whereas the outdoor db temp may be 70 to 105 and this will affect how much heat is able to be rejected outside, thanks

    • @159357ahmed
      @159357ahmed 4 роки тому +1

      @@acservicetechchannel thanks alot for these important information

    • @159357ahmed
      @159357ahmed 4 роки тому +1

      @@acservicetechchannel can you please make a video about dirty condenser and insufficient condenser fan air flow (like someone make the wrong replacement for condenser fan)

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +1

      Ahmed, thank you for letting me know what you would like to see!

  • @imkallam
    @imkallam 4 роки тому

    Who's one is right
    Means any conditions for these 2 cases
    Plz help
    ∆T = SAT - RAT
    or
    ∆T= RAT-SAT
    or Both right

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      Delta T can technically mean both but when you are talking heating Delta T can also be referred to as "Temp Rise". I will say that you hear the term Delta T used more in air conditioning mode where RAT-SAT thanks!

    • @TheRealoldcar
      @TheRealoldcar 4 роки тому

      At 51 second on the video, I think the formally is incorrect

  • @larrycavanaugh7410
    @larrycavanaugh7410 4 роки тому

    Hi your videos are informative! Hi I have a single ductless 12,000 BTU heat pump my set temp is 24° but my room temp is 18 could you explain what may be happening it is -10 outside thanks

  • @louielor5399
    @louielor5399 4 роки тому +1

    Where can I purchase your books?

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      at our website at www.acservicetech.com and also www.amazon.com/shop/acservicetech and the full outline and sample pages are at www.acservicetech.com/ac-book thanks!

  • @holtrussell
    @holtrussell 3 роки тому

    Craig, great info! Really dumb question if you have a moment. Is it possible in AC mode to have a “normal” 20 degree delta T and be significantly low on charge (maybe just above where a coil would ice over)? What I’m struggling with is despite the fact that the refrigerant is there to do it’s job, in theory, because of a lack of refrigerant, the coil should be very cold and still cooling the air going through it. Is this situation possible? Thank you!

    • @acservicetechchannel
      @acservicetechchannel  3 роки тому +2

      The only way you could have 20 degree across the coil and be low on refrigerant is if you are low on airflow too. This would result in a lower overall system capacity, thanks!

    • @holtrussell
      @holtrussell 3 роки тому

      @@acservicetechchannel Thank you so much Craig!!

  • @adoseofreality8301
    @adoseofreality8301 3 роки тому

    Hey Craig, my ac thermostat got reset by accident. I gave an question..... my ac thermostat is saying it’s 79 in here, which I KNOW it’s not. I went and brought in an external thermostat and it’s showing 77 which it definitely feels like, that’s way more accurate. So the issue is that my ac keeps showing a higher temp than actual temp, so ac keeps turning on. I feel like it has something to do with the cooling stage 1 on or off? I could be wrong but what should the setting be on, as far as inside/outside cooling stage 1?? Or does that have nothing to do with what’s going on? UGH! 😩😫 pleeeease help

    • @eclipse369.
      @eclipse369. 2 роки тому +1

      Adjust for 2 degree offset or replace tstat?
      Ie you want it 75, keep at 77

  • @9to5techs
    @9to5techs 6 місяців тому

    I thought electric resistant heat Delta t was like 35 f

  • @1mrsleepy1
    @1mrsleepy1 4 роки тому

    Do you calibrate everytime you use your dual sensors?

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +1

      No just calibrate maybe once a month but continually watch if the t1 minus t2 seems high when they are in the same location to see if one is getting off. If one seems off then calibrate to verify. Always have another in the truck because the sensor could go bad at any time due to the small thin wire resistance changing if there is a twist or nick in the wire, thanks!

    • @1mrsleepy1
      @1mrsleepy1 4 роки тому +1

      @@acservicetechchannel thanks for replying. In school they have us test em every time

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому

      Ice water every time? I guess if you don't know who was using the tool before you then you should check. Did you do this every day or was this a once or twice a week in the shop time? Thanks

  • @MrGatlin98
    @MrGatlin98 Рік тому

    Can you measure Delta T at the vents? It's 65 degrees outside, and inside my house is 75 degrees. The AC is set to 74 has been running for over an hour and the temp is still 75 degrees. Coming out of the vents is about 66 degrees, which is a Delta T of 9, but I don't know if I can check it at the vents.

  • @smacleod69
    @smacleod69 4 роки тому

    Two digital thermometers from harbor freight will save you money than buying that delta t meter