HVACR 3 Position Service Valve, King Valve: Front-Seat, Mid-Seat, Back-Seat

Поділитися
Вставка
  • Опубліковано 30 лис 2024

КОМЕНТАРІ • 44

  • @acservicetechchannel
    @acservicetechchannel  5 років тому +2

    The E-Book and Paperback: www.acservicetech.com/the-book
    Tool List- www.amazon.com/shop/acservicetech
    Support the Channel- www.patreon.com/acservicetech
    For those that are looking for the tools used in the videos: (Linked Below)
    Appion Valve Core Removal Tool amzn.to/2uYr8WL
    RectorSeal Bubble Gas Leak Detector - amzn.to/2ckWACn
    25 Valve Cores - amzn.to/2L37UJU
    25 ¼” Brass Port Caps with rubber O-rings - amzn.to/2GIOdD2
    Brass Valve Core Tool which holds 3 valve cores - amzn.to/2GFEbm2
    Valve Core Torque Wrench - amzn.to/2GHiLoD
    Locking Cap Universal Lock/Unlock Tool - amzn.to/2GGAoVp
    Locking caps - amzn.to/2GFXZ8A
    Ratcheting Service Wrench amzn.to/2dGV4Nh
    Yellow Jacket Sealright 90 Coupler- amzn.to/2LsU1V7
    Yellow Jacket 1pk Compact Ball Valve- amzn.to/2uXdF18
    Yellow Jacket 3pk Compact Ball Valve- amzn.to/2AiKfQe
    Thumb Screw Valve Core Depressor with Backseat- amzn.to/2mR0sCL
    UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ
    Yellow Jacket Refrigerant Gauge Set amzn.to/2aenwTq
    Refrigerant hoses with valves amzn.to/2aBumVI
    Yellow Jacket Gauge set & hoses amzn.to/2vLVkV9
    Yellow Jacket 4 Port Manifold w Hoses amzn.to/2BkuGIq
    Digital Refrigerant Scale amzn.to/2b9oXYl
    Ratcheting Service Wrench amzn.to/2dGV4Nh
    Accutrak VPE Ultrasonic Leak Detector amzn.to/2nFYKVe
    Accutrak VPE-GN Ultrasonic Leak Detector amzn.to/2Zy4IZP
    FieldpieceSMAN360 Digital Manifold Set amzn.to/2BdoaD4
    FieldpieceSMAN460 Digital Manifold Set amzn.to/2nB4Fe6
    Ultrasonic Leak Detector with Headphones- amzn.to/2B2cRO3
    Compact Ball Valve for Refrigerant Hose amzn.to/2KUisW8
    QuickDisconnect 90 for refrigerant hose amzn.to/2MMtVcg
    JB 6 CFM Vacuum Pump amzn.to/2nqbvo8
    Appion Blue 3/8" to 1/4" Vacuum Hose amzn.to/2uYlVyc
    Appion Red 3/8" to 1/4" Vacuum Hose amzn.to/2uYg6Ro
    Appion Valve Core Removal Tool amzn.to/2uYr8WL
    Yellow Jacket 1/4" by 1/4" hose amzn.to/2umtcod
    CPS Vacuum Micron Gauge amzn.to/2v1nM3O
    Supco Vacuum Micron Gauge amzn.to/2v1JRiA
    RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
    Magnet Jumpers- amzn.to/2PyKPQZ
    Alligator Jumpers- amzn.to/2PxqJXn
    Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3
    Fieldpiece Bead K Type Temp Sensor amzn.to/2DBwKfs
    Fieldpiece Wet Bulb Temp Sensor amzn.to/2RRI7Tw
    Fieldpiece TC24 Temp Clamp amzn.to/2qHLyjZ
    UEI DL389 Multimeter amzn.to/2xAdaJf
    Air Acetylene Torch setup amzn.to/2aQalsb
    15% Silver Brazing Rods amzn.to/2gVLyLc
    Nitrogen Regulator amzn.to/2bXdR5f
    Nitrogen Flow Meter amzn.to/2brvoBg
    Other tool links can be found in the video description section.
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech

  • @spongeblob4987
    @spongeblob4987 5 місяців тому

    New into the field and had to study this for my midterm exam. Kept confusing front with back, appreciate you showing the actual service valve itself and explaining how it works.

  • @jonathanjuarez316
    @jonathanjuarez316 3 місяці тому

    Thank you so much I've been on the roof all day trying to figure this out!!!

  • @RayRay-nb7tn
    @RayRay-nb7tn 5 років тому +3

    I have been away for awhile but back watching videos. Glad that you have your channel still. As always a great learning experience for everyone and explanation of items. HVAC ON!!!

  • @zesty2023
    @zesty2023 4 роки тому +4

    Okay.. yeah so I was looking at my Carrier unit for the first time and was so confused why there were no shraders and I wasn't getting any pressure on my gauges.. thanks.

  • @bobrebera494
    @bobrebera494 5 місяців тому

    great explanation,just ran across one of the valves

  • @tylerfabish5578
    @tylerfabish5578 5 років тому +1

    the first valve is just a 3 position suction valve, the second valve is a king valve, mounted on the receiver (liquid line)

  • @cristianrozadilla2783
    @cristianrozadilla2783 5 років тому +1

    Válvula de 3 vías, buena explicación

  • @acestu
    @acestu 5 років тому +1

    Thanks Craig

  • @Eddy63
    @Eddy63 5 років тому +1

    Good vid Craig ...

  • @bobsanders6889
    @bobsanders6889 3 місяці тому

    Can the king valve caps for this unit still ne purchased

  • @wasimedoo7994
    @wasimedoo7994 3 роки тому

    Very good information my friend God bless keep it up

  • @prabalmitra9532
    @prabalmitra9532 5 років тому +1

    Just wondering if it wouldn't have been a good idea to insert a diagram of these valves on the upper left corner along with your explanation.

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Hey Prabal, I have the photos of those in the book and I believe as one of the book sample pages at acservicetech.com thanks!

  • @WanNotJuan
    @WanNotJuan 3 роки тому

    Thank you so much!

  • @publicmail2
    @publicmail2 5 років тому +2

    Still like metal gasketed caps, what PSI are the good ones rated at?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      That I am not sure of but I am sure it is very high. That will depend on each manufacturer and they may not give those specifics, thanks!

  • @DanO181919
    @DanO181919 5 років тому +1

    Thank you!

  • @silverrambo1508
    @silverrambo1508 Рік тому

    How can I know if I have 2 position or 4 position king valve ? How to recognize them ?

  • @DanO181919
    @DanO181919 5 років тому +1

    I just purchased your paperback book, I was just wondering if you have a lot of troubleshooting topics in your book

    • @acservicetechchannel
      @acservicetechchannel  5 років тому +2

      Yes there is quite a bit in there. Please let me know what you think of it after reading, thanks!

  • @Jiggywithfacts
    @Jiggywithfacts 5 років тому +1

    Hello Craig. I have a r404a small type appliance a slushy machine to be specific. I need to recharge it. How do. I charge it. How much psig and oz should I fill it up to. There is no reading on the compressor or on the side of the machine. Thanks in advance. Should I charge it thru liquid line ?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      You would need to look up the model number or find the rating plate. There should still be a plate somewhere on it that shows the total weight. You would break the vacuum with the total amount of liquid refrigerant needed for that packaged unit, thanks!

  • @fromanabe8639
    @fromanabe8639 3 роки тому

    I think the service valves on my 40-year-old Friedrich compressor are three-position but I'm not certain. Both valves have a square stem on top covered by a black plastic cap. The access ports are just above the vapor and/or liquid lines and have no Schrader core. They have a small threaded metal cap. Any comments?

  • @kckc6578
    @kckc6578 5 років тому +1

    How do you tell whether a valve is a 2 position or 3 position service valve when looking at a unit?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      When you take the port cap off of the service valve, there will not be a schrader valve core. There will also be a large ca at the top and under it will be a large exposed stem, thanks!

  • @acrepairnearme
    @acrepairnearme 5 років тому +1

    Cooool. Great Expectations. Very informative, More About refrigeration equipment stuff )

  • @funforlife3848
    @funforlife3848 5 років тому

    Sir hmra ek 1.5 Ton ka MITSUBISHI k ac hi jab MI start krraha hi to 5 mint compressor chal rha hi phr compressor bnd hojaraha hi Magar fan continue chl rha hi kyaaaa masla hoskta hi

  • @wickedjiry7096
    @wickedjiry7096 4 роки тому

    I been having trouble closing king valves at my job is there a way to do it on a actual system for a better understanding

  • @rashpalsingh2905
    @rashpalsingh2905 4 роки тому

    Hi sir how to repair or services of this spandel value

  • @mikecastro4403
    @mikecastro4403 4 роки тому

    This video was very informative. So i have a question, Is there a position that the HVAC service valve can be where the heater would work but not the AC? I am having this problem right now. During the winter, the heater was working fine but now that its starting to get hot, the AC is blowing hot hair, but the heater is still working. The cooling setting blows hot air even when its not very hot outside. BTW i had my old co-worker work on my AC last winter, (who is HVAC certified) and refilled my freon. He also had told me that the king valve leaks if its in a certain position. So the position that he set it at doesnt leak, but now is when im noticing that the AC doesnt blow cold air. Your help is very much appreciated. thanks!

    • @strimbimmin328
      @strimbimmin328 4 роки тому

      Do you have a heat pump with strip heat? If so it sounds like your refrigerant has leaked out so the refrigeration circuit is trashed but your heat pump still bumps on the heat strips (emergency heat) and warms your house up.

    • @mikecastro4403
      @mikecastro4403 4 роки тому

      @@strimbimmin328 Thanks for the response, apparently there was not a leak like the previous HVAC technician told me. The problem was a wiring issue.

  • @matttzzz2
    @matttzzz2 Рік тому

    Can't you just use the front seat to add refrigerant? Since the valve will be open only to the suction side of the compressor which will suck the refrigerant out of the refrigerant cylinder, negating the use of a recovery unit or hot water bath to help push the refrigerant out of the cylinder

  • @5822huron
    @5822huron 3 роки тому +2

    Still confusing