Understanding System Voltages, NEC 2020, (46min:29sec)

Поділитися
Вставка
  • Опубліковано 17 гру 2024

КОМЕНТАРІ • 112

  • @Nahum17good
    @Nahum17good 3 роки тому +36

    Not only do you inspire me to be a better electrician, but you also inspire me to be a better person! God bless you and your family.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому +7

      What a lovely message, thank you.

  • @QuaabQueb
    @QuaabQueb 3 роки тому +14

    17:40 this is the type of energy and personality that makes a truly great teacher, a person so filled with not only the knowledge but also the drive, the passion and the overwhelming excitement to tell it to others.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому +2

      Thank you, I did get excited...

  • @noahmchugh3769
    @noahmchugh3769 3 роки тому +5

    Mike, I’m a 3rd year apprentice and I’ve heard your name a couple times and this is the first video of yours I’m watching and my first impression of you is excellent. What set that is how you start by giving our Father in heaven the glory.

  • @4eightyvolt
    @4eightyvolt 3 роки тому +2

    For those confused the illustration @ 3:00 is a typo. The primary should be "480/20 turns = 24v per turn" and the secondary should be
    "24v per turn x 5 turns = 120v". Mr. Holt explains it correctly though. Just fyi

  • @lauratanner8475
    @lauratanner8475 2 роки тому

    Mike Holt is a Dynamo!! Always passionate and right on the mark. Probably no one else has ever had so much working knowledge of the code.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I love helping you guys, so I guess that is obvious!

  • @rickpina5000
    @rickpina5000 3 роки тому

    This is gold. The knowledge you give us, no one will ever be able to take away.

  • @lawtonsegler1923
    @lawtonsegler1923 3 роки тому +3

    Regarding three phase autotransformers, I worked for an OEM that manufactured large three phase motor operated equipment that was sold around the world, so we used custom three phase autotransformers with taps configured for our existing 480v as well as 380, 400, and 575, all in one transformer. Large contactors were used to select voltages required by the unit under test. I know Hammond Power Solutions lists these in a catalog with common voltages, but they’ll also build you one to your specifications. I liked to use a company in Canada called Marcus Transformer. They’re real easy to work with, have a fast turnaround, and fair prices. If you call them they’ll answer in French, but will switch to English, lol…. Also, Staco Energy Products makes super slick systems like this and will build you an all-in-one package to your specs, and they provide expert advice. We even had one of their 300 KVA three haze variable autotransformers that would deliver anything from 1 to 480v. It was pretty cool. I know this really isn’t helpful to most of the audience, but knowing this stuff exists may come in handy.

  • @marcemarce9821
    @marcemarce9821 2 роки тому

    He said, ook I am been told too fast lol Thank you Mike there is no Mike you're making a big difference for many people, thank you God bless you, I don't have my licence but I am trying.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I don't know the term 'I'm trying.' This appears to provide lots of excuses to not comit. Please call 352.360.2620 and allow my staff to get you on a program to 'pass' your exam the first time.

  • @phillbenitez4216
    @phillbenitez4216 3 роки тому +2

    Thanks Mike. God bless you all!

  • @unsanctionedshortstories5778
    @unsanctionedshortstories5778 2 роки тому

    Mike Holt the legend. Sir thank you for all your work and we appreciate it!!!!

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Thank you and you are most welcome.

  • @steven7650
    @steven7650 3 роки тому +2

    IIRC you can use whatever color scheme you want as long as you're consistent in the building. So if you make your high leg zebra pink striped, well that's what all of them in that system have to be. I believe there's an exception for repair work and it must be permanently clearly labeled that the colors do not match the rest of the facility.

  • @Proiectediversediy
    @Proiectediversediy 3 роки тому +2

    Thanks Mike.Congrats from Romania.

  • @NOTTV7
    @NOTTV7 3 роки тому +1

    Thanks Mike very much needed information

  • @NameLess-ks4fi
    @NameLess-ks4fi 3 роки тому +3

    Mike is the GOAT

  • @mahadihasan93
    @mahadihasan93 3 роки тому +2

    As always outstanding content. Thank you.

  • @seantreakle1174
    @seantreakle1174 4 місяці тому

    What concerns me Mike when You're gone who's going to take over. Somebody has to come forth and stand and take your place. Without these programs the industry suffers. I couldn't imagine not having these programs Sean Denver Colorado

    • @MikeHoltNEC
      @MikeHoltNEC  4 місяці тому +1

      Sean, when I'm gone MHE will still be there with great leadership and technical skills. But these Mike Holt Video posts will not be replaced... so I hope others value what I'm sharing and show gratitude and not give me any crap.

  • @85agyoung
    @85agyoung 8 місяців тому

    In the video for a Highleg system you show 3 windings on the secondary side. Typically a highleg system would only have 2 windings. This would be the primary purpose for a high-leg or open delta saving money or reducing material. The 2 windings especially on the utility side would be used. The vector of this setup would look like a T. With the node of the T being your neutral connection. The Y axis in the vector would be your high-leg or 208 to neutral voltage.

    • @MikeHoltNEC
      @MikeHoltNEC  8 місяців тому

      A closed or open Delta secondary with a neutral will both give a high-leg voltage of 208V.

    • @85agyoung
      @85agyoung 8 місяців тому

      Agree with the closed delta giving you the same results. I have never installed or seen a closed delta highleg.
      Keep up the awesome videos! They have helped me out with getting a better understanding of the NEC.

  • @tfun101
    @tfun101 9 місяців тому +2

    Mike people keep telling me I’m wrong..I just want to make sure. If I have a 480 primary and 208/120 secondary transformer, or any other kind of transformer for that matter..Let’s say the neutral on my secondary is bonded correctly with a SBJ and I have an effective ground fault current path, and everything is correct. EXCEPT I don’t ground my transformer to the dirt, or building steel, or a water pipe or anything else. I still clear faults and still have correct voltages right? People are telling me it’s a floating neutral and my voltages are all going to be off and I’m not clearing faults, etc.

    • @MikeHoltNEC
      @MikeHoltNEC  9 місяців тому +1

      Yes, you are 100% correct. The secondary bonding established the zero reference and effective ground fault current path. Of course you knew that.

  • @poolsdoc9178
    @poolsdoc9178 3 роки тому

    Amazing theory book, every electrician should have it 👌👍👏

  • @jolyonwelsh9834
    @jolyonwelsh9834 3 роки тому +2

    You are not allowed to use slash rated breakers on an ungrounded or a corner grounded system. I wish they would make all 2 pole breakers straight rated for this reason. It would not cost much more in that they would all be made to the same standard. After all, all three pole breakers are straight rated.

  • @danielgladstone1789
    @danielgladstone1789 3 роки тому +2

    Hey Mike, great video as always. One question though: Do you use any particular software to draw your diagrams? I like how they have clamp meters etc on lines that you want to display the current reading. Makes the diagram very easy to follow and I'd like to be able to produce diagrams like that for my work as well

  • @arthurcage275
    @arthurcage275 Рік тому

    Can u make a Playlist that is in order of videos to watch to understand theory

  • @frederickmartinburg7591
    @frederickmartinburg7591 3 роки тому +2

    Hello there Mike, I'm preparing for the master electrician test. Which testing material would you recommend?
    God bless

  • @michaeljiron7038
    @michaeljiron7038 2 роки тому

    The question that was asked around the 30 minute mark... Does the SSBJ have to be bonded to the metallic raceway that connects the transformer to the first means of disconnect. Aka ground bushings. Does the answer change if it's flex or EMT?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Feeder/branch circuit bonding is only required per 250.97 for 277/480V circuits where there is a KO. Nothing else.

  • @elc2k385
    @elc2k385 3 роки тому +1

    This video is going in my Favorites.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      I love this topic. It answers so many questions.

  • @flinfaraday1821
    @flinfaraday1821 Рік тому

    3:45 The top labels in this graphic make no sense to me.
    480V/20 turns = 48V per turn??
    24V x 5 turns = 240V??
    How?

  • @asperbergers7136
    @asperbergers7136 9 місяців тому

    999th like Mike! Thanks for everything you do!

    • @MikeHoltNEC
      @MikeHoltNEC  8 місяців тому

      Aww, thank you for the compliment.

  • @agussurachman5246
    @agussurachman5246 2 роки тому

    3:18 in left slide, 480V/20 should become 24V instead of 48V, shouldn't it?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Yea.... crap... thanks. Sorry for the typo.

  • @jeremymcguire7069
    @jeremymcguire7069 3 роки тому

    The pace of this presentation is very fast. That challenges me to follow along and keeps my attention focused. Thank you, you're an excellent instructor.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому +1

      Yes it is, but the second and third time you'll notice that I'm going slower...

  • @dwaynes965
    @dwaynes965 3 роки тому +3

    I use 208 single phase all the time. 2 hot leads and a ground. no neutral.

  • @1x_technologies
    @1x_technologies 3 роки тому

    Fantastic job Mike!

  • @MrBelal79
    @MrBelal79 3 роки тому

    Amazing video as always, also I bought your books, it's amazing.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому +1

      Thank you and I'm honored to be part of your success story.

  • @brianmcdermott1718
    @brianmcdermott1718 3 роки тому

    Great info. As usual. Thanks Mike.

  • @robbullock3662
    @robbullock3662 3 роки тому

    I love your videos! That does look like a bong on your back shelf though

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I did remove it for that reason.. lol.

  • @Lionofjudah308
    @Lionofjudah308 3 роки тому +2

    Amen brother

  • @bradyy2052
    @bradyy2052 7 місяців тому

    I watch this to fall asleep hopefully some of the knowledge stays in my head tho fr

  • @ecospider5
    @ecospider5 3 роки тому

    At the 3 minute mark your slide is Transformer Turns Ratio. The bubble at the top says 240v. Shouldn’t that be 120v. So 24v per turn x 5 = 120v.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      Yep, sorry for the typo in the graphic.

  • @ohmware2020
    @ohmware2020 2 роки тому

    hi make, please make a video about single phase 2 wire system, line to ground/neutral system

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I'm confused, 2-wire is just that, 120V L-N

  • @tvblood3550
    @tvblood3550 3 роки тому

    So in a single phase system, one only wire makes the main circuit and then comes the neutral and earthing,it's like a game in wich to got shocked I just have to close a circle=circuit I get that it's all pretty clear in the figures you show, actually thanks to your drawings I can understand now the whole thing. But now, where does the big circuit ends?
    Because being a big circle means L1 must meet L2 in some point right? According to your first lesson( current always come back to the source), L1.should come back to the source using to paths (neutral wire or L2 wire) so where does L1 becomes L2? Is this meeting point a phisical place like a substation or something?

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      Watch ua-cam.com/video/mpgAVE4UwFw/v-deo.html

  • @brianharmeson3144
    @brianharmeson3144 3 роки тому

    I have a question concerning high leg identification. You stay in this video and in your diagram that the high leg must be orange. However, the code states the high leg can be identified by an orange outer covering "or another effective means". So, my question is, is the high leg actually required to be orange If you use another effective means to identify it? Thank you.

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      I can't find where I made that statement. The identification of the high-leg conductor must be in accordance with 110.15.

  • @soloado5084
    @soloado5084 3 роки тому

    Sir, I want you to clear this confusion in my mind raised after listening to your talks on grounding .
    Please , I know dis video is off it .
    Can one say that grounding/earthing only takes care of events created by lightening ?

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      Watch MikeHolt.com/Fundamentals and you'll understand what I'm saying.

  • @kahlil4745
    @kahlil4745 Рік тому

    The ruler thing is silly. It's a sine wave and that measurement is related to the area under the curve.

  • @rigobertoruiz6136
    @rigobertoruiz6136 3 роки тому

    Which videos are the first two we need to watch?

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      This is the summary, so only this one.

    • @shellypizzo6664
      @shellypizzo6664 3 роки тому

      Yes he mentions 2 previous videos that should be watched before this if he is going to fast. What are they?

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      @@shellypizzo6664 This was a series of 'live' video recordings. Only some of these are kept on UA-cam. Sorry.

  • @mikewendell4748
    @mikewendell4748 3 роки тому +1

    Thanks Mike

  • @Jecoopster
    @Jecoopster 3 роки тому

    Who has the links to the first two videos?

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому +1

      There were all combined into this summary video.

  • @Roberto-cg2gr
    @Roberto-cg2gr 22 дні тому

    Check IEEE 3000 series on System Grounding as an update to BEEMAN or at least IEEE Green book chapter 1 System Grounding

    • @MikeHoltNEC
      @MikeHoltNEC  22 дні тому

      I didn't know this! I just bought IEEE 3002!

    • @Roberto-cg2gr
      @Roberto-cg2gr 22 дні тому

      @MikeHoltNEC
      Ungrounded has an advantage of continuity of service if there is limited loads. No trip on a single line to ground fault unlike solidly grounded. Alarm only

    • @MikeHoltNEC
      @MikeHoltNEC  21 день тому

      CORRECT

  • @buckaroundandfindout
    @buckaroundandfindout 2 роки тому

    Much love mike.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Thank you, and the same to all.

    • @buckaroundandfindout
      @buckaroundandfindout 2 роки тому

      @@MikeHoltNEC wow you really replied. You are awesome and God is great.

  • @belindasiason7357
    @belindasiason7357 3 роки тому

    God bless you mike

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      Thank you and the same to you and your family.

  • @Roberto-cg2gr
    @Roberto-cg2gr 22 дні тому

    Interview experts in I-GARD to discuss all system grounding comprehensively

    • @MikeHoltNEC
      @MikeHoltNEC  22 дні тому

      I taught for Grounding and Bonding for I-Gard for many years.. Great group of engineers. Please email me your contact information, I would like to visit with you on some of your comments. Mike@MikeHolt.com.

  • @BossManGlizzy
    @BossManGlizzy 3 роки тому

    I need to card out any tips to begin studying so i can pass for the first time? I have not began studying

    • @JohnQPublic345
      @JohnQPublic345 3 роки тому

      Star reading through the NEC page by page

    • @BossManGlizzy
      @BossManGlizzy 3 роки тому

      Bill Lumburgh will that actually help

    • @JohnQPublic345
      @JohnQPublic345 3 роки тому

      I'm old school. When we wanted to learn, we worked for low wage or free....and at same time hit the books hard. Today, everyone thinks they can do anything by watching a handful of youtube videos

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      Call my office 352.360.2620 and get the proper training program.

  • @undaya
    @undaya 2 роки тому

    The conduit is the ssbj

  • @makecashnow6714
    @makecashnow6714 3 роки тому

    I am Michael holt too a master Electrician people mistake me for you but I am not in Florida lol

    • @MikeHoltNEC
      @MikeHoltNEC  3 роки тому

      I’m not sure if that is good or bad. God Bless you brother.

  • @8yerbrain
    @8yerbrain 3 роки тому

    Thank you.

  • @gilbertraydalida7551
    @gilbertraydalida7551 Рік тому

    the best :)

  • @makecashnow6714
    @makecashnow6714 3 роки тому +1

    Hi mike

  • @nlee5034
    @nlee5034 Рік тому

    Ugh!! They (powers that be) REALLY need to think about what words to use, before using them…
    Trying to explain “Grounded v Grounding”, and then an “ungrounded system”, makes me give a “parent-like” answer, to their question:
    “How is an ungrounded system, one with no ground… when the Grounded wire, is the neutral?”
    Mr- “IDK… it’s just how it is. “

    • @stillthakoolest
      @stillthakoolest 5 місяців тому

      An ungrounded system does NOT have a grounded or neutral conductor

  • @murraywendman8222
    @murraywendman8222 3 роки тому +1

    Thanks Mike