Reset Code 2 on ClimateMaster

Поділитися
Вставка
  • Опубліковано 14 жов 2024
  • Code 2 or High Pressure Condition

КОМЕНТАРІ • 10

  • @renecuevas4128
    @renecuevas4128  5 років тому +2

    This is How to Reset Code 2 or High Head Press. On Climate Master Water Cooled Heat Pump, Need to Id the Fault on the Board by Shorting the Test Pins as Shown.After id procceed to Reset thru Red Transf. Wire.

  • @renecuevas4128
    @renecuevas4128  5 років тому +2

    For my Colleagues on the Trade this Green light Board will Flash to indicate a problem.Normally only Fan will Run but no Comp. After 3 Re Try to Start System will go on Lock Out till is Reset . No water Flow or Obstruction is the Main Reason Questions?

    • @renecuevas4128
      @renecuevas4128  5 років тому +2

      3 Easy ways to make run are....1 Backflush. 2 Check Water Flow or do as 3 Acid Flush most times Back Flush its all is need it and off course Reset AC after. Questions?

    • @renecuevas4128
      @renecuevas4128  4 роки тому +2

      Code 2 on board means High Press. Cond. Due to water flow Restriccion or no water at bldg. Check water flow GPM with Bldg Eng. And flush lines. Then Reset A C. Normal HP switch open at 400 for R22 or 600 for 410 A .

    • @bsc3377
      @bsc3377 3 роки тому +1

      Thank you for sharing you knowledge about this system. I typically get code 6 with one of my systems. It is the backflow, which needs to be cleaned every so often. Do you know the procedure for lockout code 4?

    • @renecuevas4128
      @renecuevas4128  3 роки тому +2

      @@bsc3377 if it s a Climate master code 4 here in our Geothermal is FP 1 or FP 2 wich means Freeze Protection 1 and 2 if water is too cold due to water temp or if Not enough Air flow will make lines way too cold and Activate the Freeze Sensors one is gray wire and one is Purple.Also you can Cut the jumper I think W 2 or W3 on the board for Lower Freeze Prot. Temp.

    • @bsc3377
      @bsc3377 3 роки тому

      @@renecuevas4128 thank you so much Rene.

  • @renecuevas4128
    @renecuevas4128  5 років тому +1

    Once Fault is ID repair or Reset. Most times is a Bldg Issue , if Water GPM is fine Reset it, and A.C should be fine.

  • @renecuevas4128
    @renecuevas4128  4 роки тому +1

    I have code 2 today again. Ha.....😎

    • @renecuevas4128
      @renecuevas4128  3 роки тому +1

      In most of our Bldgs . When there is no Enough water or water flow.Even water enter at higher than Normal Temperature will produce a Code 2. Water Temperature of 85 is normal temp the lower the better.But over 115 Not good at all