КОМЕНТАРІ • 8

  • @IsakAmunkete
    @IsakAmunkete 2 роки тому

    Easy and Well explained. Thank you. But, whenever i calibrate a SAMSON 3725 Positioner that has a solenoid valve between Positioner and Actuator, I get "ERR" on the display after calibration is done. HELP

  • @priambodoajisupriyadi9421
    @priambodoajisupriyadi9421 2 роки тому

    hello, thank you for explained this calibration. i have a question. if after P15 INIT calibration done and then the persentation do not show 0.0 % how to solve this problem.?

  • @romaintiprez5905
    @romaintiprez5905 Рік тому

    Vous avez sauvé la boîte merci

  • @gildelrosario7710
    @gildelrosario7710 3 роки тому

    How to change the valve position from normally open to nornaly close?

  • @marlonconsignado5589
    @marlonconsignado5589 Рік тому

    after doing the procedure after initializing an error occurred

    • @marlonconsignado5589
      @marlonconsignado5589 Рік тому

      done.. i've check the position of the pin to the actuator must be in correct position

    • @marlonconsignado5589
      @marlonconsignado5589 Рік тому

      also if error occurs try to disconnect the supply and restart again the process