Hello, do I need to call FB1 (Main_Safety_RTG1) into OB1?
No needs, the safety manager will assign the FB1 to be automatically called. You can find it from the safety manager.
Hello sir, I keep getting the error from the CU, asking me to do the acceptance test. I do not see you do it in this video. How do you ack the error?
You could press ESTOP and a safety active and off, then cycle power the drive
@@electricalautomation Works like a charm! Thanks Master.
@@ken0203huang Good Luck! Thanks!
Hi admin i would like to ask some any question are the safe ty function can i use pLC S7-1517T weahter or not ?
Not quite sure your question, what do you mean about the ty function?
@@electricalautomation I m used S7-1500T and Sinamics CU320 2PNI need control stop Drive when push emer switch but the example video used PLC 1500F
@@spk7054 It will be great using 'F' safety build-in PLC. For your case, you can use safety relay to play the safety control role.
@@electricalautomation thank you very much
@@electricalautomation I m just don’t want disconnect power infeed line module oftenly
I thank you for your afford. You explain really very good and clear.
Thanks a lot!
Good
Thanks
Very nice...
Welcome!
Very nice sir.
Thanks for watching!
Hello, do I need to call FB1 (Main_Safety_RTG1) into OB1?
No needs, the safety manager will assign the FB1 to be automatically called. You can find it from the safety manager.
Hello sir, I keep getting the error from the CU, asking me to do the acceptance test. I do not see you do it in this video. How do you ack the error?
You could press ESTOP and a safety active and off, then cycle power the drive
@@electricalautomation Works like a charm! Thanks Master.
@@ken0203huang Good Luck! Thanks!
Hi admin i would like to ask some any question are the safe ty function can i use pLC S7-1517T weahter or not ?
Not quite sure your question, what do you mean about the ty function?
@@electricalautomation I m used S7-1500T and Sinamics CU320 2PN
I need control stop Drive when push emer switch but the example video used PLC 1500F
@@spk7054 It will be great using 'F' safety build-in PLC. For your case, you can use safety relay to play the safety control role.
@@electricalautomation thank you very much
@@electricalautomation I m just don’t want disconnect power infeed line module oftenly