  • 02 Digital Input / Output Parameter  This parameter can be set during operation.
    2-wire / 3-wire Operation Control
    Factory Setting: 1
    Settings
    0: No function
    1: 2-wire mode 1, power on for operation control
    (M1: FWD / STOP, M2: REV / STOP)
    2: 2-wire mode 2, power on for operation control
    (M1: RUN / STOP, M2: REV / FWD)
    3: 3-wire, power on for operation control
    (M1: RUN, M2: REV / FWD, M3: STOP)
    4: 2-wire mode 1, fast start up
    (M1: FWD / STOP, M2: REV / STOP)
    5: 2-wire mode 2, fast start up
    (M1: RUN / STOP, M2: REV / FWD)
    6: 3-wire,fast start up
    (M1: RUN, M2: REV / FWD, M3: STOP)
    IMPORTANT
    1. In fast start up function, terminal output will keep in ready status, drive will
    response to the command immediately.
    2. When using fast start up function, the output terminal will have higher
    voltage potentially.
     In Quick Start function, the output will remain ready for operation. The drive will respond to start
    command immediately.
     When using Quick Start function, there will be greater potential voltage on the output terminals.
     This parameter is for setting the configuration of external drive operation control, plus Quick Start
    function, there are six different control modes: