  • @MMAli-nj8xl
    @MMAli-nj8xl 9 місяців тому +1

    how much distance should be maintained between check valve and 90 deg. elbow in sensing line? is there any requirement for this

    • @TanweerAhmed
      @TanweerAhmed  9 місяців тому

      Minimum distance should not less than 5 feet from check valve to check valve of sensing line is given in NFPA 20 but maximum limit is not provided therefore follow maximum distance as per site conditions.

  • @MirBaqirAliSethar
    @MirBaqirAliSethar 2 роки тому +1

    Very good and informative

  • @abbassetharofficial9169
    @abbassetharofficial9169 2 роки тому +1

    Informative 👍👍

  • @sunilbhatt4490
    @sunilbhatt4490 2 роки тому +1

    Bhut achi class sir🇮🇳🇮🇳

  • @jagsingh8324
    @jagsingh8324 Рік тому +1

    Tanweer, always like your video. Please make videos on NFPA 25.

  • @vasimwadkar7834
    @vasimwadkar7834 Рік тому +1

    Bhai mujhe booster pump ka suction header aur discharge header change karna hai.. to mujhe pressure vessel ka line kholne se pehle kya procedure follow karna chahiye

    • @TanweerAhmed
      @TanweerAhmed  Рік тому

      Follow equipment manufacturer guidlines

  • @thefirefighter8417
    @thefirefighter8417 Рік тому +1

    Hi.. i have doubt..
    Why there is two check valves in sensing line .. for dampening purpose one check valve is enough , right?

  • @abdulmajeeth3135
    @abdulmajeeth3135 3 роки тому +2

    Thanks for sharing and can you explain how to testing for fm200 and testing for fire pump?

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      InshaAllah I will

    • @chetanmhatre8780
      @chetanmhatre8780 3 роки тому +1

      Hi sir,
      How to zone high rise building to use multi stage pump?

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      Floor zones and height zones are different

  • @aliraza-to5pf
    @aliraza-to5pf 2 роки тому +1

    Both NRVs should be in direction from panel to pump discharge line or only one near to panel?

  • @riannjamesvisto9471
    @riannjamesvisto9471 Рік тому +1

    Hi. Is this applicable if the system has an Alarm Check Valve?

  • @sunilraju7710
    @sunilraju7710 2 роки тому +1

    Engr Tanver Pl explain valves with zoomed schematic drg

  • @atif-aftab1atif330
    @atif-aftab1atif330 2 роки тому

    Electric pump diesel pump both I'm talking.. band kaise hota hai automatic ya manually bnd krna parta hai.

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому

      Electric fire pump on & off automatically. Diesel fire pump on auto and off manually

  • @aliraza-to5pf
    @aliraza-to5pf 2 роки тому +1

    Can we use brass pipe for sensing line?

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому

      As per NFPA requirement is copper tubes and stainless steel tubes. You are following standard requirements or not, now it's up to you.

  • @atif-aftab1atif330
    @atif-aftab1atif330 2 роки тому

    Sir deisel pump start to automatically hota hai... Sir isko off manually kiya jata hh ya off bhi automatic hota hai please answer ...

  • @TheMentorFESH
    @TheMentorFESH 2 роки тому

    On an external Fire Hydrant line, is there any minimum requirement to put pressure gauges? Like any specific distance, or on each fire hydrnt?

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому +1

      Pressure gauges shall be installed only in fire pump room. During testing of fire hydrants, pressure gauge arrangements will be arranged.

  • @Zeekay80970
    @Zeekay80970 2 роки тому

    Aoa,
    Hope you are doing well and fine.
    Sir plz confirm that Pressure sensing line can be connected with horizontal split case pumps only as it comes with seperate control panels like for jockey we have separate control panel for electrical pump we have separate control panel like wise for standby pump.
    What about end suction pumps on which single control panel provided with pump set EDJ. ?

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому +1

      Kindly watch video, all detail is explained. Sensing line provide separate for each pump

    • @Zeekay80970
      @Zeekay80970 2 роки тому

      Ok sir thanks

  • @sunilraju7710
    @sunilraju7710 2 роки тому +1

    Engr Tanver Pl show drg in the full screen

  • @satishindia5357
    @satishindia5357 4 місяці тому

    In what case pressure sensing line is not required?

    • @TanweerAhmed
      @TanweerAhmed  4 місяці тому +1

      When fire fighting system is not installed 😄

  • @dilshadkhan8990
    @dilshadkhan8990 2 роки тому +1

    I have 1000gpm electrical and Diesel pump but running time 400gpm getting not going above

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому

      How did you know that flow is 400gpm and not flowing more?

    • @dilshadkhan8990
      @dilshadkhan8990 2 роки тому +1

      @@TanweerAhmed showing the gpm meter

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому

      It will be physically checked either problem in pump, flow meter, installed pipes or somewhere else

  • @pinoyrakista
    @pinoyrakista Рік тому +1

    Pls provide English subtitles 😊

  • @niazafridi3651
    @niazafridi3651 4 місяці тому +1

    تنویر صاحب اسلام علیکم
    عرض یہ ہے کہ آپ نے یہ بتایا کہ دو چک والو لگانے ہیں جن کے درمیان پانچ فٹ کا فیصلہ ھو اور ایک میں حول بتایا جو کہ ڈھائ ملی ھوگا اور دوسرا چک والو بھی لگا نا ہیں جو پمپ کی طرف ھوگا آ یا اس کو بھی الٹا لگانا ہیں یا سیدھا اگر سیدھا لگانا ہیں تو پھر تو اس میں حال کرنے کی ضرورت نہیں۔ اور اگر اس کو بھی الٹا لگانا ہیں تو پھر اس میں بھی حول کرنا پڑیگا۔ آپ اس کی وضاحت فرمائیں پلیز۔ اور دوسری بات۔ جو چک والو ہیں اسکا جو ڈسک ھوتا ہیں ٹھیک اس کے درمیان میں سونگ کا نٹ لگا ھو تا ہیں۔ تو پھر حول کیسے کیا جائے۔ میں آپکا سبسکرائبر ھو انتظار کروں گا شکریہ

    • @TanweerAhmed
      @TanweerAhmed  4 місяці тому +1

      وعلیکم سلام، آپ کو ڈرائنگ کو دیکھیں جو این ایف پی اے 13 میں دی گئی ہے، فر آپ کے بہت سے سوالوں کے جواب مل جائیں گے۔ اور ڈسک میں سوراخ کرنا ہوتا ہے جو چیک وال میں لگی ہوتی ہے۔ مزید اور ویڈیوز اور ڈرائنگ کو اسٹڈی کریں جیسے آپ کے سمجھنے میں آسانی ہو ۔

  • @TheMentorFESH
    @TheMentorFESH 2 роки тому

    Are you CFPS ?

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому +1

      No

    • @TheMentorFESH
      @TheMentorFESH 2 роки тому +1

      @@TanweerAhmed You must try it. You have a very good knowledge.

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому +1

      What is the requirement?

    • @TheMentorFESH
      @TheMentorFESH 2 роки тому +1

      @@TanweerAhmed Ye bhi sahi he. Good, if we have some certificates as a Consultant

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому +1

      👍