Where PRV is required as per Pressure in Firefighting System? |Q&A| in Urdu/Hindi

Поділитися
Вставка
  • Опубліковано 4 жов 2024
  • This is a Basic Engineering (Q&A) video about "Where Pressure Reducing Valve (PRV) is required as per Pressure in Firefighting System?" in Urdu/Hindi language. Here I have explained your question's answer about pressure valves of fire fighting system. It is basic learning information about the firefighting or water supply system. It is also important for HVAC/MEP technical staff. Here sharing my experience and knowledge that will be helpful for Engineers and Technical staff about this topic.
    I have explained in detail, those are:
    1. Fire Sprinkler
    2. Fire Hose Station
    3. Fire Hose Reel
    4. Hose Connection
    5. Pressure Reducing valve
    6. Pressure Restricting valve
    7. NFPA-13
    8. NFPA-14
    9. Fire Pump
    10. Fire Fighting System
    Related videos for your watching:
    1. NFPA-14 Pipe Schedule Method for Standpipe
    Video's link: • NFPA 14 Pipe Schedule ...
    2. NFPA-14 Flow Rate Requirements for Standpipe & Hose System
    Video's link: • NFPA 14 Flow Rate Requ...
    3. NFPA-14 Pressure Design Requirements of Standpipe & Hose System
    Video's link: • NFPA-14 Pressure Desig...
    4. NFPA-14 Classes of Standpipe Systems
    Video's link: • NFPA-14 Classes of Sta...
    5. NFPA-13 Pipe Schedule Method Designing
    Video's link: • NFPA 13 Pipe Schedule ...
    6. NFPA-13 Sprinkler Heads Distribution
    Video's link: • NFPA-13 Sprinkler Head...
    7. NFPA-13 Density & Area of Sprinkler Operation
    Video's link: • NFPA 13 Density & Area...
    8. NFPA-13 Sprinklers Discharge Characteristics
    Video's link: • NFPA-13 Sprinklers Dis...
    9. Wet Riser Landing Valve System
    Video's link: • Wet Riser Landing Valv...
    10. Testing of Wet Riser Landing Valve System
    Video's link: • Testing of Wet Riser L...
    11. Fire Hose Reel System
    Video's link: • Fire Hose Reel System ...
    12. Testing of Fire Hose Reel System
    Video's link: • Testing of Fire Hose R...
    13. Converting Pump Head to Pressure or Vise Versa
    Video's link: • Converting Pump Head t...
    14. Difference Between Pressure Reducing & Pressure Restricting Valve
    Video's link: • Difference Between Pre...
    15. Difference Between Pressure Relief & Pressure Safety Valve
    Video's link: • Difference Between Pre...
    16. Combined Firefighting System Water Demand
    Video's link: • Combination Standpipe ...
    17. Types of fire sprinkler system of fire suppression systems
    Video's link: • Types of fire sprinkle...
    18. Dry Pipe Fire Sprinkler System
    Video's link: • Dry Pipe Fire Sprinkle...
    19. Preaction Sprinkler System NFPA13
    Video's link: • Preaction Sprinkler Sy...
    20. Single Interlock Preaction Sprinkler System
    Video's link: • Single Interlock Preac...
    21. Double Interlock Preaction Sprinkler System
    Video's link: • Double Interlock Preac...
    22. Main Components of Fire Fighting Pump Room Part-1
    Link: • Main Components of Fir...
    23. Main Components of Fire Fighting Pump Room Part-2
    Link: • Main Components of Fir...
    24. Main Components of Fire Sprinkler System Part-1[Except Pump Room]
    Link: • Main Components of Fir...
    25. Main Components of Fire Sprinkler System Part-2 [Except Pump Room]
    Link: • Main Components of Fir...
    #TanweerAhmed #firefighting #PRV #prv #sprinkler #pressure #nfpa
    = YOU CAN FOLLOW ME ON SOCIAL MEDIA =
    WEBSITE: engineertanwee...
    FACEBOOK: web.facebook.c...
    INSTAGRAM: / tanweersethar
    LINKEDIN: / tanweer-ahmed-00142631
    UA-cam: / tanweerahmed
    TIKTOK: vm.tiktok.com/...
    TELEGRAM GROUP: t.me/hvacmepenggg

КОМЕНТАРІ • 130

  • @safesohar3807
    @safesohar3807 4 роки тому +2

    thank you very much i got lot of information from your class
    a i already watched your almost all video related to fire fighting

  • @AkshayPatil-pp4ix
    @AkshayPatil-pp4ix 4 роки тому +1

    awesome information sir....i mostly like your video... cause your information help me.

  • @LearnandGrowmuz
    @LearnandGrowmuz Рік тому +1

    Perfect video for freshies

  • @snehaljagtap7452
    @snehaljagtap7452 3 роки тому +1

    Great aap reference ke sath batate ho, o great hai

  • @ahmedjahanzaib1457
    @ahmedjahanzaib1457 3 роки тому +1

    Thank you so much for clearing my concepts..
    JazakAllah❤️

  • @pakistanimanitehadinsaaf.4478
    @pakistanimanitehadinsaaf.4478 6 місяців тому

    Excellent Work…

  • @sunilraj4423
    @sunilraj4423 Рік тому +1

    THANKS A LOT FOR YOUR SHARING KNOWLEDGE.

  • @neerajjangra4877
    @neerajjangra4877 2 роки тому +1

    Great sir

  • @arifkhanplumber3595
    @arifkhanplumber3595 3 роки тому +1

    Thanks for giving fire fighting information

  • @rameezkhan7697
    @rameezkhan7697 Рік тому +1

    Great 👍 thank

  • @babugandhibose6663
    @babugandhibose6663 Рік тому +1

    Very useful video thank you sir 🙏

  • @amtechhse167
    @amtechhse167 4 роки тому +1

    very well organized video

  • @acces2894
    @acces2894 2 роки тому +1

    Well explained. Thanks

  • @elabala4538
    @elabala4538 4 роки тому +1

    Good explanation sir 👍👍👍

  • @imranrkms6861
    @imranrkms6861 4 роки тому +2

    It's a good explanation for designers Tanveer sab i appreciate.

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      Thank you

    • @amtechhse167
      @amtechhse167 4 роки тому +1

      😍

    • @rehanzahid7591
      @rehanzahid7591 3 роки тому +1

      @@TanweerAhmed pressure in main riser pipe line after PRV would be 12.1 bar I mean to say if pressure increases in day time if the pressure in riser pipe line before prv may be 15 bar so once pressure comes to the springer orifice after pvr what would be pressure 12.1 bar asper NFPA13 & once sprinkler brust the water showers as the same pressure of springer like max 1 to 3 bar correct ??

    • @rehanzahid7591
      @rehanzahid7591 3 роки тому +1

      You have very good knowledge about Fire system keep it up thanks for giving me nice info - from 🇮🇳 india

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      If sprinkler burst then pressure to be reduced and then fire pump will run automatically to maintain set pressure of PRV.

  • @anishbansal6678
    @anishbansal6678 3 роки тому +1

    Good guidelines

  • @jitendratalole9925
    @jitendratalole9925 Рік тому +1

    Sir Ji please make separate video on Press Reducing Valve , Make types of PRV valves Design calculation....

  • @zakirkhan184
    @zakirkhan184 4 роки тому +2

    So nice and good information sir . Please explain how we calculate pump size ?

  • @mohammedhussain6103
    @mohammedhussain6103 4 роки тому +1

    Bht khoob osm.
    Sir please make vedios on hydrants system for high rise building as per NFPA.

  • @TariqKhan-uk2xw
    @TariqKhan-uk2xw 3 роки тому +1

    Good

  • @niraj28june
    @niraj28june 4 роки тому +3

    Dear Sir, greetings... Thanks for sparing your time and sharing the valuable knowledge. Further, kindly elaborate that since min pressure required at sprinkler head is 15 psi in light hazard, do we not have to install prv at every floor level in sprinkler main branch to maintain 15 psi at last sprinkler of every floor. You said that prv is required if pressure is more than 175 psi which sprinkler cannot handle. so prv is not required upto 175 psi, but keeping such a high pressure will give very high discharge from sprinkler as per Q=K*P^(1/2). This will empty the tank very quickly and not last for required duration. So do we require prv at evry floor in sprinkler branch line?? I hope i am able to explain my query properly. Pls clear my doubt on the same. Thanks in advance & god bless u for your service..

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому +1

      1st point: Sprinkler orifice or hole is small therefore flow of water to be 15psi or small up/down pressure as per K-factor.
      2nd point: Sprinkler design pressure means max pressure, if water pressure increases then sprinkler burst or damaged automatically. Therefore 150 or 175 psi is max design pressure limit.

    • @Zubair_Engineer786
      @Zubair_Engineer786 2 роки тому +1

      Question which i understand from above person if there is 100 psi pressure in pipe line .is we required to install PRV or not? If not then why?

  • @quaziab
    @quaziab 2 роки тому

    Thanks a lot sir , greatly explained

  • @sirqadeeracademy3893
    @sirqadeeracademy3893 4 роки тому +1

    Nice Tanveer brother.

  • @irfanraza2223
    @irfanraza2223 4 місяці тому +1

    Assalamualaikum ❤️ sir pump room pe ek video banaye

    • @TanweerAhmed
      @TanweerAhmed  4 місяці тому

      W.Salam,
      Already video available

  • @moqaddasazam1
    @moqaddasazam1 Рік тому +1

    Assalam alaikum Sir, please make video for fire pump start and stop pressure.

  • @uzmanawaz7317
    @uzmanawaz7317 4 роки тому +1

    Go ahead

  • @mepexperttech6209
    @mepexperttech6209 4 роки тому +1

    Excelent Sir
    Can u prepare a vedieo on FM 200 system design, installation and operation.
    How it will integrate with BMS and Fire Alram System.

  • @waqarahmed4593
    @waqarahmed4593 4 роки тому +1

    AOA sir ap ne Class 1 ka btaya k pressure 12 bar se zyada nhi hona chiye aur class 2 main 6.9 bar se zyada nhi hona chiye agar pressure range main hai to PRV ke zarorat nhi hai iss hisab ae class 3 main to hume definitely prv ke zarorat hai. Am I right?

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      Yes right, for Hose reel /Hose rack need PRV

  • @sumitbhattacharyya9677
    @sumitbhattacharyya9677 4 роки тому +3

    Could you please make a video on Fire Pump selection? What GPM pump should be selected for which system? Thsnks in advance. God Bless.

  • @sameeraryan8327
    @sameeraryan8327 4 роки тому +1

    Nycs sir ji

  • @Justlikethat2030
    @Justlikethat2030 3 роки тому +1

    Tanweer sir. Greetings. could you please make a video on water mist system designing

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому +1

      Thanks, yes I will upload video on mist system but it will take time

    • @Justlikethat2030
      @Justlikethat2030 3 роки тому +1

      @@TanweerAhmed I am.from.India sir. U are my teacher . Love the way you explain concepts .

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      Thanks

  • @amjedhussaini3823
    @amjedhussaini3823 4 роки тому +1

    Assalamualikum sir, aapke vidoes ke slide bhi agar miljate to bahut accha hota tha notes.

  • @ak-lr5jc
    @ak-lr5jc 10 місяців тому +1

    Assalam o Allium...dob need prv for high rise plumbing system as well? Also how much pressure is to b kept for farthest away point from the plumbing line?

    • @TanweerAhmed
      @TanweerAhmed  9 місяців тому

      W.Salam, plumbing is different

  • @hvacmepwork.9262
    @hvacmepwork.9262 4 роки тому +2

    Hii. ...
    Could you please tell me what's minimum height between celling & Roof slab for installation ?

    • @hvacmepwork.9262
      @hvacmepwork.9262 4 роки тому +1

      Means how much is enough? For properly installation.

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      "NFPA-13 Sprinkler distribution" refere this my video for this

  • @AbidHussain-hk6hx
    @AbidHussain-hk6hx 4 роки тому +2

    Sir, for a Complete city hydrant network project, what will be the pump capacity? Hydrant network may be of 30 km approx.
    As i understand it should be 500 gpm considering 2 hydrant in operation at a time. Please suggest.

  • @hhtradingplchaimanotmekone7581

    Is there an english version of your successive trainings ?

  • @tagarsengupta4409
    @tagarsengupta4409 3 роки тому +1

    Sir, I am facing one problem,
    in our fire fighting system main line prv pressure suddenly come in zero when fire fighting system start on operation
    What is the problem

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      Where are you inspection this pressure? When system start?

  • @shadiqueamin2823
    @shadiqueamin2823 2 роки тому +1

    Plz make a video ul listed non UL listed and FM approval

  • @mrj8012
    @mrj8012 4 роки тому +1

    AoA sir hope u fine
    Kum videos bana Rahay hain ajj kal....
    Kindly confirm PRV stand pipe k sath weld hoTA HY yan flanged PRV hota HY aur pipe k dosray end par flange weld hoo gi.

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому +1

      Flange weld with pipe as per built-in prv flange size

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому +1

      W.salam, you are right, now a days, I am busy with other works.

    • @mrj8012
      @mrj8012 4 роки тому +1

      Thanks , hope u will do something in BQ estimation Of MEP

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      insha'Allah

  • @snehaljagtap7452
    @snehaljagtap7452 3 роки тому +1

    Plz sir fire fighting pump capacity kaise decide kare o batao na

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      I am working and learning about this. Will upload video, Insha'Allah

  • @wasimahmad4017
    @wasimahmad4017 4 роки тому +1

    could you please make a video on fire fighting pump and what should be must cut off and cut in pressure of all fire fighting pump!

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому +1

      Kindly watch my video "Main components of firefighting pump Room" this detail is given

    • @wasimahmad4017
      @wasimahmad4017 4 роки тому +1

      @@TanweerAhmedvery well explain in part-01,02 & thank you.

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      Welcome

  • @shashankparadkar4691
    @shashankparadkar4691 Рік тому +1

    Sir hamre yha pressure kabhi badh rha hai kabhi kam hora hai ky reason hoga

    • @TanweerAhmed
      @TanweerAhmed  Рік тому

      Check your pressure transducers and its sensing pipelines

  • @govindsolanki2213
    @govindsolanki2213 4 роки тому +1

    What should be the pressure at ground floor pump for a single story warehouse (high class category)
    Below 15 m , wet sprinkler system please?

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      As per standard requirements min to max which is explained in video

    • @govindsolanki2213
      @govindsolanki2213 4 роки тому +1

      Thanks!!👍👍👍👍👍👍👍👍👍

  • @snehaljagtap7452
    @snehaljagtap7452 3 роки тому +1

    Koi bhi ek example leke batao, head kaise calculate kare

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      I am working and also learning about it. Will upload soon video, Insha'Allah

  • @Shaaz_Line
    @Shaaz_Line 2 роки тому

    Dear Engr
    What is the maximum residual pressure for Class 1 hose connections? What i understood is for Max Static pressure of 12.1Bar requires PRV but is there anywhere telling about using prv to restrict maximum residual pressure for 21/2 hose connections.

    • @TanweerAhmed
      @TanweerAhmed  2 роки тому

      Watch my standpipe pressure requirements video

  • @musiqisever1
    @musiqisever1 4 роки тому +1

    How much pressure must be in the 50 hose to get 2.5 liters of water per second?

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      Check yourself and inform me

    • @musiqisever1
      @musiqisever1 4 роки тому

      Why?

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      100 to 175 psi pressure for 65mm Dia hose pipe connection recommended by NFPA-14

  • @mrj8012
    @mrj8012 4 роки тому +1

    Fire Fight aur Hvac Sy niklo Bhi Jan...MEP main aur buhat kuch hy valves par clip banatay Rahay tu hoo gya kam.

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому

      What do you want to watch video about ?

    • @mrj8012
      @mrj8012 4 роки тому +1

      App MEP Engineer ho App ko tu kudh hi pata hy MEP yani Fire Alarm , CCTV ,tv tel wiring ,Bill Of quantity estimation electric , water supply motors , Generators , Lift passenger cargo installation ,Hvac load calculation , BASIC MEP FORMULAS,
      PEHLAY BHI APP KO YEHI BATT BATAII THI JANAB.
      GOOD WORK KEEP IT UP
      BEST REGARDS
      THANKS

    • @TanweerAhmed
      @TanweerAhmed  4 роки тому +1

      As per demand I make videos accordingly. Thanks for reminder, now will start lift wort videos soon

    • @mrj8012
      @mrj8012 4 роки тому +2

      Keep IT UP sir

  • @chandrakant128
    @chandrakant128 2 роки тому +1

    Is its mandatory??

  • @abhinavkumarsingh6792
    @abhinavkumarsingh6792 3 роки тому +1

    pipenet please sir

    • @TanweerAhmed
      @TanweerAhmed  3 роки тому

      I have not used this software. I don't know about it.

  • @mohammeduzzolmiah8374
    @mohammeduzzolmiah8374 3 роки тому +1

    Hi

  • @nfpafiresafetydesignsoluti8525
    @nfpafiresafetydesignsoluti8525 4 роки тому +1

    THANKS A LOT FOR YOUR SHARING KNOWLEDGE.