Walkthrough of VFD wiring for TR150
I go through wiring diagram of vfd panel
Переглядів: 571

Відео

Trane RTAC ball valve crack
Переглядів 644 місяці тому
Trane RTAC ball valve crack
Turtles at Kitty Hawk North Carolina
Переглядів 297 місяців тому
summer 2023
Finding bad lug connections on Trane AHU for startup
Переглядів 108Рік тому
I find bad terminal lug connections on VFD section of a Trane AHU. #hvac #commercialhvac #hvaccontractor
Repairs on Trane Commercial AHU
Переглядів 144Рік тому
Piping in new filter driers for both circuits. #hvacservice #hvaclife #commercialhvac
PM on Carrier 30HXA Screw Chiller
Переглядів 1,8 тис.Рік тому
Given call to complete PM on Carrier screw chiller, Checked system for alarms, checked and tightened all electrical connections, checked compressor terminals, checked solenoids, leak checked all refrigerant lines and connections, checked refrigerant monitor, checked remote condenser, washed coils, checked fan motors, checked condenser fan vfds, checked chilled water pumps. #hvaclife #commercial...
Recovering R410A for TXV replacement on Trane voyager
Переглядів 4382 роки тому
I ended up only recovering like 16ish lbs of gas, bubble tested joints and it held 375 psi for over 30 mins and I left nitrogen charge overnight to check it tomorrow .
Changing condenser fan motors on Trane RTAA
Переглядів 3,6 тис.2 роки тому
Continuing a job where we are changing 4 screw compressors, EEVs, all fan motors and blades, and new control wiring. #chiller #hvaclife #hvac #trane #commercialhvac
Annuals on Daikin Chillers
Переглядів 1,1 тис.2 роки тому
Draining chiller before punching tubes #hvac #chiller
Easy friday as a commercial hvac apprentice
Переглядів 2 тис.2 роки тому
Boring but mellow day punching tubes on McQuay Chiller, afterwards I reinstalled the head and filled. #hvac #hvaclife #hvacmaintenance #commercialhvac #chiller
MRI Chiller coil cleaning
Переглядів 3 тис.2 роки тому
cleaning coils on MRI Chiller #hvac #hvaclife #commercialhvac
Cooling tower cleaning
Переглядів 2552 роки тому
Cooling tower cleaning
Commercial/Industrial HVAC service apprentice, Carrier 19XR Centrifugal Chiller punching tubes
Переглядів 1 тис.2 роки тому
I recently switched into the commercial space, I am punching tubes on this Carrier 19XR chiller. I am exited to learn and grow in this field. #hvac #refrigeration #hvaclife
Veto Pro Pac MB2, my residential HVAC service bag loadout
Переглядів 19 тис.2 роки тому
Veto Pro Pac MB2, my residential HVAC service bag loadout
no heat emergency service call, Fujitsu unit with shorted control board
Переглядів 1622 роки тому
no heat emergency service call, Fujitsu unit with shorted control board
Replaced Triangle Tube Prestige Solo 110 combustion blower
Переглядів 1,3 тис.2 роки тому
Replaced Triangle Tube Prestige Solo 110 combustion blower
Rooftop tool hunting in Washington DC
Переглядів 6162 роки тому
Rooftop tool hunting in Washington DC
Replaced honeywell zone valve power head, expansion tank and relief valve on Burnham boiler
Переглядів 472 роки тому
Replaced honeywell zone valve power head, expansion tank and relief valve on Burnham boiler
How to diagnose combustion blower on Triangle Tube Prestige Solo 110
Переглядів 2,2 тис.2 роки тому
How to diagnose combustion blower on Triangle Tube Prestige Solo 110
Found bad zone valve motor, replaced and purged zone
Переглядів 402 роки тому
Found bad zone valve motor, replaced and purged zone
I replaced expansion tank and purged all zones for big house
Переглядів 262 роки тому
I replaced expansion tank and purged all zones for big house
cap and remove abandoned boiler supply and return
Переглядів 172 роки тому
cap and remove abandoned boiler supply and return
circulating pump came out of thermal overload
Переглядів 462 роки тому
circulating pump came out of thermal overload
Interesting hydronic piping done by contractor, wow
Переглядів 162 роки тому
Interesting hydronic piping done by contractor, wow
NTI boiler, domestic water relief valve discharging 2nd opinion
Переглядів 4992 роки тому
NTI boiler, domestic water relief valve discharging 2nd opinion
2012 Bryant heat pump frozen, no heat service call
Переглядів 4 тис.2 роки тому
2012 Bryant heat pump frozen, no heat service call
Utica boiler gas valve replacement from previous video
Переглядів 2572 роки тому
Utica boiler gas valve replacement from previous video
Utica boiler with noisy gas valve
Переглядів 2,7 тис.2 роки тому
Utica boiler with noisy gas valve
checking out an old weil-mclain boiler and found water heater about to explode
Переглядів 1612 роки тому
checking out an old weil-mclain boiler and found water heater about to explode
Carrier mini split blower wheel removal and cleaning
Переглядів 31 тис.2 роки тому
Carrier mini split blower wheel removal and cleaning

КОМЕНТАРІ

  • @anns8893
    @anns8893 11 днів тому

    Why did you Not tape the most important part of video???

  • @Rippleman5974
    @Rippleman5974 Місяць тому

    It is an equalization tube for txv & Lennox is bad about supporting copper feeders & suction access tubes and this happens

  • @gatlinholland6453
    @gatlinholland6453 2 місяці тому

    awesome, working on a TR150 tomorrow 😅

    • @dmvhvactech
      @dmvhvactech 2 місяці тому

      nice man, all work out?

  • @corybrattain4157
    @corybrattain4157 2 місяці тому

    How did you pop the bushing out?

  • @VentureSocal
    @VentureSocal 3 місяці тому

    I have the exact same leak on my Lennox package unit TXV. What does it run to repair this and recharge it?

  • @cfvlabs7693
    @cfvlabs7693 3 місяці тому

    Nice - about how long does it take to replace each fan motor and/or blade?

  • @chadforehand480
    @chadforehand480 4 місяці тому

    What do if you don’t have anything on c and d would that be the thermostat?

  • @DJV94022
    @DJV94022 6 місяців тому

    Speaking of quality..people have been complaining on the new ml17xp1 how they make too much noise..and its because they cage of the condenser all that aluminum is hollow..theres nothing you can do about it itll flap no matter what..however carrier units still seam rigid because they aluminum they are using is heavier..if ford is making less quality trucks so are these aluminum condensers..copper is very soft nowadays no need for a tube bender

  • @NorCalHydro
    @NorCalHydro 7 місяців тому

    Great video, thanks for the help! Isnt it odd that manufacturers dont include these steps in the troubleshooting guides?

  • @lonetraveler5660
    @lonetraveler5660 7 місяців тому

    The shade pole under coil is broken. You can change your power supply vdc to dc. Make sure cut voltage roughly in half. Ie. 24 vac to 12 dc, etc. then try to find a minimal current which can activate the valve or introduce a resistance to reduce the current

  • @lonetraveler5660
    @lonetraveler5660 9 місяців тому

    i have the same problem. i havd very old gas furnace. i could not find the same solenoid valve. it use 24 v. three wire and standing pilot.may i just use any solenoid valve using these same spec?

  • @nycowboy2288
    @nycowboy2288 9 місяців тому

    How do you get the screw out the back of the blower?

    • @done7689
      @done7689 6 місяців тому

      long screw driver

  • @DanKrischke
    @DanKrischke 10 місяців тому

    You skipped the most important part. Thanks for nothing.

  • @SaltySullyYT
    @SaltySullyYT Рік тому

    Noise is most likely a seized or a gas valve beginning to seize and go bad?

  • @dyworking
    @dyworking Рік тому

    useless video. doesnt show what screws to remove to access the fan.

  • @juantoledo8595
    @juantoledo8595 Рік тому

    If the thermostat that comes with the system is bad can we put a regular thermostst?

  • @boywhohadatiger
    @boywhohadatiger Рік тому

    How long does your micron guage take to clear O.L and start reading microns ?

    • @dmvhvactech
      @dmvhvactech 5 місяців тому

      Depends on a few things, but if system is tight then should read within a few minutes. Old or long line set may increase that time. For residential systems I never had issues pulling with one hose on suction.

  • @EverythingHVACR
    @EverythingHVACR Рік тому

    Every FN time! I've found them cross threaded too. Great job.

    • @dmvhvactech
      @dmvhvactech Рік тому

      Have to check everything now adays. I found the other day an Ipak with bolted 150amp fuses for the supply fan in the main control cabinet. Found L2 and L3 terminal lugs were cross threaded so bad. The actual bolts weren't tight and I could spin the washers with my finger. Also found red wire nuts used inside the pecker head for 4awg wire lol. Factory must be giving it the all clear at 2pm on a Friday.

    • @EverythingHVACR
      @EverythingHVACR Рік тому

      @@dmvhvactech I had the same fuse issue 😆 kinda sad

  • @jshady4873
    @jshady4873 Рік тому

    Not a fan of the carrier mini split however I had to replace a head due to a leaking coil new layout. The blower and wheel is on a hinge and the assembly slides out. Looks like a nice feature without compromising the coil.

  • @davidspear5470
    @davidspear5470 Рік тому

    This is very helpful, thank you. What does it take to have the thermostat 'relearn' the system? A factory reset?

  • @boywhohadatiger
    @boywhohadatiger Рік тому

    Do you remove the valve core on the liquid line ?

    • @dmvhvactech
      @dmvhvactech 5 місяців тому

      I don't on this setup

  • @dr.comforthvacr8889
    @dr.comforthvacr8889 Рік тому

    GREAT WORK!!!

  • @DD-ud8oz
    @DD-ud8oz Рік тому

    How did you get to the set screw holding the fan on the right side? I can’t move the coil away enough to access.

    • @dreamintigers84
      @dreamintigers84 Рік тому

      Ever figure it out. I have the same issue. Doesnt show that 😢

    • @R3CKLESSHD
      @R3CKLESSHD 11 місяців тому

      Rotate the wheel.

  • @dawnsimental765
    @dawnsimental765 Рік тому

    I'm working with a Daikin Chiller Mn#WWVMNNSASNC having issues punching the tubes, rod size doesn't fit, however the 1/2" brush is good. I have a Goodway machine as well. What rod/hose size did you use on yours?

    • @dmvhvactech
      @dmvhvactech Рік тому

      My bad saw this late, I already punched these tubes again this year I'm pretty sure 5/8" brush for this.

  • @heavydiesel
    @heavydiesel Рік тому

    Well done spotting the damaged fan blades!

  • @FreePalestine718
    @FreePalestine718 Рік тому

    Discuss fucking retarded. She doesn’t even show you how to take it off.

  • @robwells9814
    @robwells9814 Рік тому

    Literally just came across this same exact situation BUT the entire front part of the fan separated and broke up into three giant pieces. We only have maybe 8 that I've seen of these boilers.

    • @done7689
      @done7689 6 місяців тому

      my unit has had 7 replacement blowers, plastic fan blades corrode and shatter. junk design

  • @tomyxu3977
    @tomyxu3977 Рік тому

    any screw holding the blower in the other end? I was trying to put but very hard to get it out? your video not show anything from the other end ...!:(:( I need help at this moment...! thanks

    • @R3CKLESSHD
      @R3CKLESSHD 11 місяців тому

      There is a set screw on the motor end. Rotate the wheel until you can see it. Loosen the screw, DO NOT REMOVE. Then you'll be able to pull the wheel free.

  • @TheWendyWilliamsShow
    @TheWendyWilliamsShow Рік тому

    Was it giving an 04 error code? How old was that flame sensor?

  • @almamunguia6570
    @almamunguia6570 Рік тому

    You never show how to remove de blower wheel.

  • @Detechj
    @Detechj Рік тому

    Good job 👍

  • @kountryedge
    @kountryedge Рік тому

    My house was built in 1900 and I still have the cast iron boiler and burners.

  • @lucas956jolomcu
    @lucas956jolomcu Рік тому

    Hello my mini split I’m not sure the blowing fan making nois

  • @AmericanFarmerHVAC2024
    @AmericanFarmerHVAC2024 Рік тому

    Secondary plugged tighter than hell

  • @samuelaranda4568
    @samuelaranda4568 Рік тому

    I got shocked using the field piece. On a disconnect. Then I was looking for a short in a electrical panel an and it wouldn’t find it. I took my fluke out and found the short in 5 minutes. I threw that meter off the roof.

  • @jesseruiz9257
    @jesseruiz9257 Рік тому

    What if you get call and only compressor runs and not the fan ? I replaced motor and stop same issue runs for a min and trips on high head due to no fan .

  • @dominicarjune8064
    @dominicarjune8064 2 роки тому

    Rtx 4090

  • @chriswatson2407
    @chriswatson2407 2 роки тому

    Best fan-boi channel on yt

  • @Straycurrent
    @Straycurrent 2 роки тому

    That's a whopping number of fans. Stay dry. I take it this is all done as preventive maintenance.

    • @dmvhvactech
      @dmvhvactech 2 роки тому

      This was part of a quoted job for work to essentially give old equipment new warranty since they did not go for a chiller replacement. They have 4 400ton air cooled chillers for this stadium and all from 1998. We did 4 new compressors, all original fan motors replaced, new EEVs and wiring/modules, all new pressure transducers and switches, filters,etc. One ckt had a comp burnout so that one got virgin r22, other ckt just got what we pulled out which was the factory charge. New stadium will be built at some point so this is just to help make it till then.

    • @Straycurrent
      @Straycurrent 2 роки тому

      @@dmvhvactech Sounds like just about everything got replaced except the coils and barrels. I was imagining it was some critical installation such as a hospital or industrial processing. I underestimate the importance of sports :-) Anyway, thanks for explaining which refrig -- I was curious about that too.

  • @Jleek159
    @Jleek159 2 роки тому

    You didn’t show me anything

  • @shootups3716
    @shootups3716 2 роки тому

    Heyo! Vids popped back up in Shorts. Joined 602 baby! Working for a commercial refrigeration shop in Upper Marlboro. See ya in school next year lol!

    • @dmvhvactech
      @dmvhvactech 2 роки тому

      Yo nice man thats awesome congrats brotha!! Its a big commitment but well worth it so far. Try to keep a low profile and you’ll be fine, alot of guys talk too much and that can get them in trouble. Drive safe and stay clean my advice. Never turn down any job

  • @b-2466
    @b-2466 2 роки тому

    A that's a good idea with the wire nuts in the bit pockets. Definitely gonna do that to mine.

  • @PBS-nm1uu
    @PBS-nm1uu 2 роки тому

    please do a sequence of operation. thanks

  • @izzymoney85
    @izzymoney85 2 роки тому

    Keep up the good work 👍

  • @eastcoast186
    @eastcoast186 2 роки тому

    What is the communication voltage you are looking for

    • @dmvhvactech
      @dmvhvactech 2 роки тому

      If I remember correct a good reading is anywhere from 2.5-4vdc pulsing

  • @officerkrupke4966
    @officerkrupke4966 2 роки тому

    If whoever rewired the contactor had put the safeties wire on the brown wire side instead of the wire going to t1, they would have had to stick around and find out why the fuse protecting the low voltage control blew. As it turned out, they just disabled the defrost cycle, and made their getaway. Nice catch. You had it earlier when you tested t1 and got zero volts with contactor energized. t1 is an input terminal and gets its voltage from jumper from contactor coil 24 volt side. Tells the logic that compressor is running, which starts the timing if defrost tstat is below thirty degrees. They had it hooked up to common side.

  • @rgk9495
    @rgk9495 2 роки тому

    Good explanation. Thanks.

  • @mrsean209
    @mrsean209 2 роки тому

    Wow, man...the wires on the coil, same thing happened to me not too long ago. It took me about an hour to find it. It was really sad. lol

  • @applianceman6009
    @applianceman6009 2 роки тому

    Lennox today is not the same as the Lennox of the 20th century. Their quality significantly declined in the late 2000’s, and it never was the same. Lennox used to be one of the finest brands of HVAC. Not anymore. This leaking condenser with an LG scroll= absolute garbage!!

    • @dmvhvactech
      @dmvhvactech Рік тому

      yeah lennox is trash lol, I would do Goodman all day over Lennox

    • @willmann81785
      @willmann81785 Рік тому

      ​@@dmvhvactech just had an HVAC tech come out to determine why my outdoor unit wouldn't come on. Low pressure fault. Puts nitrogen in the system you can immediately hear the leak. Outdoor TXV had a weak weld from the factory. Shoddy work by Lennox. System is less than 2 years old. Part is under warranty but labor and all that refrigerant 410A is not. So expensive repair. Lennox should be responsible for it. When it's time to replace in hopefully 10-15 years, I am not going with a Lennox. Thanks for the video. I thought TXVs were mostly indoor? Or are there 2. I am not an HVAC tech but I want to sound somewhat knowledgeable when speaking with the tech coming out on Monday.

    • @dmvhvactech
      @dmvhvactech Рік тому

      ​@@willmann81785 Sorry about your unit, typical straight ac systems have one metering device before the evaporator. A heat pump system in cooling mode works the same, has a metering device before refrigerant enters the evaporator. A heat pump running in heat mode the outdoor coil is now your evaporator absorbing heat from the outside air. Some units use a txv as that metering device, some use fixed orifice.

    • @DJV94022
      @DJV94022 6 місяців тому

      ​@@willmann81785yes in heat pumps stock from factory has 2 txvs atleast for lennox (1 indoor and 1 for outdoor) The one for outdoor is pretty much to manipulate the system In cars your car will have 1 txv When you hit that ac button thats what will give you a/c For heating ina car its a seperate mini radiator inside the cabin that tees off from radiator hoses or thermostat housing .. So in heating mode for houses The indoor unit becomes the radiator And the outside unit becomes the a/c which is funny because youre giving the cold outdoors a/c but thats where technology steps in with defrost mode (not going to explain that) but thats what makez these systems $10k

  • @mackenziegray2090
    @mackenziegray2090 2 роки тому

    was it a bad defrost board since it had a closed defrost sensor?

    • @dmvhvactech
      @dmvhvactech 2 роки тому

      honestly if I remember right I wasn't getting full 28volts on R, I found a bad wire nut at the ahu. Once I remade that connection it went right into defrost since I never went back there.