AB PLC Test Bench
AB PLC Test Bench
  • 74
  • 239 351
SLC503 & 1747-UIC
Quick video on setup and using a 1747-UIC USB to DH485/ RS232 communication adapter.
Переглядів: 983

Відео

1771-ALX & 1785-L40L testing
Переглядів 1967 місяців тому
Setup and testing of the 1771-ALX local adapter connected to the 1785-L40L processor. Showing a couple of tips and tricks for getting this going. Still lots of these in service world-wide
1771-QB Linear Positioning Module
Переглядів 26410 місяців тому
Follow up video to one I did a few years ago. Also showing what you see with a dead or damaged module. I reference using Snagit for a screen capture, but was not able to get working on my WIN7 screen. Maybe next time☺
SLC500 Analog I/O
Переглядів 793Рік тому
In this short 10 minute video, I will show ou how I setup and test the SLC500 1746-NI8 input - 1746-NO8I Current/ mA Output & 1746-NO8V Voltage output. The same steps apply to all of the SLC500 analog cards. Years ago I asked various forums about how to test these cards and never got any help. Hopefully this will help you to keep your operation running.
1784-CF64 - Memory card for PLC
Переглядів 342Рік тому
How to configure and use the 1784-CF64 memory card with the L6x RS5000 processors
1756-IF8 Calibration
Переглядів 580Рік тому
A quick video using the concepts and setup that I used before on the IF16 calibration. The IF8 that I have in hand has channel 1 with a calibration error. Was originally calibrated in 2006 - which seems to be the factory standard date.
2nd - Calibration procedure for 1756-IF16 Analog input.
Переглядів 1,8 тис.Рік тому
Video 2 of 2 on how I calibrate the AB/ Rockwell 1756-IF16 Analog input module in my shop. This shows the module with one channel that was not calibrated and how it is calibrated. There is no mystery to doing this calibration just a little bit of time and patience. A good to excellent quality power supply is a must for doing this. A high quality digital meter or Scopemeter is also needed to get...
Calibrate a 1756-IF16 Analog Input
Переглядів 1,1 тис.Рік тому
Video 1 of 2 on how I calibrate the AB/ Rockwell 1756-IF16 Analog input module in my shop. There is no mystery to doing this calibration just a little bit of time and patience. A good to excellent quality power supply is a must for doing this. A high quality digital meter or Scopemeter is also needed to get accurate results.
1756-OF8 Damage results
Переглядів 484Рік тому
Showing the testing process and results in detail of the OF8 to IF16 testing procedures. Both Voltage test and mA/ current test. In this case we have a damaged OF8 output that we are comparing to a known good OF8 in the chassis. At the end of the video we open up the module for inspection.
1771-IFE Analog Input
Переглядів 1,4 тис.Рік тому
A discussion and showing of how I test the AB 1771-IFE/C Analog input module. How to set the jumpers for various modes as you need them and a quick screenshot or 2.
How to change out broken divider plates on CLogix chassis
Переглядів 2312 роки тому
In this video I show how to change out the divider and power supply end plates on either a ControlLogix or SLC500 Chassis. I Also show that the CLogix footprint was taken directly from the SLC500 footprint.
How to assemble a CLogix chassis and modules
Переглядів 2,9 тис.2 роки тому
In this video I show how to install a power supply onto a 1756-A10 chassis and how to insert and remove modules from a chassis. This is the same procedure for any size CLogix chassi.
1756sc-IF8u - Spectrum Controls
Переглядів 3692 роки тому
Spectrum Controls - 1756sc-IF8u. 8 Channel universal Analog input for ControlLogix. Explanation and how I test this very handy analog input module. Manuals - Add on profiles and more can be downloaded free from the Spectrum site - spectrumcontrols.com/support/
1756-L81E/B T01:C61 Error Code
Переглядів 4,4 тис.2 роки тому
I have purchased 2 of these 1756-L81E/B processors in the last few months. They were purchased about 3 weeks apart. 1 from the east coast of the USA and 1 from GB. Both when powered up gave the same display. Major Fault T01:C61 Non-Recoverable - Backup Energy HW Failure. From an online discussion forum this fault is: Major Fault T01:C61 - Power-up Fault: Non-recoverable Fault with saved Diagnos...
1756-IF6I - Isolated Analog input testing
Переглядів 2,8 тис.2 роки тому
How I test the 1756-IF6I in both voltage and current / mA modes at my workbench.
1756-IF8 & 1756-OF4 Testing
Переглядів 3,2 тис.2 роки тому
1756-IF8 & 1756-OF4 Testing
1746-NT8 Thermocouple Input testing
Переглядів 1,3 тис.2 роки тому
1746-NT8 Thermocouple Input testing
AB 1492-IFM wiring arms
Переглядів 1,2 тис.2 роки тому
AB 1492-IFM wiring arms
1756-TBCH wiring arm assembly
Переглядів 1,5 тис.2 роки тому
1756-TBCH wiring arm assembly
Wiring arm for 1756-IF16 in mA mode
Переглядів 4,7 тис.2 роки тому
Wiring arm for 1756-IF16 in mA mode
1756-TBNH wiring arms
Переглядів 6382 роки тому
1756-TBNH wiring arms
1756-TBCH & 1756-TBNH wiring arms
Переглядів 1,8 тис.2 роки тому
1756-TBCH & 1756-TBNH wiring arms
1756-IF16 - Damaged Inputs
Переглядів 2,2 тис.2 роки тому
1756-IF16 - Damaged Inputs
1756-OF8 & IF16 mA testing
Переглядів 2 тис.2 роки тому
1756-OF8 & IF16 mA testing
SLC500 Analog NI4 & NO4I
Переглядів 9912 роки тому
SLC500 Analog NI4 & NO4I
1756-HSC
Переглядів 4,2 тис.2 роки тому
1756-HSC
MicroLogix 1769-OW16 Testing
Переглядів 9843 роки тому
MicroLogix 1769-OW16 Testing
MicroLogix & CompactLogix
Переглядів 9743 роки тому
MicroLogix & CompactLogix
1756-OA16 Ver 3.2 Fuse change
Переглядів 6 тис.4 роки тому
1756-OA16 Ver 3.2 Fuse change
1756-IF4XOF2F mA/ Current mode wiring
Переглядів 1,8 тис.4 роки тому
1756-IF4XOF2F mA/ Current mode wiring

КОМЕНТАРІ

  • @olalereisaiah
    @olalereisaiah 19 днів тому

    Hello there, Please can you demonstrate a connection of 1756 of4 analog output card. thanks

  • @Nicofish2023
    @Nicofish2023 Місяць тому

    Hello . Please can you give me a little training on devicenet ? Thanks

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      Hello: Devicenet is no longer supported by Rockwell or anyone else. I used it for a bit while I was working in the sawmill, but that was it. It was a system that was prone to failures and had way too many quirks. Nothing I can do for training and suggest your facility get rid of it as soon as you can.

    • @Nicofish2023
      @Nicofish2023 Місяць тому

      @ thanks. Please can you train me in plc programming?

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      @@Nicofish2023 If you have questions on how to learn to be a PLC programmer - I would strongly suggest that you check out this website www.plcs.net - Clear and concise explanations about PLC programming

  • @olajideadmola3293
    @olajideadmola3293 Місяць тому

    Thanks for all you do.

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      Hi: You are welcome - I hope my videos assist in understanding AB PLC's.

  • @benwilkinson6578
    @benwilkinson6578 Місяць тому

    I was wondering when I wire one of these up do i need to use a separate power source for the load. I see your using a 120 volt source for the light and im guessing when they say load dependent it means the 120 volt source is dependent upon the 24 volt NO relay inside the module? Just wondering if I'm understanding this correctly.

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      Hi: There are 16 tiny little relays in there and you don't really want a heavy load on them. Personally I would not put more than 1/4 to 1/2 amp load at max on any channel regardless of the voltage.

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      Hi again: YES - I would keep the processor power supply and communication power supplies separate from any field devices power. AC or DC. High swings to the incoming power supply can cause the power supply to malfunction. It can also clear the memory and fault the processor. This is exactly the same scenario that happens with the SLC500.

  • @MiguelGomez-rc7ou
    @MiguelGomez-rc7ou Місяць тому

    Hello!! I want to connect to a SLC 5/03 on the Port 0 is configurated as DF1 Full Duplex, is posible to use this cable?

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      Hello Miguel: The UIC adapter can be switched between RS232 for the serial communication port or DH485 which is the other port. Even though it looks like an ethernet port it is not. Just about any USB to serial adapter will allow you to hook up to the 9 pin RS232 port. The biggest trick is to make sure you have the correct 9 pin cable. Thne do an auto configure in Linx and it should connect.

    • @MiguelGomez-rc7ou
      @MiguelGomez-rc7ou Місяць тому

      @@abplctestbench759 Thanks for your Response! Well I try with my USB Serial Adapter and a null-modem cable and the RSLinx never connect to the PLC, and the Autoconfigure always fail. The correct cable is a female to female DB9 with Pins 2 - 3; 3 - 2; and Straight 5? Thanks Again?

    • @MiguelGomez-rc7ou
      @MiguelGomez-rc7ou Місяць тому

      @@abplctestbench759 Another Question, Sir have experience with the DTAM plus Terminals? Is possible to upload from the terminal to my PC (I Have the DPS software) this terminal have Printer port RS-232, wich cable is needed to connect to the PC? Thanks!

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      @@MiguelGomez-rc7ou Sorry to take so long - been having PC problems all last week. Good except on each end you have to jumper: 1 to 6 and then it should work. If not let me know and I will do up a video showing the connections. Once you get it working on the 1 it will work on all of the devices you need.

    • @MiguelGomez-rc7ou
      @MiguelGomez-rc7ou Місяць тому

      @@abplctestbench759 Hope all problems has been solved!! OK, Maybe week I need to return to that CPU and DTAM terminal and will probe that config. Thanks!!!!

  • @Aerobix
    @Aerobix Місяць тому

    Is there any way to get a replacement key for the config/run mode switch?

    • @abplctestbench759
      @abplctestbench759 Місяць тому

      HI: The key is the same one that is used in PLC5 processors. Simply take it to any locksmith and they can copy it for you. Nothing special about it.

    • @Aerobix
      @Aerobix Місяць тому

      @@abplctestbench759 Great thanks a lot. I still have 3 units here to refurbish :) lmk when you need hmi spare parts. I am small german repair guy Siemens/Beckhoff/AB etc

  • @eluwax
    @eluwax 2 місяці тому

    I had the same issue with L81E, A10/C chassis and PB75/B power supply. Replaced every part in the configuration and issue was not resolved. Finally changed power supply to a few years old PB72/C and the power up fault was resolved. I’m bit confused as the datasheet indicates PB75/B supports both type B and C chassis. Anyways hope this will help someone

    • @abplctestbench759
      @abplctestbench759 2 місяці тому

      Hi been away for a few weeks on the road. Rockwell has multiple issues on this setup that they are not resolving or letting people know how to resolve. The 81x Error codes that keep popping up show how far down their quality has gone.

  • @eluwax
    @eluwax 2 місяці тому

    I had the same issue with L81E, A10/C chassis and PB75/B power supply. Replaced every part in the configuration and issue was not resolved. Finally changed power supply to a few years old PB72/C and the power up fault was resolved. I’m bit confused as the datasheet indicates PB75/B supports both type B and C chassis. Anyways hope this will help someone

    • @abplctestbench759
      @abplctestbench759 2 місяці тому

      Thanks for finding this tip. Hope it helps someone else also.

  • @hakitechautomation9270
    @hakitechautomation9270 2 місяці тому

    can i use the 4 outputs of module for pulse output train

    • @abplctestbench759
      @abplctestbench759 2 місяці тому

      Hi: Been away for a couple of weeks. You should be able to by setting the trigger points in the module setup screens. Not something I have ever needed to try.

  • @dalekurita1075
    @dalekurita1075 2 місяці тому

    I would like see a proper software lesson to test communications

    • @abplctestbench759
      @abplctestbench759 2 місяці тому

      Hello Dale: I have been out and on the road for awhile. Your inquiry would be best asked at www.plcs.net/ - He has multiple training videos. My videos are the basics. Thank you

  • @ثقافةعامة-ظ7خ
    @ثقافةعامة-ظ7خ 3 місяці тому

    Hello sir. Can I get help please?

  • @ثقافةعامة-ظ7خ
    @ثقافةعامة-ظ7خ 3 місяці тому

    Hello sir. Can I contact you? Because I have a problem and I cannot solve it. Can you help me? Thank you.

  • @mouhabd5451
    @mouhabd5451 3 місяці тому

    Merci

  • @michaelastaiza6935
    @michaelastaiza6935 3 місяці тому

    Hello, I have a panel view plus 7, the bd9870 voltage regulator is burned out, it has fatal error 3a, can you explain to me what could have happened, thank you

    • @abplctestbench759
      @abplctestbench759 3 місяці тому

      Hi Michael: THE PVP7 overlays that come direct from the factory are some of the cheapest crap I have seen since in years. 3A Fatal error is when the touchscreen overlay is damaged and stuck to glass. It is a stuck button error and can be caused by any abrasion or pushing too hard on the screen. I had one the other day that I fixed that looked perfect, but still gave the error. A pin prick thru the plastic to the glass will give the error also. Burning out the power supply is a new one on me. Was this in an area of some fluid or somewhere similar?

  • @mrtrader4628
    @mrtrader4628 4 місяці тому

    I trying to get it to take but I don't see my Flex I/O in linx when I connect from the laptop to the unit. the switch has 011 on the front this was given to us from a different plant as a trainer but I not having much luck connecting. bootp is see it so can you please tell me where I'm going wrong. MAC:0000bc376f2d We also have a switch in the trainer, but I tried but ways Thanks Darren.

    • @abplctestbench759
      @abplctestbench759 4 місяці тому

      Hi: You don't say if it is a series A or B. I suspect it is a series A. Try watching my other video - ua-cam.com/video/VSc628BpRSE/v-deo.html

  • @joew4202
    @joew4202 4 місяці тому

    I fought a mass meter today on a Ctr8 that wouldn’t give any feedback on 2 channels. I swapped it with a channel that was working and the problem moved. How can i verify this channels are getting feedback

    • @abplctestbench759
      @abplctestbench759 4 місяці тому

      HI: Normally my experience if the problem moves it is the input device. Take a spare input device - disconnect the field device at the PLC and hook the spare up to the card. Then see if you have the readings from the new device. (If you don't get a reading from the new device then it is the module - replace it.) Reconnect the field device. Go to a junction box close to the field device - disconnect the field device and hook on you now known spare device. If you get the readings at that point it is a safe bet that the original field device is dead. This is the standard 'divide and conquer' technique.

    • @joew4202
      @joew4202 4 місяці тому

      @@abplctestbench759 we had a short on a machine frame and had several devices get fried. What’s strange about this one card is it has 4 devices on it and we originally lost 3/4. We replaced them now 1/3 doesn’t work. We moved that one to a another channel and it didn’t work there either.

    • @abplctestbench759
      @abplctestbench759 4 місяці тому

      @@joew4202 Hi: Still sounds like you have bad field wiring or devices to me. Without being there it is really hard to guess from my end. (You can buy me a plane ticket and I can come for a visit🤣 to see if I can help)

  • @JoelS-ky7ym
    @JoelS-ky7ym 5 місяців тому

    Great video Where do you get your new parts?

    • @abplctestbench759
      @abplctestbench759 4 місяці тому

      In Canada from Monitech Industrial in Ontario. They also have a branch in Florida. There are other sources if you look hard enough. Some better than others.

  • @fidellamothe6469
    @fidellamothe6469 6 місяців тому

    pleas i need a copy of softwere let me know

    • @abplctestbench759
      @abplctestbench759 5 місяців тому

      Hello Fidel: Sorry for the delayed reply. I do NOT have any software to sell. It is illegal for me to sell and Rockwell software. There is a group of Rockwell lawyers waiting for me to do that so they can sue me. You would have to have someone sign over their license to you in order to get a copy. Maybe one of the other subscribers has a copy they can lend to you, but I can't because of legal threats from Rockwell. I am sorry that I can not assist you with the software.

  • @turismodedrone3887
    @turismodedrone3887 6 місяців тому

    Hello. Thank you very much for the video

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      You are very welcome. Hope that the information is helpful.

  • @Yoyosten99
    @Yoyosten99 6 місяців тому

    What are the white/greenish trays that come with these terminal blocks? Looks like 8 tabs and 8 hooks/clips. Can't for the life of me figure out what they're for. Never seen any of our other slots use them.

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      Hi: Another bad idea from AB. These are supposed to be like the old style Keying bands that used to come with PLC5 chassis. They were responsible for a lot of damage to chassis and modules. You can set them up in a configuration of your choice to make sure the correct module is inserted into the correct wiring arm. A nice idea, but no idea if anyone uses them and AB does not give any guidance about using them. Recycle bin is best location IMO.

  • @bigtr250277
    @bigtr250277 6 місяців тому

    We had a L82ES do the same thing we have changed CPU's powersupply's and chasing, but no resolve. Rockwell has yet to come back with a good answer.

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      Hi BigTr: The longer the l8x is in service, the more problems seem to be showing up! Rockwell keeps doing firmware changes and screaming like kids about how everyone has to buy their software at insane prices, but not putting out a higher quality product. Each generation of Clogix processor has increased the processor speed 10x each time. But is it necessary? A super high speed processor is still not going to make your waste system in the basement work any faster or better. I still have customers very happily running SLC & PLC5 and it just keeps plugging along doing what it was designed to do.

  • @TB-oe4vr
    @TB-oe4vr 6 місяців тому

    I have some of these. How do you set them up to just test and try it out? I'm worried that some software that is no longer available is needed.

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      Hello TB: Which Flex I/O modules are you worried about? There are many of them and all are current. Can you be more specific in your question? I have a number of videos on my channel that use the 1794 modules. ua-cam.com/play/PLApJy6_fcuvi_kx1MeMJjYus6rphDwVma.html You can also check the Rockwell site for product lifecycle status list - www.rockwellautomation.com/en-us/support/product/product-compatibility-migration/product-lifecycle-status.html

  • @kimberlyclark955
    @kimberlyclark955 6 місяців тому

    Had a few real quick questions is there a part number to these plates and are these plates available from Allen Bradley?

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      Hi: If you look close on each one there is a part number on there. No idea if AB sells them as I am blacklisted from buying from AB because I sell parts that are experienced. I ended up getting a guy to make on a 3D printer. In bulk they cost me $45 (CDN) each to get made. The option is to get some SLC500 chassis and strip them out of there. They are exactly the same size and better quality using the grey plastic compared to the cheap black plastic that they used in Clogix. The Clogix footprint is based on the SLC footprint. If you look at the screw holes in the chassis they are exactly the same. Hope this helps.

    • @kimberlyclark955
      @kimberlyclark955 6 місяців тому

      @@abplctestbench759 Thanks for answering my questions that actually helps out a lot. I think I’m going to buy a 3D printer and print them off. I have a feeling Allen Bradley doesn’t sell them. I tried looking at some distributors but they all said they would had to get back to me. lately a lot of your videos have been a great help to me, so thank you for that as well.

    • @kimberlyclark955
      @kimberlyclark955 6 місяців тому

      @@abplctestbench759 Thanks for answering my questions . It helps out a lot.

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      @@kimberlyclark955 Your welcome - I have some in stock if you need a couple.

  • @emilio.ferreira
    @emilio.ferreira 6 місяців тому

    Hi... Where do I find Range12To15[0]?

    • @abplctestbench759
      @abplctestbench759 6 місяців тому

      Hello: I am not quite sure what you are asking. Can you please explain a little more what you are looking for. Thankyou

  • @agustinmozzoni6041
    @agustinmozzoni6041 7 місяців тому

    Hey i wanna know how i connect the panelview to the plc ... have allen bradley slc500 and panelview 550

  • @tonytanou
    @tonytanou 7 місяців тому

    I have had this on 3 processors. Terrible situation, we brought Rockwell for their reliability and responsibility. Both are badly lacking. I am now moving to use Japanese and Chinese plc products and so far reliability has been perfect.

    • @abplctestbench759
      @abplctestbench759 7 місяців тому

      HI Tony: I have to agree with you on the lower quality of the product they are putting out in the last 10 years. What was an industry standard is getting to be an industry joke. The original PLC5 / 1771 structure was designed by old school Rockwell engineers and built to US MIL Spec - MTBF design was 80 years. Lots of it still running. The new stuff is designed to commercial specs and will normally last around 10 years.

  • @edenlumbanraja5541
    @edenlumbanraja5541 7 місяців тому

    This is wonderful. Thank you

  • @tarynhuber6123
    @tarynhuber6123 7 місяців тому

    Thanks a lot my facility still implementing plc5, older SLC processors and different remote I/0 types not enough videos like this to learn from

    • @abplctestbench759
      @abplctestbench759 7 місяців тому

      Hi Taryn: Glad you were able to get some value out of my videos. As I have mentioned before the PLC5 generation of processors were designed by an older generation of designers. They were also built to US MIL SPEC and a have a MTBF of 80 years. The processor I used in this video has a date code of 1992 and I had just replaced the channel 1 communication port. It had blown up and there was carbon everywhere. But a quick changeout and away it goes for another 20 to 40 years. I think there will be lots of these in service long after I have turned to dust.☺

  • @michaelpetermorley3797
    @michaelpetermorley3797 8 місяців тому

    You’re a legend

  • @heshamtaha7562
    @heshamtaha7562 8 місяців тому

    hello sir , I was wondering if i can upgrade sd ram and cf card of allen bradley by other sd ram and cf card but not alllen bradley but its out cost around 50$ and in ab cost 800$ so am asking it is possible

    • @abplctestbench759
      @abplctestbench759 8 місяців тому

      Hello: The CF card is formatted with the operating system and the RAM chip matches the card. You should be able to pickup a set of CF & Ram from ebay or similar online market place in your country for a lower price than Rockwell dealers want. Once you have made sure that the 'new' CF card has the correct version of F/W to match your running program, just reload your program on to the new card. Sorry I can't help any more than that. Thank you for the question.

  • @MrExtremehustler
    @MrExtremehustler 8 місяців тому

    “Pktx rio adapter driver detected block transfer size mismatch for BT1 (rack:1(oct.) slot:8) Driver*” Any idea what to do about this message on my PV+? I have tried what is written in the knowledge base but that didn’t change anything. I have also tried two separate HMI.

    • @abplctestbench759
      @abplctestbench759 8 місяців тому

      HI: I have never seen that error. Suspect that you are using this on a PLC5? Possibly change out the RN6 communication card that is mounted on the logic module. The RN6 contains a standard 1784-PKTX communication card that plugs into the logic module. They can be set up for DH+ - RIO - DH485 for communication with PLC5 & SLC processors.

    • @MrExtremehustler
      @MrExtremehustler 8 місяців тому

      @@abplctestbench759 Thanks, yes that’s correct, PLC 5. The PanelView is connected to a 1771-ASB from the RN6. I have also tried two separate PV+ units. Both give the same error.

    • @abplctestbench759
      @abplctestbench759 8 місяців тому

      Hi:@@MrExtremehustler Not sure what to suggest then. Possibly check your program backups compared to your running file to see if anyone changed a parameter in the block transfers for the read and write to the PV. Is there data being written into the BT file area that is overwriting something it should not. Also is there a DH+ network and maybe someone is writing to your PV from another station? The only other possibility I might suggest is changing out the logic module and downloading a backup file to it. Not the file running on the PV you are having trouble with.

  • @jung1e
    @jung1e 8 місяців тому

    Have you ever had a chassis with dead spots? We have a 1756-A17 and a couple of he 1756-OF8 cards had their RTNs stop having continuity to the chassis ground. We have had 2 OF8 side by side with their RTNs functioning differently. Card replacement did not resolve the issue, so we are thinking its the chassis.

    • @abplctestbench759
      @abplctestbench759 8 місяців тому

      I have seen a couple of bad ones for sure. Because of how cheaply they designed the system it is possible for thin pieces of metal to get behind the backplane and then short out pins. I would start by taking the chassis apart on a clean bench and see if anything conductive comes out when you have dismantled it. The same with where the cards plug into the headers. They are not sealed on the bottom so there is a possibility of shorting material there. Also confirm all of your grounding from the power supplies and the chassis. All grounds used in the system must be tied to a common grounding point. Hope this helps.

  • @israelsalas4617
    @israelsalas4617 9 місяців тому

    awsome video!, is there a way that you can share the panel builder software for the 1400e? tnx!

    • @abplctestbench759
      @abplctestbench759 9 місяців тому

      Hello Israel - I do not have a copy that I can sell or give away. Even though AB / Rockwell no longer sells or supports the software they still own it and guard it like a mad dog. I have been warned that the Rockwell lawyers are laying in wait for me to sell software so they can shut me down. So I do not sell or trade in any software. If someone else has a copy that they can give you hopefully they contact you after seeing this post. Bruce

    • @israelsalas4617
      @israelsalas4617 8 місяців тому

      @@abplctestbench759 thank you!

    • @abplctestbench759
      @abplctestbench759 8 місяців тому

      Your Welcom@@israelsalas4617

  • @Gam491961
    @Gam491961 9 місяців тому

    Do you have a procedure to calibrate a thermocouple card mv 1756 16 or 8 Channel Type J

    • @abplctestbench759
      @abplctestbench759 9 місяців тому

      Hi Greg: From what I read in the documentation - a percision resistor is required to do this calibration on these cards. I asked multiple supply sources and no one could supply me with one about 6 months ago when I looked for them. The software will step you thru the calibration but the external resistor is required before you start. I will find the value and post here in the answers tomorrow. If you have a source I would like to get some for my stock! Thank you for asking.

    • @abplctestbench759
      @abplctestbench759 9 місяців тому

      Found this today in the Analog calibration manual: From reading thru the manual you need a mV voltage calibrator source. I don't currently have one and not sure of the prices, but suspect that $1000 or more is not out of line. Cut and paste from manual below. -------------------------- Calibrating the 1756-IT6I or 1756-IT6I2 This module only calibrates in millivolts. You can calibrate the module to either a -12…+30 mV range or -12…+78 mV range, depending upon your specific application.

  • @muqkhan786
    @muqkhan786 10 місяців тому

    Appreciate you for share your knowledge. It helped me and saved me time.

  • @Ronnie-f8x
    @Ronnie-f8x 10 місяців тому

    What cpu can wee connect for this i/o?

    • @abplctestbench759
      @abplctestbench759 10 місяців тому

      Hello: Any AB - Rockwell CPU that communicates with remote I/O devices.

  • @josmelc
    @josmelc 10 місяців тому

    Hello Sir, I had the same problem with 3 brand new series C 1500 screens, however, I fix the problem with just a firmware update. I used RP1 logic modules on those screens and after the firmware update didn't show any errors. The FW version I used was 5.10.16UP

    • @abplctestbench759
      @abplctestbench759 10 місяців тому

      Hi - Glad to hear of another way to fix this. Thank you

  • @OnlineIncome522
    @OnlineIncome522 10 місяців тому

    Sir, may i ask if the terminal A0 and 17 will normally have a 24v voltage?

    • @abplctestbench759
      @abplctestbench759 10 місяців тому

      Hi - Input or output module?? The wiring diagram shows all of the connections.

    • @OnlineIncome522
      @OnlineIncome522 10 місяців тому

      @@abplctestbench759analog input module sir, connected to 4 wire flowmeter

    • @abplctestbench759
      @abplctestbench759 10 місяців тому

      The wiring diagrams and documentation is on the Rockwell website. I suggest you go there and download the document for the module . www.rockwellautomation.com/search/ra-en-US;keyword=1794-IE12;startIndex=0;activeTab=Literature;spellingCorrect=true;facets=doc_type_full_s%253A%2528%2522Installation%2520Instructions%2522%2529;languages=en;locales=en_GLOBAL,en-US;sort=bma;isPLS=false;sessionID=7d520837-6fe7-6066-20ff-de0ddee07dab;deepLinking=false

  • @marshal7102
    @marshal7102 11 місяців тому

    Hi, I have several AB PLC's mostly SLC500 and 1000"s and have RS Logix 500 and 5000. I also have the 1771 with a 1785 5/40 Processor and a 1785 5/20. I and trying to find RS logix 5 demo or evaluation copy just to get this this this running and I have loads of card for it from analog, discrete, digital and many more it has the full size back plane I forget how many slots, I go it put up now but would love to fire it up and see what it does. I cannot find it anywhere other than from Rockwell Automation and can't even get my account setup with them anyway for some reason but don"t have the thousands of dollars for it. Is there a demo version of this available?

    • @abplctestbench759
      @abplctestbench759 11 місяців тому

      Hi Marshal: There used to be demo versions but Rockwell is hard set on trying to kill off the PLC5 systems. Last I heard is that they have removed all support for it and if you really want a copy it is well north of $20K for a 1 year license. There are none on ebay that I know of because of Rockwell threatening to sue ebay over copywrite. Because of threats of being sued I have no idea where I can suggest that you go and I do not have any demo's left that work. If someone has a copy that they are no longer using and have the key disk for it that will be your best bet. Sorry I can't be of any help on software but Rockwell has it tied up in a steel drum and welded shut. Hopefully someone can get ahold of you thru your website with an offer.

    • @marshal7102
      @marshal7102 11 місяців тому

      Yeah I was afraid of that. Well, Thanks very much for your help and your videos are great. Thanks again and keep up the great work.@@abplctestbench759

  • @diegoestebandagatti4150
    @diegoestebandagatti4150 11 місяців тому

    Hi! Nice to meet your channel, where are you from?

  • @emrekahraman9854
    @emrekahraman9854 11 місяців тому

    You didnt explain how we solve this issue. Could you explain how we solve please

  • @srinathan8494
    @srinathan8494 11 місяців тому

    Hello sir..hmi not working off mode only Back side of hmi faulty indication coming what is the issue can u possible to tell..

    • @abplctestbench759
      @abplctestbench759 11 місяців тому

      Hello: Without having it in hand I can only guess. I would suspect that the touchscreen is damaged and needs to be replaced. The touchscreen overlay is made of a plastic and depending upon the age may have an electrical grid in it to work as buttons for the screen You would have to send it out for repair or get an exchange unit. If you have the parts in hand it is a bit of work to rebuild, but can be done if you have the experience.

    • @srinathan8494
      @srinathan8494 10 місяців тому

      @@abplctestbench759 I think not a touch screen problem..becaz I swapped logic module from another hmi ...that time hmi was on mode...so what is the pbm in logic board ...

    • @abplctestbench759
      @abplctestbench759 10 місяців тому

      @@srinathan8494 - Hi: Logic boards have been known to die. You need to get a replacement or send it out for repair.

  • @jamiuadeagbo1444
    @jamiuadeagbo1444 11 місяців тому

    Thanks for this wonderful and peaceful assembly explanation without stress

  • @nadavran
    @nadavran Рік тому

    This is probably a power supply issue. I had the same problem with a PB75 + L81E. the same PLC worked well on another chassis so I figured out it was not the fault of the PLC. After replacing the bad PB75 with a different power supply unit, everything worked well.

    • @abplctestbench759
      @abplctestbench759 11 місяців тому

      Hi: A good thought to check into, but with the unit shown it was tested in multiple chassis and it still did the same errors. Thank you

  • @bartniehorster3453
    @bartniehorster3453 Рік тому

    Hi I am trying to troubleshoot a Panel view Plus 1000, but when powered the screen does not show anything, and The Fault LED is blinking, according to the manual this means it is a recoverable fault. I suspect it does not go past the initial boot. Any ideas, or do you have a contact I could reach out to you to better explain?

    • @abplctestbench759
      @abplctestbench759 Рік тому

      HI Bart: I would suspect that the CCFL is burnt out and not having a picture to look at possibly a damaged overlay causing a stuck button error. Since the PVP6 is a plug and play item, I would start by moving the logic module to another panelview if you have it to see if the problem moves with the logic module. No idea where on the planet you are - I am in BC Canada. Normally I can turn these around in a day as I have the parts in hand to fix them at a reasonable price. I will see if I can enable the contact link here on YT and then you will be able to contact me. Bruce B

    • @abplctestbench759
      @abplctestbench759 Рік тому

      email is enabled on youtube. Once you contact me I will disable it. Way too much spam out there. BB

    • @bartniehorster3453
      @bartniehorster3453 Рік тому

      Thank you for replying to my comment. I am in Honduras, Central America. I am looking for way to contact you via email, but can't see where contact on youtube is located. Not sure if I can give my email, and then you can erase the comment to prevent from getting spam, or falling in the wrong hands.

    • @abplctestbench759
      @abplctestbench759 Рік тому

      @@bartniehorster3453 at the top of the front page where it says' with over 35 years experience' there is a > - click on that and a window will open - scroll down a bit and you will see the contact area. Click on it and follow the steps to get my youtube email. Bruce

  • @MuhammadFaisalTalib28
    @MuhammadFaisalTalib28 Рік тому

    Hi I have a 1794-IE12 that is flashing green and showing FieldPowerOff as a 1. I have it configured properly. What can I do to fix this issue?

    • @abplctestbench759
      @abplctestbench759 Рік тому

      Hello: That is normally the error when you have a broken wire / open connection between the device and the module.

  • @Nicofish2023
    @Nicofish2023 Рік тому

    Thanks sir. Please do you offer any training?

    • @abplctestbench759
      @abplctestbench759 Рік тому

      Hello - No I do not. There is a link at the top of my page that shows www.plcs.net/ for training I would start there as there are multiple subjects and links for training. Thank you for asking.

  • @RodrigoSantander-c6v
    @RodrigoSantander-c6v Рік тому

    What kind of wire did u use ?

    • @abplctestbench759
      @abplctestbench759 Рік тому

      Hello: 18AWG - Shielded wire. All grounds tied together at the module end.

  • @richarddemelobezerra3122
    @richarddemelobezerra3122 Рік тому

    Olá amigo, estou com problema em uma L-82ES /b está com a falha 61, o que pode estar ocasionando isto?

    • @abplctestbench759
      @abplctestbench759 Рік тому

      Hello Richard: It is appearing that this is some sort of generic code that pops up for different reasons. Rockwell does not seem to be willing to help much. Sorry I can't give any better ideas on this.

  • @fernandomatiasn
    @fernandomatiasn Рік тому

    Hi, do you have any video or code that you can send on how to create a virtual axis through an encoder that enters an HSC module and then gear it to a real axis of a Kinetix 6000. Regards

    • @abplctestbench759
      @abplctestbench759 Рік тому

      HI Fernando: Sorry I have no idea about anything to do with Kinetix. Have never worked with them and don't think I have ever seen one. Wish I could offer more help but not within my abilties.