Heating Diverter Valve Faults SOLVED

Поділитися
Вставка
  • Опубліковано 15 гру 2024

КОМЕНТАРІ • 31

  • @dinosauraccounts1411
    @dinosauraccounts1411 Рік тому +1

    Hi George, very informative. I have just changed a diverter valve - brand new.
    When hot water is on, the CH Flow pipe get red hot at the same time- letting by.
    Also when heating comes on- it ramps up temp really quickly and shuts off within a few wins
    I ran the p0 purge sequence- thinking it was air trapped in main heat exchanger without luck.
    Canoe filter is clear, expansion vessel charged up, boiler has inhibitor, plate exchanger seem clean when I inspected.
    What could it Be? I suspect the motor on diverter is not fully sealing?

    • @mrcombiBedford
      @mrcombiBedford  Рік тому

      Thanks for asking and comment, Not understanding you changed the diverter but NOT the motor? DON'T get a recon buy NEW. It comes as a unit. Well done with the canoe you have a lot to talent and guts, not many would know about that the but it's only on the HW side, wouldn't solve your problem. Vaillant have a program "P1" etc. to remove air use it, I am the only person who used it.
      Check pump is 220Ω and flush main EXCH then 2 bottles of F2 should do. good luck 👍😀

  • @andymav3023
    @andymav3023 2 роки тому +1

    Hi George another great video and very pleased with the apps!! Would a flow turbine / sensor give a fault like no hot water but heating still works ? what do you need to look for to differentiate between the diverter vale fault and a flow sensor ? Might seem a silly question but still learning myself really.

    • @mrcombiBedford
      @mrcombiBedford  2 роки тому

      Hi Andy, thanks for asking, easy, if the DV is stuck we don't get the demand we want, if the sensor is faulty we don'ts get change in ohms Hz or volts from 0 to what ever it should be @ 10ltrs M.
      That is a £20 question Ha Ha. take care, george 😍

  • @sambutler927
    @sambutler927 4 роки тому

    Great vid, I have been wiring my own heating controls for the last few years and am allot more confident with my fault finding thanks to this man. Well done George 👍👏👏

    • @mrcombiBedford
      @mrcombiBedford  4 роки тому

      Hi Sam, many thanks for the kind review, if anyone would like a video on a subject please email info@mrcombi.com

    • @mrcombiBedford
      @mrcombiBedford  4 роки тому

      Hi Sam, Thanks for kind words, a cheque is in the post.

    • @mrcombiBedford
      @mrcombiBedford  3 роки тому

      Thanks for the kind words, only trying to help. Take Care george staszak

    • @mrcombiBedford
      @mrcombiBedford  3 роки тому

      The cheque is in the Post, thanks for kind words, george

    • @mrcombiBedford
      @mrcombiBedford  3 роки тому

      Hi Sam, I do try and make a difficult job a bit easier to understand, take care, george

  • @adamwilliams5372
    @adamwilliams5372 3 роки тому

    Does the diverter valve make a high pitch squealing under hot water demand before it fails?

    • @mrcombiBedford
      @mrcombiBedford  3 роки тому +1

      Hi Adam, thanks for the question, yes they do make a noise when the gears are moving, this can happen after 5 years that's why we recommend replace all valves then. That stops expensive breakdowns and slows to upgrade the system. regards, george

    • @adamwilliams5372
      @adamwilliams5372 3 роки тому

      @@mrcombiBedford Thank You George appreciate your reply

  • @ganoostermoppy4325
    @ganoostermoppy4325 3 роки тому

    How much will a plumber charge to replace/fix this diverter, I don’t want to be scammed. Thanks

    • @mrcombiBedford
      @mrcombiBedford  3 роки тому +2

      Thanks for the question, To replace the whole valve would be about £300.00 including flush and F2 inhibiter. To find someone, go to the boiler web site to find a local hero you can trust.Take care george staszak

  • @FitOnce
    @FitOnce 3 роки тому

    Will do - kit works fro both brass and plastic. Must admit have changed 100s of these and never seen the actual valve body split its always been the internal cartridge leaking. Cheers.

    • @mrcombiBedford
      @mrcombiBedford  3 роки тому

      You are very lucky, plastic and combies don't mix. Remember the VCW 242 had a black chocolate heat exchanger, was it a good idea? No all split went to S Steel very quickly. george

  • @MegaSunnydon
    @MegaSunnydon 2 роки тому +2

    Too much talking on what to do not telling enoug

    • @mrcombiBedford
      @mrcombiBedford  2 роки тому

      Thank you for your comment, regards, george

    • @MegaSunnydon
      @MegaSunnydon 2 роки тому +2

      @@mrcombiBedford
      You can go into details excluding the details of tools you can’t be advising public as a person has to be gas safe registered,if the person doesn’t know tools then you are wasting other peoples time by going into elementary details
      Sorry I feel that way

    • @mrcombiBedford
      @mrcombiBedford  2 роки тому

      @@MegaSunnydon Hi Sunny, good point thanks for your opinion, take care, george