Shane , thanks for the great contents. Do you have any video about importing exporting recipes ? the reason is to edit them in excel and then import them back . is this possible ?
If I have a project in factorytalk machine edition and I want to migrate it to site edition, what do you think is the best way to migrate the alarms? my problem is that I have groups of real type alarms, for example in tag1, if I send 10 it is an alarm, for the same if I send 11 it is another alarm and so on several occasions. I'm interested in your video of derived tags, I haven't used them but I think it can be done with it, or I thought of making a level alarm for each case but I didn't think it was the best way, could you give me your opinion? thank you
Depending on what version of Factory Talk SE you are using, I would recommend exporting the alarm database then restoring it in Site edition. Do a practice run on a separate PC then double check all is working as designed. I say this because FTview 12 no longer supports legacy alarms I made a video about the legacy alarms & spoke about this
Subscribe: mmini.me/Subscribe-4-Updates
Other socials:
Facebook: facebook.com/OnlinePLCSupport
LinkedIn: www.linkedin.com/in/shane-welcher-sr/
Shane , thanks for the great contents. Do you have any video about importing exporting recipes ? the reason is to edit them in excel and then import them back . is this possible ?
Not at this time, it's a good idea though
If I have a project in factorytalk machine edition and I want to migrate it to site edition, what do you think is the best way to migrate the alarms? my problem is that I have groups of real type alarms, for example in tag1, if I send 10 it is an alarm, for the same if I send 11 it is another alarm and so on several occasions. I'm interested in your video of derived tags, I haven't used them but I think it can be done with it, or I thought of making a level alarm for each case but I didn't think it was the best way, could you give me your opinion? thank you
Depending on what version of Factory Talk SE you are using, I would recommend exporting the alarm database then restoring it in Site edition.
Do a practice run on a separate PC then double check all is working as designed.
I say this because FTview 12 no longer supports legacy alarms
I made a video about the legacy alarms & spoke about this
Hey Shane,
Is there any limitations to the number of tags to be on one GFX/screen?
Not to my knowledge, it would effect screen loading times though
Thank you Im korean
Glad to help
I'm guessing this is not available in ME?
Correct, this is for Site Edition.
There is a similar way to do this with Machine Edition as well.