Daikin inverter | air conditioner Thermistor Failure Symptom

Поділитися
Вставка
  • Опубліковано 7 вер 2024
  • Brand : Daikin
    model : MKS80QVM
    ERROR : No error
    Symptom: Running after 45minutes,Fcu auto off and auto on back,outdoor LED 1 & 2 light up.
    Cause : Thermistor failure Symptom,thermistor short circuit.
    #bonmj #daikin #inverter

КОМЕНТАРІ • 108

  • @Techhvac
    @Techhvac 3 місяці тому +1

    Sir .Bon Mj
    Your technical Video's very useful for technician. Great job
    Thank you so much 🙏🇶🇦

    • @BonMj
      @BonMj  3 місяці тому

      It's my pleasure

  • @Achabab
    @Achabab 2 роки тому +1

    I never find this problem before😂😂😂, first time some one share this information in UA-cam.
    You are the best⭐⭐⭐⭐⭐

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @vladimirmakhney5407
    @vladimirmakhney5407 2 роки тому +1

    Hello. A very good tip, I'm sure many technicians didn't even know about it

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @robinsonguanzon8092
    @robinsonguanzon8092 2 роки тому +1

    Thanks Sir Bon Mj ❤️
    A big help to us technician, A far areas and urban areas..🙏🙏🙏

    • @BonMj
      @BonMj  2 роки тому

      Welcome

  • @JDT738126
    @JDT738126 2 роки тому +2

    Bon your videos are excellent! Thank you

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @carlocurotto7555
    @carlocurotto7555 2 роки тому +2

    That’s a great tip thank another fantastic video

    • @BonMj
      @BonMj  2 роки тому

      Thanks bro🙏

  • @birin.6884
    @birin.6884 2 роки тому +3

    Hey, thanks for everything. explain his picture and I'm good.

  • @februaryoakkar938
    @februaryoakkar938 2 роки тому +3

    Thank you sir

  • @jagannath3839
    @jagannath3839 2 роки тому +1

    This is very good helpful information thanx sir.

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @estanislauboavidabelo4975
    @estanislauboavidabelo4975 2 роки тому +1

    thank you, please continue to upload the video.

    • @BonMj
      @BonMj  2 роки тому

      Thanks bro

  • @narayanaya5519
    @narayanaya5519 Рік тому +1

    Very useful information

  • @linaung127
    @linaung127 2 роки тому +1

    Hello sir, nice troubleshooting, thanks

    • @BonMj
      @BonMj  2 роки тому

      Welcome

  • @arunramachandrana1025
    @arunramachandrana1025 2 роки тому +1

    Very good information

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @Blueblurr112
    @Blueblurr112 2 роки тому +1

    Great video thank you.

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @shreekanay698
    @shreekanay698 2 роки тому +1

    Thanks Boss.

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @karimchiu7527
    @karimchiu7527 Рік тому +1

    Thank Sir Bon

  • @sarfarajshaikh4582
    @sarfarajshaikh4582 2 роки тому +1

    Nice one bro

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @alanwong2761
    @alanwong2761 2 роки тому +1

    👏 bravo bro 👍

  • @Didik-cq8wy
    @Didik-cq8wy Рік тому +1

    Trimakasih bos

    • @BonMj
      @BonMj  Рік тому

      You Dari mana?
      Terima kasih banyak nonton video saya

  • @hafeezdaikin2517
    @hafeezdaikin2517 2 роки тому +1

    Thank you boos 👍

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @arafteknikac
    @arafteknikac 2 роки тому +1

    Thank you so much

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @aselajayasundara1669
    @aselajayasundara1669 2 роки тому +1

    Thank you sir 🙏

    • @BonMj
      @BonMj  2 роки тому

      Thanks🙏

  • @karaors8970
    @karaors8970 2 роки тому +1

    Thank you bro

    • @BonMj
      @BonMj  2 роки тому

      Thanks bro

  • @winmaung4558
    @winmaung4558 2 роки тому +1

    Thank sir

    • @BonMj
      @BonMj  2 роки тому

      Welcome

  • @mdtuhintalukder5012
    @mdtuhintalukder5012 2 роки тому +1

    Thank you....

    • @BonMj
      @BonMj  2 роки тому

      Thanks

  • @tabresztabu562
    @tabresztabu562 2 роки тому +1

    Tq Boss 🙏

    • @BonMj
      @BonMj  2 роки тому

      Thanks🙏

  • @khaidang8614
    @khaidang8614 Рік тому +1

  • @JDT738126
    @JDT738126 2 роки тому +2

    Hi Bon, could you please provide a source for many of the common manufacturers thermistor resistance/temperature values? I cannot find any for the LG brand.

  • @jamestan7901
    @jamestan7901 2 роки тому +1

    👍 👍 👍

  • @user-vz6mu7iu7j
    @user-vz6mu7iu7j Рік тому +1

    hi sir im p paul kolkata i lick you video

  • @peramaraj2763
    @peramaraj2763 11 місяців тому +1

    Normally daikin compressor discharge thermistor range 13 to 15 kilohms right ?

  • @MrRandyj72
    @MrRandyj72 2 роки тому +1

    That would be hard to find on the system unless its in cooling mode developing condensation at the time you are checking.
    Did the error code send you in the direction to check the thermistors?
    Last question did you full change the harness or just dry and seal the bad thermistor?

    • @BonMj
      @BonMj  2 роки тому +3

      Just happen after running 45minutes.
      Only outdoor LED 1&2 on when stop running,indoor auto off and will auto on back after for awhile.
      We replace the new harness.

    • @Achabab
      @Achabab 2 роки тому +1

      @@BonMj thank you share your knowledge 🙏🙏🙏god bless you

    • @BonMj
      @BonMj  2 роки тому

      @@Achabab welcome

  • @alembattlerealmsgamefowl6631
    @alembattlerealmsgamefowl6631 5 місяців тому +1

    sir inverter daikin 1.5hp ,indoor fan motor stay in low speed what maybe the reason o the problem ? even we changes to high speed in the remote fan speed still low,thanks for the reply

    • @BonMj
      @BonMj  4 місяці тому

      Any coil choke

  • @azadabduellahal8116
    @azadabduellahal8116 Рік тому +1

    Same can happen Mitsubishi system

  • @errantpmd3765
    @errantpmd3765 Рік тому +1

    Sir. My aircon.. cut in compressor n fan for 30min for 3 room.
    Is it thermistor of outdoor? I saw your ismike series, u change the indoor thermistor...
    May I know if is the same logic?
    Mine are toshiba

    • @BonMj
      @BonMj  Рік тому +1

      What is your setting temperature

    • @errantpmd3765
      @errantpmd3765 Рік тому +1

      @@BonMj sir.. even in the lowest also the same.

    • @errantpmd3765
      @errantpmd3765 Рік тому +1

      @@BonMj correction sir. Is 30sec..not min.

    • @BonMj
      @BonMj  Рік тому +1

      @@errantpmd3765 may be outdoor pcb problem

    • @errantpmd3765
      @errantpmd3765 Рік тому +1

      @@BonMj sad.. :(
      Thought is some thermistor...

  • @ThesecretS_a_n_3_1
    @ThesecretS_a_n_3_1 3 місяці тому +1

    Daikin Indoor fan motor no running a6 alarm coming I replace indoor motor and indoor PCB board also but still have a6 alarm ? What is problem

    • @BonMj
      @BonMj  3 місяці тому

      Check thermistor

  • @zse0118
    @zse0118 2 роки тому +1

    Hi Sir!
    What's the reason you put the thermistor in the water and than you checked the countinity again?

    • @BonMj
      @BonMj  2 роки тому +2

      Put in the water just show the thermistor is short circuit when water go in to the parts.
      When the thermistor locate at suction pipe,the water will go into the parts after gas pipe condensation.

    • @zse0118
      @zse0118 2 роки тому +1

      @@BonMj Thank you so much for your answer.

  • @arasanairconsolution4u9
    @arasanairconsolution4u9 2 роки тому +1

    Hai sir ,vrv 3 Daikin system one outdoor 3 indoor ,all running good but , standard compressor Haven't run even one FCU haven't achieve room required temperature.please advise

    • @BonMj
      @BonMj  2 роки тому

      May be already by pass.
      Check mode2

    • @peramaraj2763
      @peramaraj2763 11 місяців тому

      ​@@BonMjalready bypass how to find ? Bro

  • @antoinetuyongo6527
    @antoinetuyongo6527 2 роки тому +1

    Bonjour , comment je pourrais avoir la version française

  • @narayanaya5519
    @narayanaya5519 Рік тому +1

    If short thermistor what could happen PCB

    • @BonMj
      @BonMj  Рік тому

      For this case intermittent blinking, pcb ok.

  • @janshaw5472
    @janshaw5472 2 роки тому +1

    这种情况好难被发现!感谢老师!contiuniry中文是什么?

    • @BonMj
      @BonMj  2 роки тому

      谢谢你。去了两次才发现

    • @BonMj
      @BonMj  2 роки тому

      Continuity 是联系的,比如wire用meter 量continuity 。

  • @randypatcho6051
    @randypatcho6051 Рік тому +1

    How to apply your company sir

  • @ManojKumar-zu2yz
    @ManojKumar-zu2yz Рік тому +1

    Sir daikin vrv3 modal rxyq12pry6 error code p4 Cheng master PCB

  • @abidshirhatti6815
    @abidshirhatti6815 2 роки тому +2

    Hi sir my wathsup no not going for comment

  • @gothandaraj860
    @gothandaraj860 2 роки тому +1

    Hi sir vrv 3 Daikin AC e2 error and E3 error how to make rectify

    • @BonMj
      @BonMj  2 роки тому

      E2 may earth leakage
      E3 high pressure sensor/high pressure switch

  • @govindarasugovindarasu7440
    @govindarasugovindarasu7440 2 роки тому +1

    Hi sir I have problem is Diakin air conditioning vrv system celling saspanded units have the error UF this error what is the problem sir thanks

    • @BonMj
      @BonMj  2 роки тому

      You change indoor pcb?

    • @govindarasugovindarasu7440
      @govindarasugovindarasu7440 2 роки тому

      @@BonMj no sir

    • @BonMj
      @BonMj  2 роки тому

      @@govindarasugovindarasu7440 check indoor all fcu voltage or pcb faulty

  • @nagarajvenkat8476
    @nagarajvenkat8476 2 роки тому +1

    Hi sir I have problem daikin package unit error E 32 how to rectify this problem sir

  • @mycountrymyvlog1
    @mycountrymyvlog1 2 роки тому +1

    i need job i am air conditioning and refrigeration mechanic

  • @azizullahkhanpathan2693
    @azizullahkhanpathan2693 2 роки тому +1

    Hello sir I am Aziz. I have a Daikin 1.5 ton inverter split AC. My AC is showing C3 error code. Can you please tell me what C3 error code is and how to solve it . Model no FTKZ50U

    • @BonMj
      @BonMj  2 роки тому

      Try check i door thermistor.
      Actually this error is water level sensor problem

    • @azizullahkhanpathan2693
      @azizullahkhanpathan2693 2 роки тому +1

      Thank you for your reply sir 👍

    • @azizullahkhanpathan2693
      @azizullahkhanpathan2693 2 роки тому +1

      I will check

    • @azizullahkhanpathan2693
      @azizullahkhanpathan2693 Рік тому +1

      @@BonMj Hello sir my AC is Daikin inverter split AC it is showing C3 error code will you please confirm what is the issue in it C3 means?????

    • @azizullahkhanpathan2693
      @azizullahkhanpathan2693 Рік тому +1

      In the split AC water level sensor will be there ?????