@@bishantkumar12589 sir i am electronics engineer. I want to know from you whether I should change the ID card or solve the program problem in the software section? what advice do you think?
Sir, acs 800 drive me 99 group me motor data set kardia but jab id run kia to no motor data show karta he drive, kya problem ho sakta he thoda bataiye sir
Halo sir, Sir 22 kw abb ke vfd hi, usme vfd runing tim me vfd automatic output dena band kr deti hi. Fir 10 minutes ke bad chalne lagti hi. Na he koi alram aa rha hai, na he koi tripping indication. Out put voltage 412, 412,411 Feq 42 hz high set point. Ples help me sir
dear sir i have abb drive 2.2 kw 3phase motor run position many times stop There is no error i change bush buttons relay with bas and also drive but still problems
Well sorry about this, we hardly used laptop for program configuration in ABB ACS drives yet. So not having proper idea. With CDP/HMI we do program configuration
You can connect drive panel to USB to laptop. But this is normal panel. You can't do with this one. After connection you can Install drive composer pro or entry and can access full drive from it.
Maximum current limit too low. Check settings of parameters 99.06 Motor nominal current and 30.17 Maximum current. Make sure that 30.17 > 99.06. Check that the drive is dimensioned correctly according to the motor.
@@bishantkumar12589 Display fitting same hy but it's ACS 355 not ACS 550 , agr aap k pass ACS550 original panel display hy to aap ko difference pta chal jy ga
Thanks for the explain easily
Welcome 🤗 pl share this technical channel with your electrical team 🙏🏼
Sir apne ID run load coupled condition me kiya ya decoupled me.. Coupled contidion me ID run kar sakte hai kya.? Please reply to me ..sir
Donno condition me possible h ID run. Coupled condition me Standstill mode select karna hota hai
Sir plz give some more videos on abb 550 drive ..so that it b helpful for us
Few more videos available on my channel, pl do check ✔️
Presentation is very good. Just use a microphone to improve the sound quality.
Okay sir. Thank you for your feedback 😊
Nicely explained 👍
TQ sr
Hello how to run this in remote mode.I need to set this on timer mode.Thank you.
ID run can not be done on Remote Mode as per my experience
Off karne ke baad v kuch kuch frequency me run karts h kya
15-20 seconds tak karta hai. Ramp down time kahate hai use
@@bishantkumar12589 bms se off karte h but vfd me 0.6 hz rahta hi h esliye motor chalta rahta h
@@bishantkumar12589 esliye kya koi programing miss h ya kuch aur
Bhut achha video hai sir
DHANYAVAAD DOST
Good information
TQ
Abb550 ko 3phese 230v se start kar sakte hai?
Nai Bhai
Ye quick commissioning ke parameters koi bhi batayega ..dig input outputs, mode of frequency setoing dig inputs parameters bhi batao
Ok
How to find igbt phase missing through ABB drive window.
I'm not sure about it, but I think CPD will display phase loss fault in that case
Sir abb vfd ko Solar voltage ⚡ kitny se kitny tk de sakty hen
Iska too idea nai h mujhe bhai. Maine esa use nai kiya abhi tak
Check karta hu, sayad kuch mil jae
hello sir I have an Abb ACS550 series. It gives error f0026. what should i do Is it possible to reset this error?
It's drive error. Internal Fault, configuration block drive id is not valid brother. You need to contact your ABB service engineer
@@bishantkumar12589 sir i am electronics engineer. I want to know from you whether I should change the ID card or solve the program problem in the software section? what advice do you think?
Sir, acs 800 drive me 99 group me motor data set kardia but jab id run kia to no motor data show karta he drive, kya problem ho sakta he thoda bataiye sir
Ek baar program upload kariye
Nai too parameters load karne k baad, save kariye. Parameter number main dekh k batata hu
Sir I have VFD ABB make model Acs550 fault F0101 what should I do so that fault may be rectify
Sir. It's SYSTEM ERROR. you have to contact the service engineer of ABB
@@bishantkumar12589 please help me to contact service engineer
Very good sir
Thanks bhai
Motor de couple nahi karsakthe hai tho konsa setting
ACS 550 me couple/decouple k liy same steps h
Sir aap ek video ht motor pe bnaye
Okay bhai. Waise Maine ek video Dala hai, Lt n Ht motor k difference pe. Aap dekh sakte h
Driveb me light nhi a rhi hai
display me ???
Halo sir,
Sir 22 kw abb ke vfd hi, usme vfd runing tim me vfd automatic output dena band kr deti hi. Fir 10 minutes ke bad chalne lagti hi.
Na he koi alram aa rha hai, na he koi tripping indication.
Out put voltage 412, 412,411
Feq 42 hz high set point.
Ples help me sir
Running condition ka voltage h ye sab .?
Ek baar local me run kar k chhod do bhai. Observe karo esa hota h ya nai
@@bishantkumar12589 ok sir
@@bishantkumar12589 ha ji
Jb vfd remote mode me running hoti tabi yhi problem ati hai,
All perameter, amp, feq is ok
Sir please tell me ABB drive 550 how can change acceleration and deceleration time
Paaji. Pl go through this link ... All important parameters are covered for ACS 550 drive
ua-cam.com/video/vBOuVZ3V7RY/v-deo.html
Good sir
ACS 550 all setting pe video banaiye sir
Okay dost. Banata hu jaldi hi.
Pl support channel.
dost actually, total 99 parameters hote ahi. aane wale videos me main jo imp parameters hai uspe video daal dunga, pl wait for sometime
Sir inverter drive ke repiring pr b video opload kary thanks
Okay sir
dear sir i have abb drive 2.2 kw 3phase motor run position many times stop There is no error i change bush buttons relay with bas and also drive but still problems
I'll check and tell your solution, pl wait.
Nice
TQ sr
How to connect acs550 to laptop?
Which one software is option?
Well sorry about this, we hardly used laptop for program configuration in ABB ACS drives yet. So not having proper idea. With CDP/HMI we do program configuration
@@bishantkumar12589 thanks for your quick response
@@sudalaimuthup ur wlcm. Pl support d channel.
You can connect drive panel to USB to laptop. But this is normal panel. You can't do with this one.
After connection you can Install drive composer pro or entry and can access full drive from it.
Drive windows light2
please give me some information.
Ya 👍🏼
I have issues VFD ABB2016 alarm
Check for minimum torque settings
Display kaha mileage sir ..
Order karna hoga ABB team ko
Sir ACS550 ABB VFD is showing F0001 how to fixed.
Maximum current limit too low. Check settings of parameters 99.06
Motor nominal current and 30.17
Maximum current. Make sure that
30.17 > 99.06.
Check that the drive is dimensioned
correctly according to the motor.
Please check the solution sr
Sir vvfd main faut A50011 hain
Esa koi alarm nai h sir.
A5011 hai - drive kisi dusre source se control ho raha h, wo check Karo aap
How can change the direction of motor
ua-cam.com/video/SjdqvXm0iFQ/v-deo.html
Please check this video
whats purpose of id run?
ua-cam.com/video/0amyra50Bg0/v-deo.html
Ye kitne kw ki hai
5.5 kW
Vdf 550fault 0021 aa raha hai solution bataye sir
It's - drive's internal fault. Current measurement is out of range. Talk to your service provider ABB
Moter Rpm change 50hz video bana degiye
Okay bhai
Sir isme A 2010 dikha raha hai kiya kare
Check for MOTOR TEMPERATURE sir.
Motor temperature can be more, motor RTD is in line with drive ?
Check parameter p35. Motor temp measure
How to see load
Check parameter - 0106 : Power
Very good sir apka chahiye
TQ sr
Mujhe draif chahiye sir apka number dijiye
Mujhe draif chahiye sir apka number dijiye
👌👌👍👍
Thank you
Please help me to fix A2004 error code. DIR lock
What's the problem? Direction not changing or. Drive tripping?
@@bishantkumar12589 drive not starting
Sir abb vfd ky fault history reset kasy kry gy
HMI se hona muskil hai, aap laptop connect kar k delete kar sakte hai. Pl contact service engineer
Why need ID run..?? explain..
ua-cam.com/video/0amyra50Bg0/v-deo.html
Please watch this video
Calculate motor characteristics for higher accuracy control motor , especially vector control mode
I'd runs Ka mean kya hota h
Identification Run !!!
ua-cam.com/video/0amyra50Bg0/v-deo.html
Please check the link
Sir display ACS 355 Ka hy, kindly change kr ly
Nai bhai. ACS 550 ka hi hai. Donno ka same ho sakta hai
@@bishantkumar12589 Display fitting same hy but it's ACS 355 not ACS 550 , agr aap k pass ACS550 original panel display hy to aap ko difference pta chal jy ga
I'd run nhi ho rha h fault 0011 aa rha h
ID run complete nai ho raha hai.
Check for and correct -
1. Motor connection
2. Motor parameter - 9905 to 9909
acs550 vfd me last falt kaise dekhe
Main uspe VIDEO upload karta hu
Jitne bhi fault code hain ABB Frequency Drive model ACS 550 mein sabki list bhejta hoon apna mob. No dena
Jitne bhi fault code hain ABB Frequency Drive model ACS 550 mein sabki list bhejta hoon apna mob. No dena
DCS 800 Ka ek video banaye I'd run Kise hoga
OK
@@bishantkumar12589 sir dcs800 autotune Karna hai
@@amitkoni92 main check k reply karta hu
Acs 560 parameters 2 wire and 3 wire
Sir ac VFD mein torque ko kitne mein set karna chahiye.
Minimum = - 300
Maximus = + 300
Parameter 24 in ABB ACS 850
General settings
Sar Ji ek drive mein model acs150 porat s nhi calri number 8930936009 aap bataiye kis parameter ki ismein problem hai
Okay bhai. Check kar k msg karta hu asap
@@bishantkumar12589 kya hua ser ji
@@bittuverma02552 bhai. Check Parameter : 16 - SYSTEM Controls. 1606 - set to 0 for local Control
Shola Shola mein jakar zero kar diya hai per fir bhi nahin chala
@@bittuverma02552 remote se run karna h ya drive k panel se ?
F0022folt
FAULT - SUPPLY PHASE
SOLUTION - Ripple voltage in the DC link is too high. Check for and correct:
• Missing mains phase.
• Blown fuse.
Good sir
Thank you