ABB ACS 550 VFD - ID RUN / MOTOR IDENTIFICATION RUN STEPS

Поділитися
Вставка
  • Опубліковано 26 жов 2024

КОМЕНТАРІ • 158

  • @amirkumarsamal7991
    @amirkumarsamal7991 11 місяців тому +1

    Thanks for the explain easily

    • @bishantkumar12589
      @bishantkumar12589  11 місяців тому

      Welcome 🤗 pl share this technical channel with your electrical team 🙏🏼

  • @Raja8809-z2q
    @Raja8809-z2q 2 роки тому +2

    Sir apne ID run load coupled condition me kiya ya decoupled me.. Coupled contidion me ID run kar sakte hai kya.? Please reply to me ..sir

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому +1

      Donno condition me possible h ID run. Coupled condition me Standstill mode select karna hota hai

  • @kavyamohan7973
    @kavyamohan7973 2 роки тому +1

    Sir plz give some more videos on abb 550 drive ..so that it b helpful for us

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому

      Few more videos available on my channel, pl do check ✔️

  • @basant05164
    @basant05164 3 роки тому +2

    Presentation is very good. Just use a microphone to improve the sound quality.

  • @vinodmusicprogamer9503
    @vinodmusicprogamer9503 3 роки тому +1

    Nicely explained 👍

  • @domdomgin
    @domdomgin Рік тому +1

    Hello how to run this in remote mode.I need to set this on timer mode.Thank you.

    • @bishantkumar12589
      @bishantkumar12589  Рік тому

      ID run can not be done on Remote Mode as per my experience

  • @mohammadgulphamahmad594
    @mohammadgulphamahmad594 Місяць тому +1

    Off karne ke baad v kuch kuch frequency me run karts h kya

    • @bishantkumar12589
      @bishantkumar12589  Місяць тому

      15-20 seconds tak karta hai. Ramp down time kahate hai use

    • @mohammadgulphamahmad594
      @mohammadgulphamahmad594 Місяць тому

      @@bishantkumar12589 bms se off karte h but vfd me 0.6 hz rahta hi h esliye motor chalta rahta h

    • @mohammadgulphamahmad594
      @mohammadgulphamahmad594 Місяць тому

      @@bishantkumar12589 esliye kya koi programing miss h ya kuch aur

  • @rohitdewangan7129
    @rohitdewangan7129 4 роки тому

    Bhut achha video hai sir

  • @srinivasulupeddapasupala2335
    @srinivasulupeddapasupala2335 2 роки тому +1

    Good information

  • @shivchandrachaudhary5900
    @shivchandrachaudhary5900 7 місяців тому +1

    Abb550 ko 3phese 230v se start kar sakte hai?

  • @sumits_shetty
    @sumits_shetty Рік тому +1

    Ye quick commissioning ke parameters koi bhi batayega ..dig input outputs, mode of frequency setoing dig inputs parameters bhi batao

  • @amardeepekka-jm3ke
    @amardeepekka-jm3ke Рік тому +1

    How to find igbt phase missing through ABB drive window.

    • @bishantkumar12589
      @bishantkumar12589  Рік тому

      I'm not sure about it, but I think CPD will display phase loss fault in that case

  • @asesstv688
    @asesstv688 3 роки тому +2

    Sir abb vfd ko Solar voltage ⚡ kitny se kitny tk de sakty hen

  • @kamaltexno
    @kamaltexno 9 місяців тому +1

    hello sir I have an Abb ACS550 series. It gives error f0026. what should i do Is it possible to reset this error?

    • @bishantkumar12589
      @bishantkumar12589  9 місяців тому

      It's drive error. Internal Fault, configuration block drive id is not valid brother. You need to contact your ABB service engineer

    • @kamaltexno
      @kamaltexno 9 місяців тому

      @@bishantkumar12589 sir i am electronics engineer. I want to know from you whether I should change the ID card or solve the program problem in the software section? what advice do you think?

  • @pramodsahoo1375
    @pramodsahoo1375 3 роки тому +1

    Sir, acs 800 drive me 99 group me motor data set kardia but jab id run kia to no motor data show karta he drive, kya problem ho sakta he thoda bataiye sir

    • @bishantkumar12589
      @bishantkumar12589  3 роки тому

      Ek baar program upload kariye

    • @bishantkumar12589
      @bishantkumar12589  3 роки тому

      Nai too parameters load karne k baad, save kariye. Parameter number main dekh k batata hu

  • @jasvirsinghrathore4107
    @jasvirsinghrathore4107 3 роки тому +1

    Sir I have VFD ABB make model Acs550 fault F0101 what should I do so that fault may be rectify

    • @bishantkumar12589
      @bishantkumar12589  3 роки тому

      Sir. It's SYSTEM ERROR. you have to contact the service engineer of ABB

    • @jasvirsinghrathore4107
      @jasvirsinghrathore4107 3 роки тому +1

      @@bishantkumar12589 please help me to contact service engineer

  • @netkumarpandey8876
    @netkumarpandey8876 4 роки тому +1

    Very good sir

  • @jkj1459
    @jkj1459 4 роки тому +1

    Motor de couple nahi karsakthe hai tho konsa setting

  • @akcreation1792
    @akcreation1792 4 роки тому +1

    Sir aap ek video ht motor pe bnaye

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      Okay bhai. Waise Maine ek video Dala hai, Lt n Ht motor k difference pe. Aap dekh sakte h

  • @DHARMENDRAKUMARSHARMA-i6g
    @DHARMENDRAKUMARSHARMA-i6g Рік тому +1

    Driveb me light nhi a rhi hai

  • @komitkumar3033
    @komitkumar3033 Рік тому

    Halo sir,
    Sir 22 kw abb ke vfd hi, usme vfd runing tim me vfd automatic output dena band kr deti hi. Fir 10 minutes ke bad chalne lagti hi.
    Na he koi alram aa rha hai, na he koi tripping indication.
    Out put voltage 412, 412,411
    Feq 42 hz high set point.
    Ples help me sir

    • @bishantkumar12589
      @bishantkumar12589  Рік тому

      Running condition ka voltage h ye sab .?

    • @bishantkumar12589
      @bishantkumar12589  Рік тому

      Ek baar local me run kar k chhod do bhai. Observe karo esa hota h ya nai

    • @komitkumar3033
      @komitkumar3033 Рік тому

      @@bishantkumar12589 ok sir

    • @komitkumar3033
      @komitkumar3033 Рік тому

      @@bishantkumar12589 ha ji

    • @komitkumar3033
      @komitkumar3033 Рік тому

      Jb vfd remote mode me running hoti tabi yhi problem ati hai,
      All perameter, amp, feq is ok

  • @rajindersingh872
    @rajindersingh872 2 роки тому +1

    Sir please tell me ABB drive 550 how can change acceleration and deceleration time

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому

      Paaji. Pl go through this link ... All important parameters are covered for ACS 550 drive

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому

      ua-cam.com/video/vBOuVZ3V7RY/v-deo.html

  • @DeepakKumar-lo3yw
    @DeepakKumar-lo3yw 3 роки тому +1

    Good sir

  • @rohitdewangan7129
    @rohitdewangan7129 4 роки тому +2

    ACS 550 all setting pe video banaiye sir

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому +1

      Okay dost. Banata hu jaldi hi.
      Pl support channel.

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому +1

      dost actually, total 99 parameters hote ahi. aane wale videos me main jo imp parameters hai uspe video daal dunga, pl wait for sometime

  • @bismillahelectronicsindust9824
    @bismillahelectronicsindust9824 3 роки тому +1

    Sir inverter drive ke repiring pr b video opload kary thanks

  • @waveautomation1686
    @waveautomation1686 4 роки тому +1

    dear sir i have abb drive 2.2 kw 3phase motor run position many times stop There is no error i change bush buttons relay with bas and also drive but still problems

  • @gautamgujaria5960
    @gautamgujaria5960 3 роки тому +1

    Nice

  • @sudalaimuthup
    @sudalaimuthup 4 роки тому +1

    How to connect acs550 to laptop?
    Which one software is option?

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому +1

      Well sorry about this, we hardly used laptop for program configuration in ABB ACS drives yet. So not having proper idea. With CDP/HMI we do program configuration

    • @sudalaimuthup
      @sudalaimuthup 4 роки тому +1

      @@bishantkumar12589 thanks for your quick response

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому +1

      @@sudalaimuthup ur wlcm. Pl support d channel.

    • @preetparikh9549
      @preetparikh9549 3 роки тому

      You can connect drive panel to USB to laptop. But this is normal panel. You can't do with this one.
      After connection you can Install drive composer pro or entry and can access full drive from it.

    • @bch2780
      @bch2780 Рік тому

      Drive windows light2

  • @kamaltexno
    @kamaltexno 9 місяців тому +1

    please give me some information.

  • @parmodbist414
    @parmodbist414 Рік тому +1

    I have issues VFD ABB2016 alarm

  • @dharanipatel195
    @dharanipatel195 2 роки тому +1

    Display kaha mileage sir ..

  • @tomer5697
    @tomer5697 2 роки тому +1

    Sir ACS550 ABB VFD is showing F0001 how to fixed.

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому +1

      Maximum current limit too low. Check settings of parameters 99.06
      Motor nominal current and 30.17
      Maximum current. Make sure that
      30.17 > 99.06.
      Check that the drive is dimensioned
      correctly according to the motor.

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому +1

      Please check the solution sr

  • @mohammadrafiq4420
    @mohammadrafiq4420 7 місяців тому +1

    Sir vvfd main faut A50011 hain

    • @bishantkumar12589
      @bishantkumar12589  7 місяців тому

      Esa koi alarm nai h sir.

    • @bishantkumar12589
      @bishantkumar12589  7 місяців тому

      A5011 hai - drive kisi dusre source se control ho raha h, wo check Karo aap

  • @chighalimohamedmahmoud7761
    @chighalimohamedmahmoud7761 3 роки тому +1

    How can change the direction of motor

  • @kishorekrrishe
    @kishorekrrishe 2 роки тому +1

    whats purpose of id run?

  • @ganpatsinghrisingperson4194
    @ganpatsinghrisingperson4194 2 місяці тому +1

    Ye kitne kw ki hai

  • @indianmixtubevlogs
    @indianmixtubevlogs 2 роки тому +1

    Vdf 550fault 0021 aa raha hai solution bataye sir

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому

      It's - drive's internal fault. Current measurement is out of range. Talk to your service provider ABB

  • @avinashkhindkar1869
    @avinashkhindkar1869 4 роки тому +1

    Moter Rpm change 50hz video bana degiye

  • @bestmusic3209
    @bestmusic3209 2 роки тому +1

    Sir isme A 2010 dikha raha hai kiya kare

  • @9866sree
    @9866sree 2 роки тому +1

    How to see load

  • @danielkerketta2179
    @danielkerketta2179 2 роки тому +1

    Very good sir apka chahiye

  • @maruthikonnari8523
    @maruthikonnari8523 4 роки тому +1

    👌👌👍👍

  • @thechampvishnu1518
    @thechampvishnu1518 6 місяців тому +1

    Please help me to fix A2004 error code. DIR lock

    • @bishantkumar12589
      @bishantkumar12589  6 місяців тому

      What's the problem? Direction not changing or. Drive tripping?

    • @thechampvishnu1518
      @thechampvishnu1518 6 місяців тому

      @@bishantkumar12589 drive not starting

  • @makmalnadeem1133
    @makmalnadeem1133 2 роки тому

    Sir abb vfd ky fault history reset kasy kry gy

    • @bishantkumar12589
      @bishantkumar12589  Рік тому

      HMI se hona muskil hai, aap laptop connect kar k delete kar sakte hai. Pl contact service engineer

  • @gurnamsingh8952
    @gurnamsingh8952 4 роки тому +1

    Why need ID run..?? explain..

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      ua-cam.com/video/0amyra50Bg0/v-deo.html

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      Please watch this video

    • @bch2780
      @bch2780 Рік тому

      Calculate motor characteristics for higher accuracy control motor , especially vector control mode

  • @इंजीनियरसंजूयादव

    I'd runs Ka mean kya hota h

  • @waqarhussain729
    @waqarhussain729 3 роки тому

    Sir display ACS 355 Ka hy, kindly change kr ly

    • @bishantkumar12589
      @bishantkumar12589  3 роки тому

      Nai bhai. ACS 550 ka hi hai. Donno ka same ho sakta hai

    • @waqarhussain729
      @waqarhussain729 3 роки тому

      @@bishantkumar12589 Display fitting same hy but it's ACS 355 not ACS 550 , agr aap k pass ACS550 original panel display hy to aap ko difference pta chal jy ga

  • @mangaldev190
    @mangaldev190 2 роки тому +1

    I'd run nhi ho rha h fault 0011 aa rha h

    • @bishantkumar12589
      @bishantkumar12589  2 роки тому

      ID run complete nai ho raha hai.
      Check for and correct -
      1. Motor connection
      2. Motor parameter - 9905 to 9909

  • @rohitdewangan7129
    @rohitdewangan7129 4 роки тому +1

    acs550 vfd me last falt kaise dekhe

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      Main uspe VIDEO upload karta hu

    • @jasvirsinghrathore4107
      @jasvirsinghrathore4107 3 роки тому

      Jitne bhi fault code hain ABB Frequency Drive model ACS 550 mein sabki list bhejta hoon apna mob. No dena

    • @jasvirsinghrathore4107
      @jasvirsinghrathore4107 3 роки тому

      Jitne bhi fault code hain ABB Frequency Drive model ACS 550 mein sabki list bhejta hoon apna mob. No dena

  • @amitkoni92
    @amitkoni92 4 роки тому +1

    DCS 800 Ka ek video banaye I'd run Kise hoga

  • @ranjitpanditvlog3415
    @ranjitpanditvlog3415 2 роки тому

    Acs 560 parameters 2 wire and 3 wire

  • @consoultechnical1688
    @consoultechnical1688 3 роки тому +1

    Sir ac VFD mein torque ko kitne mein set karna chahiye.

    • @bishantkumar12589
      @bishantkumar12589  3 роки тому +1

      Minimum = - 300
      Maximus = + 300
      Parameter 24 in ABB ACS 850
      General settings

  • @bittuverma02552
    @bittuverma02552 4 роки тому +1

    Sar Ji ek drive mein model acs150 porat s nhi calri number 8930936009 aap bataiye kis parameter ki ismein problem hai

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      Okay bhai. Check kar k msg karta hu asap

    • @bittuverma02552
      @bittuverma02552 4 роки тому +1

      @@bishantkumar12589 kya hua ser ji

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      @@bittuverma02552 bhai. Check Parameter : 16 - SYSTEM Controls. 1606 - set to 0 for local Control

    • @bittuverma02552
      @bittuverma02552 4 роки тому

      Shola Shola mein jakar zero kar diya hai per fir bhi nahin chala

    • @bishantkumar12589
      @bishantkumar12589  4 роки тому

      @@bittuverma02552 remote se run karna h ya drive k panel se ?

  • @sureshParmar-ei8zk
    @sureshParmar-ei8zk Рік тому +1

    F0022folt

    • @bishantkumar12589
      @bishantkumar12589  Рік тому

      FAULT - SUPPLY PHASE
      SOLUTION - Ripple voltage in the DC link is too high. Check for and correct:
      • Missing mains phase.
      • Blown fuse.

  • @praveenk5019
    @praveenk5019 4 роки тому

    Good sir