Troubleshooting the Pressure Switch in a Gas Furnace!

Поділитися
Вставка
  • Опубліковано 2 лис 2024

КОМЕНТАРІ • 57

  • @acservicetechchannel
    @acservicetechchannel  6 років тому +2

    Tool List- www.amazon.com/shop/acservicetech
    Support- www.patreon.com/acservicetech
    For those that are looking for the tools used in the videos: (Linked Below)
    UEI Digital Dual Manometer- amzn.to/2CWC6BD
    Fieldpiece SDMN6 Dual Pressure Testing Manometer with Pump-amzn.to/2jyK5Ka
    UEI DL479 Multimeter with temp sensor- amzn.to/2jtsUbJ
    3/16" x 3/16" x 3/16" brass barbed tee- amzn.to/2INSRhQ
    1/8" NPTF x 3/16" barb fitting for reading wc pressure- amzn.to/2G563Bq
    Supco Universal Adjustable Pressure Switch -.01wc -10.0wc amzn.to/2G1y0py
    Supco Magnet Jumpers amzn.to/2gS4h6z
    2 pairs of alligator clips- amzn.to/2CtIL5z
    Here is the Link for the Yellow Jacket Refrigerant Manifold Gauge Set used in the videos amzn.to/2aenwTq
    Here is a link to Refrigerant hoses with valves used in the videos amzn.to/2aBumVI
    Here is a link for RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
    Here is the link to the Appion Valve Core Removal Tool- amzn.to/2uYr8WL
    Here is the link for the Ratcheting Service Wrench amzn.to/2dGV4Nh
    Here is the link to the CPS Vacuum Micron Gauge- amzn.to/2v1nM3O
    Here is the Link to the Appion Blue 3/8" to 1/4" Vacuum Hose- amzn.to/2uYlVyc
    Here is the Link to the Appion Red 3/8" to 1/4" Vacuum Hose- amzn.to/2uYg6Ro
    Here is the link to the Yellow Jacket 1/4" by 1/4" heavy duty hose straight- amzn.to/2umtcod
    Here is the link to the pack of 25 C&D valve cores- amzn.to/2J1lurm
    Here is the link for the C&D Valve Core Wrench, Container, and 3 valve cores- amzn.to/2EVGkps
    Other tool links can be found in the video description section.
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech
    All of the ACSERVICETECH Playlists- ua-cam.com/channels/OZR-1IqsAer9wzlvFgb4mA.htmlplaylists?view_as=public

  • @nurfetalic205
    @nurfetalic205 6 років тому +15

    For new technicians this is the gentleman that you have to pay attention it will teach you all kinds of stuff and believe me you got to have a little patient and down the road you going to be just fine he's got a lot of knowledge to share with you guys.
    Craig well done as allways.

    • @acservicetechchannel
      @acservicetechchannel  6 років тому

      Thanks a lot Nurfet Alic!

    • @truthfiend6909
      @truthfiend6909 3 роки тому

      not only for the new techs , this channel is the best HVAC channel there is imo...ve been in the trade for more than a decade and i'm still learnin new things watching his vids

  • @drifter436
    @drifter436 6 років тому +12

    You are the best on UA-cam sir. You have the gift to teach. Thank you for all these videos , they are a huge help.

  • @Digitaldendo
    @Digitaldendo 6 років тому +2

    Just getting started in the industry with 2 levels of school, this channel is great Thank you.

  • @chriscooper9729
    @chriscooper9729 6 років тому +2

    Thank you very much. I'm a new technician I need all the help I can get your videos or not just informative but their inspirational as well.

  • @whitesheatingairappliancer7101
    @whitesheatingairappliancer7101 6 років тому +1

    You are a great teacher. I will use this setup for troubleshooting. Thank you for the video.

  • @stephens1950
    @stephens1950 3 роки тому +1

    Just replaced a pressure that was BAD. The replacement just gave me problems after a week of working. Thoughts?

  • @bills6946
    @bills6946 Рік тому +2

    You can tell an instructor from a UA-cam service Technician. A technician will usually slip in something bad about Goodman, because Goodman doesn’t pay companies incentives like some other brands. An instructor will teach you that if you install a system correctly, they are all good

    • @burg5556
      @burg5556 Рік тому

      Arrived at service call.
      Wiped top cabinet with a rag.
      Conclusion: its goodman

  • @fazesenso2864
    @fazesenso2864 9 місяців тому

    Hello! I noticed that you had the positive port of the manometer hooked to the - Side of the switch (more of a vacuum ) . And the negative port of the manometer hooked to the + side of the switch that connects to the burner box which is atmospheric. For ur differential. Is that a mistake ? Or does it not matter ??? I’m a new technician out of school and I am constantly running into pressure switch issues and I am trying to really grasp what readings I’m looking at and what readings I should have 100%. So I am not just guessing

  • @ejohnfall
    @ejohnfall 6 років тому +1

    Thanks again perfect time it started to get cold

  • @johnsonvideos1450
    @johnsonvideos1450 25 днів тому

    hi i have the 24v going from pressure switch back to control board but still not moving to next sequence i think i have abad board?

  • @caseyfike226
    @caseyfike226 2 роки тому

    Thank you for your great content & sharing your expertise with us. But 1 question I have that I've wondered is, say the furnace goes through its sequence and starts heating. What if the pressure switch opens back up after it's already started heating, will the system shut back down or will it wait until next start up cycle. Thank you so much again.

  • @davidhazas7162
    @davidhazas7162 2 роки тому

    I've found the water column rating for the pressure switchs on the actual schematic in small writing in some cases.

  • @Rezcat-y6r
    @Rezcat-y6r 5 років тому

    Hey my friend. I’m still going to purchase a dual manometer but without it the furnace does everything. Cfm on, pressure switch closed, HSI lit, burners on with a flame sensor, then off 4-7 seconds.

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Sounds like flame rectification, board or pressure switch but you would need to test each function individually, thanks

  • @Matthew-jr1xr
    @Matthew-jr1xr Рік тому

    Im wondering why on a new install why sometimes priming the drain trap is needed so the pressure switch makes but then the same issue is present when the trap is clogged..🤔

  • @ghleader2179
    @ghleader2179 6 років тому +2

    Thnx for your video, i love your Chanel.

  • @gilbertopatino2616
    @gilbertopatino2616 6 років тому +1

    Thank you very much for another great video 👍👍👍👍🇺🇸

  • @johnaries9301
    @johnaries9301 Рік тому

    Can you wire a pressure switch backwards?

  • @mark.r8900
    @mark.r8900 6 років тому +1

    hi, so on the + side of the pressure switch the vacuum is created through the heat exchanger? is this correct? thanks.

  • @robcarnaroli269
    @robcarnaroli269 6 років тому +5

    Great video but now I'm dying to know what was the blockage!

  • @benkuxhouse787
    @benkuxhouse787 6 років тому +1

    Great video. I've been doing HVAC for a 30 years 33 to be exact and have never had a really good procedure on very tough pressure switch problems. I work for a school district now and don't have to deal with it as much but we still have some furnaces there. How did you figure out it was the induction tube by your pressures that you were reading? Cuz they both right about the same. What I've done in the past is I've just disconnected both the supply in the exhaust and see if it would come on to see if it is the exhaust or intake piping. Real good video and I know it's going to help me in the future but how did you figure that one out by just looking at those pressures that it was the intake?

    • @acservicetechchannel
      @acservicetechchannel  6 років тому

      You are right, I just opened up the combustion air inlet and the pressure changed. Also, when the inducer is high enough to allow the pressure switch to close and the intake is just as high then you know the problem is on the intake or heat exchanger side, thanks

    • @benkuxhouse787
      @benkuxhouse787 6 років тому +1

      @@acservicetechchannel how would you know if you had a problem with the heat exchanger looking at those readings?

    • @greghuber9773
      @greghuber9773 Рік тому

      If you can’t suck right , there’s not much air to push ! Like if you put a box fan against a wall , you won’t get much air flow on the outlet !

  • @BoffinGrusky
    @BoffinGrusky 6 років тому +1

    Well done!

  • @chrisswofford5757
    @chrisswofford5757 2 роки тому

    Could you do a video about correctly hooking up manometer hoses in line with pressure switches? I always get mixed up.

    • @acservicetechchannel
      @acservicetechchannel  2 роки тому

      look up "acservicetech pressure switch" and "gas furnace component history"

  • @geojor
    @geojor 6 років тому +1

    enjoyable to watch ...

  • @CheiithooCat
    @CheiithooCat 6 років тому +1

    Awesome...

  • @madurasenju2015
    @madurasenju2015 5 років тому

    One small questions . I get the pressure switch hose that runs directly to the inducer . But right here I see it hooks up to the gas valve then goes to the burners to just have a hoe inside the cage burners . ? Why ?! Can you please explain throughly . Thank u

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      That is so that the atmospheric pressure at the burners remain the same as at the gas valve so there is no problems with the flame or at the pressure switch!

  • @clintglasgow5633
    @clintglasgow5633 6 років тому +1

    👍

  • @الجمهوريةالشيطانيةراعيةللارهاب

    Can this furnace be used for a down flow application ?

  • @heatncool
    @heatncool 6 років тому +1

    Sweet. Look forward to your videos! I get to be the first comment 😋😀