Generator Voltage Problems in Urdu / Hindi: Causes and Remedies. Overvoltage and Undervoltage Faults

Поділитися
Вставка
  • Опубліковано 8 січ 2025

КОМЕНТАРІ • 97

  • @muhammadshoaibkhan4750
    @muhammadshoaibkhan4750 4 роки тому +11

    Im working in cement factory (power house) in ksa today i face this problem one DG over voltage ,suddenly i see the your vlog ,and fixed the problem
    Thank you asad

  • @sajeewanchoudhary7523
    @sajeewanchoudhary7523 3 роки тому +2

    Very good suggestion,sir.

  • @axomiya9799
    @axomiya9799 2 роки тому

    Nice video.you are talented men.

  • @jpsahni1338
    @jpsahni1338 3 роки тому

    Full details type of load video banaye, good video thank you so much

  • @syyednoor277
    @syyednoor277 4 роки тому +4

    Masha Allah.. 🤲🤲🤲

  • @kidsactivites6196
    @kidsactivites6196 4 роки тому +1

    Masha allah 🤲🤲

  • @electricalTechnician412
    @electricalTechnician412 2 роки тому +1

    السلام عليكم ورحمة الله
    Can you please make a video on floating Neutral and bonded Neutral?

  • @Shahlazaidi7
    @Shahlazaidi7 4 роки тому +3

    Mashaallah

  • @kewalsingh9934
    @kewalsingh9934 2 роки тому

    Nice sir ji thanks🌹🌹🌹🌹

  • @wazirmuhammad836
    @wazirmuhammad836 4 роки тому +2

    beautifull...

  • @KananBehera-q5k
    @KananBehera-q5k 2 місяці тому

    Thank you sir

  • @electricalTechnician412
    @electricalTechnician412 3 роки тому

    السلام عليكم
    Asad bi kya haal ha. Mery pass 150 kva ka DG ha . Brand new .just kay output voltage 220 /380 set ha Company ki target say . Lekin must 230 /400 chahiye . Iss ka ka hal ha . Kya AVR say 10 volt increase kar sakty ha koi mushkel to ni

  • @ramzanchramzanch6344
    @ramzanchramzanch6344 4 роки тому +2

    Vry niceeee

  • @59907
    @59907 Рік тому

    Good sir

  • @ahmedtariq6289
    @ahmedtariq6289 4 роки тому +2

    good

  • @er.karmvirchauhan7861
    @er.karmvirchauhan7861 4 роки тому +1

    Dear sir, 15 KVA Cummins Powerica Ka DG hi 560 V AC phase to phase me as rha hi aur alternator heat ho rha hi kya problem hi please give me reply urgently

    • @AsadElectrical
      @AsadElectrical  4 роки тому

      AVR se voltage ki setting check karain warna windings me problem lagra he

  • @arvindsinghrana1607
    @arvindsinghrana1607 2 роки тому +1

    I have a Volvo D7AT series DG..LO temp FW temp is showing wrong on panel..i have checked sensor, relay, fuse but not satisfactory..pls give me suggestions

    • @AsadElectrical
      @AsadElectrical  2 роки тому

      Please make sure wiring connection are in order

    • @arvindsinghrana1607
      @arvindsinghrana1607 2 роки тому

      @@AsadElectrical checked all are in proper order..

    • @AsadElectrical
      @AsadElectrical  2 роки тому

      @@arvindsinghrana1607 please tell me whats wrong in reading

    • @arvindsinghrana1607
      @arvindsinghrana1607 2 роки тому

      @@AsadElectrical when i am measuring through infrared gun LO Temp is 78deg, FWT is 68deg, LO pressure is .40MPA(in pressure gauge), Voltage is also 25V(12V+12V)....but on panel LO Temp is 91deg, FWT is 83deg and pressure is .45MPA,VOLTAGE is also 30Volt...

    • @AsadElectrical
      @AsadElectrical  2 роки тому

      @@arvindsinghrana1607 actually sensor readings can't be exact match with infrared because sensor is located on close circuit .

  • @MuhammadRizwan-cu1dt
    @MuhammadRizwan-cu1dt 4 роки тому +1

    Brother 50 Hz or 60 Hz difference p video bnaya.thanks

    • @AsadElectrical
      @AsadElectrical  4 роки тому

      Please check below links:
      ua-cam.com/video/HX6cfuliJYw/v-deo.html
      ua-cam.com/video/3GcWd1BgRD0/v-deo.html
      ua-cam.com/video/ffk2CIZTL4Q/v-deo.html

  • @ShabirAhmed-nv2ez
    @ShabirAhmed-nv2ez 2 роки тому

    hi . mere pas jasco ka chota 3000 watt wala generator he . us main b voltage drop wala problem he. load dalany pr voltage drop hotay hain . us ka governor ok he avr b change kr k dekh Liya he . engine b overhaul kr Liya he . lekin problem nhi thek ho rhi . or small electronic appliances like charger led bulb b khrab hojay hain . plz kya apko koi idea he k aesa kyun je

    • @AsadElectrical
      @AsadElectrical  2 роки тому

      Agar load pe speed drop hogi to low frequency ki waja se bhi equipment kharab hongay. Agar speed constant he aur voltage drop hotay hen to load suddenly nhi apply krain, gradually increase krain

  • @mrswati374
    @mrswati374 3 роки тому +1

    Asad Bhai mere pas jesco 2.5kw ka genrator he aj mene genrator pe istri chalayi kuch der chalne k bad istri burn hoke kharab hogay 4 bulb be jal gay . Mene foran genrator ka load off Kiya or genrator k voltage 100 show horahay hen plz btayn is me Kiya problem hogay he plz reply me

    • @AsadElectrical
      @AsadElectrical  3 роки тому

      100 Volt low hen. Low voltage ki waja se apkay equipment kharab hogye. AVR replace krna parega ya phir windings test hoga

    • @pramodpramodkumarswain43
      @pramodpramodkumarswain43 3 роки тому

      Jeise bataye ho kabhi bhi low voltage ke wajah se iron ,aur bulb jalte he??wrong information.dena band karo, sahi fault ke bare me jankari batao

  • @muhammadshoaibkhan4750
    @muhammadshoaibkhan4750 4 роки тому +2

    Long live brother

  • @malikfaisal8295
    @malikfaisal8295 Рік тому

    Bhi hamra 500 KVA ka Gen Auto py over voltage ka alram deta ga ATS sy agr manual kro to theek chalta ha

    • @AsadElectrical
      @AsadElectrical  Рік тому

      Voltage potentiometer ATS panel pe he ya Generator pe?

    • @malikfaisal8295
      @malikfaisal8295 Рік тому

      @@AsadElectrical Asad bhai jab Gen locked out ka alarm ata sath over voltage ka b baki usi time manual kr k normal voltage b stable han

  • @mahenkowsivlogs2518
    @mahenkowsivlogs2518 2 роки тому

    Hi sir my problem is dg starting is good 380vac but put load after voltage is high 500vac what problem sir

  • @TalhaAbid-e7m
    @TalhaAbid-e7m 10 місяців тому

  • @tanveermalik7371
    @tanveermalik7371 4 роки тому +1

    hi bro mera alternator load dalne par engine ko bahut load deta he kya problem ho sakti he

    • @AsadElectrical
      @AsadElectrical  4 роки тому

      please check full load current of Alternator and power factor of load.

  • @RupeshKumar-vk5ro
    @RupeshKumar-vk5ro 3 роки тому +1

    Low voltage ka batay sar

  • @farheensuhail454
    @farheensuhail454 3 роки тому

    Assalamualaikum bhai Maine 380volt se 220 volt 3 phase banaya hai tab se gen under voltage display hoko band hojaray eska saluotion batao

    • @AsadElectrical
      @AsadElectrical  3 роки тому

      Panel k undervoltage setpoint ko bhi km karna parega.

  • @arvindsinghrana1607
    @arvindsinghrana1607 3 роки тому

    I have volvo penta 72DK genset.. frequency is getting down and up..any input?

    • @AsadElectrical
      @AsadElectrical  3 роки тому +1

      check engine speed. is it constant ?

    • @arvindsinghrana1607
      @arvindsinghrana1607 3 роки тому

      @@AsadElectrical RPM is also fluctuating...we changed fuel pump with new one,also changed fuel filters but nothing worked..

    • @AsadElectrical
      @AsadElectrical  3 роки тому +1

      @@arvindsinghrana1607 you should check injectors, pump, speed sensor etc..step by step

    • @AsadElectrical
      @AsadElectrical  3 роки тому

      @@arvindsinghrana1607 Frequency depend on RPM. so try to constant engine rpm

  • @jalalmondal1103
    @jalalmondal1103 3 роки тому +1

    sir avr connection give with motor winding to avr practically. outher witch I can gate your m.b no..sir

  • @santhoshpaul382
    @santhoshpaul382 2 роки тому

    Hi sir our Perkins generator stopping due to over voltage alarm. Phase to phase is 380 v but Line to phase is getting 270 v but we need 220 v ... How to adjust

    • @AsadElectrical
      @AsadElectrical  2 роки тому

      Please check all 3 phases voltage properly with neutral and let me know the values of all 3 phases.

    • @alamzeb9577
      @alamzeb9577 Рік тому

      ​​@@AsadElectricalap ka wattsap number chaheye...fg wilson generator k bary mai

  • @dildartechnician3420
    @dildartechnician3420 10 місяців тому

    Sir 50kva ka generator hai load pr volt zayda krta hai narmol 401 volt module pr sho hote hai but load pr 467v ho jate hai Kya masla ho ga

  • @bellalhossain3965
    @bellalhossain3965 2 роки тому

    How to came over voltage and voltage up down please tell me

  • @shrikrishnaraibole735
    @shrikrishnaraibole735 3 роки тому

    Sir, 1010 kva ke do genset synchronised parallel karate hi dono amp me load show karte hai, please solution bataye, or please give your cant no

  • @AbdulRehman-ii5lj
    @AbdulRehman-ii5lj 4 роки тому +1

    Salam 190 volts kam hen ya normal hen

  • @mechanicalandelectricaleng9649
    @mechanicalandelectricaleng9649 4 місяці тому

    Out of sync ka erore q aita ha

  • @masumgazi8228
    @masumgazi8228 4 роки тому +1

    Potentiometer problem

  • @haseenakhter6815
    @haseenakhter6815 3 роки тому

    Prectcal bataiye bhai

  • @shivanandasingha
    @shivanandasingha 3 роки тому +1

    750 kV ka parkince DG us Mai achanak phase to phase 520 V araha tha AVR Naya lagake minimum Mai setting Kiya Lekin 437 volt se niche Nehi Ara hai phir kya kare Lekin tin char bar 415 volt diya

    • @AsadElectrical
      @AsadElectrical  3 роки тому +1

      Excitor aur main windings ko megger test karain.

    • @shivanandasingha
      @shivanandasingha 3 роки тому

      Sir stater ka Megger Kiya Sahi hai Lekin stater garam horaha hai Bina laod ka

    • @shivanandasingha
      @shivanandasingha 3 роки тому

      Sir Paheli 3 se 4 bar start karenge us samay 415 volt deta hai bad Mai volt 436 hota hai

    • @AsadElectrical
      @AsadElectrical  3 роки тому

      @@shivanandasingha winding problem he

  • @NasirKhan-nm2kp
    @NasirKhan-nm2kp 3 роки тому

    Salam Bhai Cummins Generator ha hrs show nahi hota only 3.5 hr ata ha

  • @amitsharma1957
    @amitsharma1957 3 роки тому +1

    Namaskar sir ji harmonic ki wajah se DG ki VOLTAGE up and down ho rahi hai to kya kiya jaaye sir ji pls bataye urgent hai sir ji aur DG set 180 kva ka hai aur printing machine par laga hua hai printing machine ki motor dc 33 kw ki hai pls bataye urgent hai sir ji

    • @AsadElectrical
      @AsadElectrical  3 роки тому

      Motor ki speed ko slowly increase krna parega takay variation minimize hojaye. Motor voltage ?

    • @amitsharma1957
      @amitsharma1957 3 роки тому

      @@AsadElectrical 95-380dc

  • @aurangzaibaurangzaib1756
    @aurangzaibaurangzaib1756 Рік тому

    B practical par video p

  • @sajidaltaf989
    @sajidaltaf989 3 місяці тому

    Hi sir

  • @sivauml1739
    @sivauml1739 2 роки тому

    Gun under voltage

  • @haseenakhter6815
    @haseenakhter6815 3 роки тому

    Issue air bhi utuber dekhege

  • @saleembinramzan75
    @saleembinramzan75 2 роки тому

    No 5 ho to kia Kary in uv

  • @bachakhan7393
    @bachakhan7393 2 роки тому

    Generator start ho ker under voltig alarm de ker off ho jata hai

  • @Najimu384
    @Najimu384 4 роки тому +1

    Assalamualaikum air conditioning unit main use hota hai temperature sensor ki bari main video chahie.

  • @azharansari4713
    @azharansari4713 4 роки тому

    Salam asad bhai generator 300 volte de raha hai avr kharab ho raha hai bar bar

    • @AsadElectrical
      @AsadElectrical  4 роки тому

      Wsalam. 300 volt ph to ph he ya ph to neutral ?

    • @azharansari4713
      @azharansari4713 4 роки тому

      Apka whatsupp number mil sakta hai uspe thek se bata dunga ya mera number lelen ap ispe reply karden plzz
      03152957066

    • @AsadElectrical
      @AsadElectrical  4 роки тому

      @@azharansari4713 Actually i am not using whatsap because of time shortage, you can send me email or you can ask in comments.
      asad89electrical@gmail.com

    • @azharansari4713
      @azharansari4713 4 роки тому

      Masla ye ke generator over voltage de raha hai kal ta sahi tha aj ye masla hua avr kharab hogaya new lagaya jab bhi 300 voltage de raha tha mene generator band kardia warna avr kharab ho jata avr garam hogaya tha bohot

    • @AsadElectrical
      @AsadElectrical  4 роки тому

      @@azharansari4713 Ap AVR se excitor k wire (f1 f2) remove kr k generator chala k dekhain kitnay voltage arhay hen. Aur potentiometer ko minimum par kardain. phir AvR connect kar k dekhain.

  • @jeetendrakumar3704
    @jeetendrakumar3704 3 роки тому +1

    Aapka number jaega sir