120V from both 240V single phase and 208V 3 phase systems?

Поділитися
Вставка
  • Опубліковано 1 жов 2024
  • Hello everyone, welcome to At-Man Unlimited. Last time I took a math class 120 + 120 did not equal 208! So what gives? How can you get 120V from a 240V residential system AND a 208V 3 phase commercial systems? How can that possibly work? Let’s find out!
    If you have any questions please feel free to comment or email me, AtManUnlimited@gmail.com
    If you would like to support the channel please visit our Patreon page
    patreon.com/us...

КОМЕНТАРІ • 271

  • @KevinCoop1
    @KevinCoop1 5 років тому +2

    I do not understand where people started coming up with the term "split phase" and 180 degrees out of phase for single phase. A single phase 120/240 volt system has a single coil winding inside with a center of winding connection used as neutral. The number of windings sets voltage. So as the magnetic flux moves across the coils in the transformer secondary coils you get either 120 line to neutral or ground if grounded and 240 volts line to line. The sine waves are the exact same point in time just different voltages. By saying you add 120 v to 120 v is incorrect. L1 to L2 just is 240 v.the sine waves shown above and below the horizontal line at the same time are incorrect. Again single phase, one sine wave at one point in time.

    • @mmaad2165
      @mmaad2165 5 років тому

      Why the top wire of the top windings is 120v and the bottom wire of the second windings is 120v??
      If what you are saying is right the bottom line of the second windings has to be 0v

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому

      Kevin, it all depends on how you look at it and what your reference is. Most people just see the neutral and two hot lines. They don't understand how transformers are wired and constructed. If you put both legs referenced to neutral on a two channel scope, you will get two sine waves 180 degrees out of phase. If you add a math channel to add the two channels together, you get a 240V rms signal.

    • @KevinCoop1
      @KevinCoop1 5 років тому +1

      At-Man Unlimited Machining If you put one 120 volt RMS signal on your scope, it is a simple sine wave. Correct? If you connect scope to L1 to L2 you get a simple sine wave with basically twice the amplitude. Correct? If you connect to 2 120 volt locations L1, L2, and N. you should get two sine waves exactly on top of each other. Is there a way to manipulate these waves to not be on top of each other for clarity? If so, then it is a false indicator. It is absolutely impossible for them to be out of sync with each other. One primary sine wave creates all secondary waves.

    • @KevinCoop1
      @KevinCoop1 5 років тому +2

      Molham Adawi I'm not exactly sure what you are asking. If a load is connected L1 to L2 the voltage is 240 volts. If the load is connected L1 to neutral it is 120 volts. If a load is connected L2 to neutral, it is 120 volts. If the neutral is grounded, meter connected either L1 or L2 to ground, is 120 volts. If a meter is connected neutral to ground it is zero volts. Make sense?

    • @carultch
      @carultch 4 роки тому

      ​@@mmaad2165 The neutral is bonded to ground at the service disconnect, and ground is DEFINED AS zero volts. By extension, neutral is also at zero volts.
      The two ungrounded lines of a split phase system, are at equal and opposite voltages-to-ground. The voltage between them comes from the full scale quantity of secondary windings in the transformer. The voltage-to-neutral comes from half the secondary windings in the transformer due to the center tap.
      So we have the following equations that govern what the two line voltages are. The volt values are really RMS voltages, which is a special kind of averaging called root-mean-square. What really happens is there is a sine wave, that has a peak at sqrt(2)*the RMS voltage.
      | V1 - V2 | = 240V
      | V1 - VN | = 120V
      | V2 - VN | = 120V
      V1 = -V2
      VN = 0

  • @thomasjust2663
    @thomasjust2663 5 років тому +9

    Great, great explanation, you should do a podcast or become a teacher

  • @jakekaj111
    @jakekaj111 4 роки тому +5

    That is the answer I've been looking for since I graduated in my college. Thank you!

  • @elvisfrog2171
    @elvisfrog2171 4 роки тому +3

    208v comes from the trig sin function between the 2 phases with a 120 degree phase relationship. (170v peak + 170v Peak) X sin(120 degree) = 294.4v peak, or 208v rms.

    • @ShedPowersports
      @ShedPowersports 4 роки тому

      thanks!!!

    • @ShedPowersports
      @ShedPowersports 4 роки тому +1

      Just make sure your calculator is set to DEGREES if you're doing it on your phone haha

  • @stevenlapham5254
    @stevenlapham5254 2 роки тому +1

    I don't know what orifice my head has been in all my life but that was the best statement I have ever heard describing RMS ...... to make a static single measurement of a constant moving voltage. WOW! I'm stealing that line ...... thanks

  • @illestofdemall13
    @illestofdemall13 3 роки тому +3

    They are opposite polarity but not really 180 degrees out of phase. You can't have a single phase transformer be out of phase with itself.

    • @tysesty
      @tysesty 3 роки тому +2

      I think he doesn’t know what he is talking about.

    • @GH-oi2jf
      @GH-oi2jf 3 роки тому

      The transformer is not out of phase with itself, but when you cut the 240V single-phase secondary in half, you get two 120V waveforms, and when you reverse one, they are in opposite phase. That is equivalent to 180° out of phase. He does know what he is talking about, you just don’t like his terminology.

    • @illestofdemall13
      @illestofdemall13 3 роки тому

      @@GH-oi2jf I am not talking about what I like or don't like. I was talking from how I learned it and it was said that in single phase there is only one "phase" but since there is a center tapped neutral, the polarities are opposite. I didn't say he doesn't know what he's talking about.

    • @GH-oi2jf
      @GH-oi2jf 3 роки тому +1

      @@illestofdemall13 - Vladimir said he doesn’t know what he is talking about. I responded to both in one reply. I apologize for being lazy, but stand by my opinion that “opposite phase” is a legitimate way to characterize the situation.

    • @illestofdemall13
      @illestofdemall13 3 роки тому

      @@GH-oi2jf Nothing wrong with standing by your opinion. I may have been fussy with semantics. I have OCD so sometimes I can be that way without meaning to.

  • @libertyforallutah3263
    @libertyforallutah3263 4 роки тому +1

    So it seems by looking at the comments everyone else is understanding and I am just confused 😡what formula did you use for single phase 180 degrees out of phase when you got 240??? I don’t see how you add there? I thought they were both IN PHASE and then you add 120+120 , you get 240. If they are really out of phase then it’d be called 2 phase no? Basically the question I’ve been searching for my whole career and i can’t seem to find anyone who can explain it in a way I understand .I’ve already spent two hours tonight researching again . My question has been : why is it called single phase when there are two wires that according to you are out of phase. If they were in phase then calling it single phase would make a lot of sense

    • @libertyforallutah3263
      @libertyforallutah3263 4 роки тому

      Please help lol 🥺🥺🥺

    • @intheskymusic
      @intheskymusic 3 роки тому

      Think of it like taps on a transformer..its the potential difference between different points one 240 v coil. The 180 degrees out of phase makes no sense.

  • @timbrackett1518
    @timbrackett1518 3 роки тому +1

    Oh yeah, that graph is wrong too. The graph with 2 “out of phase” 120v sine waves? That graph shows Zero voltage. Since when does 120v plus -120v equal 240v? You keep saying “add two 120v legs”. Nowhere ever are two 120v lines tied together to make 240v. 240v is split. You didn’t shift anything in time. Both haves are still in phase. You are just measuring each side from the middle. In doing so you are reversing the order of the leads on one side compared to the original 240v.

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      subtract

    • @RoyceHintergardt
      @RoyceHintergardt Місяць тому

      The graphs are in reference to the neutral and it is a correct example. This is exactly how we measure 240 volts. If you graphed it using “A” phase as your reference, you’d have two sine waves. One twice as big as the other, and they would be in phase with peaks at the same points. You would still measure 120 and 240 RMS.

  • @kingredleg6747
    @kingredleg6747 7 років тому +2

    When you pulled out that stretch band I thought that you where going loopy. But you showed the best demo I have ever seen for the 240 volt sign wave. After looking for a good answer on the internet and from people in the electrical business. You made It finally make scene. Thank You

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  7 років тому +1

      Your welcome, I do have some odd methods, but they seem to be working well!

  • @parkourguyyy
    @parkourguyyy 3 роки тому +1

    This is the stuff they don't teach you, or atleast don't teach you well in trade school. This is so simple, yet so effective

  • @TheGermanElectrician2000
    @TheGermanElectrician2000 3 роки тому

    High-leg delta is a bad system. Symmetrical load is almost impossible. Here in Europe, every household gets 230/400V three-phase power. 230V 1p for normal appliances and 400V 3p for every device above 4kW.

  • @8bellsringer
    @8bellsringer 3 роки тому

    NIce explanation, but the analogy with the exercise band is not correct because if the red dot is a zero for both, then each hand has to cross over that dot going from +120V to -120V. Not the way it's show on the video. If the red dot represent -120V for one hand and +120V for another hand (that's how it was explained on the video) - then the maximum difference between two hands is 480V (when the phases difference between the hands is 180 degrees).

  • @1969Kakashi
    @1969Kakashi 5 років тому +1

    I've been dealing with hooking power to our labs on drilling rigs for over 20 years and never has the 208 question mark been answered in a more clear way. All power on a rig is three phase, but we would only take two of the hots (single phase) to power our trailer. I do also remember seeing 220 volts on some rigs, but as I recall the single hots would be higher, as you've indicated. Thanks for clearing that up, At-Man.

  • @mrtickyricky1
    @mrtickyricky1 4 роки тому

    I wired two 240v outlet from the same panel, same breakers and one is 240v and the other 208v?????

  • @arpitdave7211
    @arpitdave7211 7 років тому +3

    You've very wide knowledge and good teaching skills, sir. Thank you for this superb explanation.

  • @twu2023
    @twu2023 Рік тому

    Can I connect a 208V-1 Phase device to a 120/240V system?

  • @n310ea
    @n310ea 5 років тому +1

    Kinda like a 4-cylinder engine; where the pistons are 90° offset from each other. Thanks

  • @emarr3720
    @emarr3720 3 роки тому

    Best explanation I've encountered!! All of sudden RMS, Peak voltage & why 208v 3-phase make sense. I came to this channel from a residential 3-phase power video that didntvexplain why the "High Leg" is 208v & an Ideal Circuit Analyzer video talking about Peak voltage & I didn't fully understand it. I didn't know 120v came from a special way of averaging!!! The only part that's unclear is how 208v is represented graphically. It was clear graphically for 240v--it's peak to peak of the 2 sine waves but 208v is not peak to peak. It is "somewhere" on the 2 waves, shoulder to shoulder so to speak but where exactly on those shoulders? Your channel is a welcomed surprise for a channel about machine shop work--not electrical. Great job.

  • @cindytepper8878
    @cindytepper8878 4 роки тому

    Fun fact. "Single phase" 120/208 from a WYE connected transformer is not really single phase if you include the neutral. I learned this after troubleshooting an overheating 3 phase motor in a facility. The "electrician" had hooked up a 208 3 phase motor to 2 of the hots and the neutral. It was starting but overheating, it was an easy troubleshoot and fix but I got to thinking, "How can a 3 phase motor start on single phase?" .
    If you think about it, two phases and a neutral from a WYE connected transformer give you some strange poly-phase with weird phase relations

    • @Jason-wc3fh
      @Jason-wc3fh 2 роки тому

      Well the person who wired that is a total moron. Maybe that neutral gave it just enough bump to get the motor to rotate and start. Typically trying to start a 3phase motor with only 2 of the required phases doesn't work very well. And any electrician wiring 3 phase should be prepared to confirm the phasing is correct with the proper tools. Having certain 3 phase equipment run backwards without confirmation of proper phasing should have ruled out that a neutral was where it shouldn't have been.

  • @Cloakedpyro
    @Cloakedpyro 4 роки тому +1

    Excellent video, and demonstration/graphs! thank you for your clear and precise explanation!

  • @mailee4740
    @mailee4740 3 роки тому

    At 7:50, you mentioned that for 120v, three phase system, a one leg would be higher than 120v and needs to be stepped down. Could you please clarify? My understanding is that the 208v came from 120v with three phases , each phase is 120 degree apart. The line to neutral would be 120v. Thank you.

    • @GH-oi2jf
      @GH-oi2jf 3 роки тому

      He didn’t say that. He said if you had 220V 3-phase, the voltage phase-to-neutral would be too high, much more than 120. You want to have 120V service, so that requires that for 3-phase, the phase-to-phase voltage will be 208V.

  • @dieselwelds8645
    @dieselwelds8645 Рік тому

    So the 240vac single phase is NOT split-phase. the 60hz waveform does not split. What is happening is the transformer is made to output 240vac and is completely electrically isolated from the input or any other line. then a tap is made in the middle of the winding, like on a welder transformer that has multiple taps. We call that tap neutral and because it is in the middle of the winding it gives 120vac from neutral to each line. So the graph showing two separate waves 180 degrees apart from each other is wrong. it's a single wave form of 240vac.

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      "Neutral" means connected to ground. The center tap of the secondary is grounded, as is the common line of the wye distribution line. The primary and secondary are not completely electrically isooated because the neutrals are connected.

  • @xNYCMarc
    @xNYCMarc Рік тому

    The leggs in split-phase are NOT 180 degrees out of phase. It's SINGLE PHASE. Something can't be out of phase with itself. If you're going to be "explaining" things to people, you might want to make sure you actually understand it yourself.
    If you measure the waveforms CORRECTLY on the split-phase, the red and black traces on the graph would be superimposed over each other. In other words, it would look like one waveform.

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      This is pedantry. Polarity reversal of a symmetric periodic waveform is equivalent to a phase shift of 180°. The pole transformer is a single phase transformer, in the context of a 3-phase power distribution network, but when we are just looking at waveforms plotted on a graph, how we describe them is just mathematics, irrespective of what the plots represent. "Phase shift" is a term used to describe identical waveforms which are displaced in time relative to one another.
      If you had an actual 2-phase generator producing the 120V power, you would not be able to distinguish the output from the split-phase output. They are equivalent.

    • @xNYCMarc
      @xNYCMarc Місяць тому

      @@GH-oi2jf Calling it "pedantry" is useless. The fact is that split-phase is not "out of phase".
      The 3 phase distribution has absolutely nothing to do with anything and you're throwing it in there to add more information, which is irrelevant, in an attempt to obfuscate the incorrect information.
      Split-phase uses ONE PHASE of the 3 phases being distributed. It's ONE PHASE that is being "split" in half. One can use the two halves separately for 120v or use the entire phase for 240v.
      It's one phase. It cannot be "out of phase" since it ONE PHASE. You need another phase to be out of phase from to be out of phase.

  • @MrSehka77
    @MrSehka77 4 роки тому

    Can 120/ 208v 3 phase generator power a 230v 1 phase welder without modification has 4 prong 120/208v 20amp receptacle beside getting an adpator from 3 prong welder plug to 4 prong from generator?

  • @timbrackett1518
    @timbrackett1518 3 роки тому +1

    Splitting a single phase 240 service does not create two legs 180 degrees out of phase. Measuring from a center tap to each hot is simply half the voltage with the order of the leads reversed. In other words it measures the opposite polarity, not 180 out of phase. Phase is a shift in time. 3 phase power is truly 3 waves shifted in time by the physical placement of the generating coils 120 degrees apart on the rotor.

    • @GH-oi2jf
      @GH-oi2jf 3 роки тому

      Opposite polarity is equivalent to a 180° phase shift. There is no point in quibbling about the terminology.

    • @timbrackett1518
      @timbrackett1518 3 роки тому +1

      What is the point in making this video with incorrect terminology? I just explained the difference. That is not “equivalent”. What you mean to say is that they have an equivalent result. Phase and polarity are not the same thing. Using them interchangeably just leads to misconceptions. That’s when you get people talking about 2 phase power which doesn’t even exist. If there was a point to this video there certainly is a point to clarifying the terminology.

    • @GH-oi2jf
      @GH-oi2jf 3 роки тому

      @@timbrackett1518 - It’s not incorrect terminology. It is just a way of looking at it. “Polarity” is incorrect terminology when speaking of AC, in my opinion. That is a DC term. For AC, we say “opposite phase” instead of “opposite polarity.”

    • @timbrackett1518
      @timbrackett1518 3 роки тому +1

      @@GH-oi2jf Sorry the terminology is incorrect. You go look up definitions for phase and polarity. Then come back and tell me again they are the same. They are not! No one cares about your opinion. You come here just to argue? I commented because this “educational video” uses misleading terminology. You commented to argue.

    • @tjblues01
      @tjblues01 3 роки тому

      @@GH-oi2jf Phase is a shift of sine wave form. It is not just "opposite polarity". To have real 180 degrees out of phase you would need one sets of wires coming from N-L2 to be longer than wires from N-L1 (or other way around). And because we are talking about 60Hz grid then difference in length should be around half of the wavelength of it. It means: *λ = v/f = (c * VoP)/f*
      (.82 * 300000km/s) / 60Hz = 4100km = 2548 miles. Half of it is 1273.81 miles.
      I bet you that you usually don't have that much of wiring in an average house.
      --------
      *λ* wavelength
      *v* speed of wave propagation
      *f* frequency
      *c* speed of light in vaccum
      *VoP* velocity of propagation expressed in %. For typical copper wires it's something between 80 to 90% of c.

  • @ibrahiemmuhamed9455
    @ibrahiemmuhamed9455 3 роки тому

    Can I connect a Single phase device between two phases of three-phase 208 v system, is it work healthy or a problem will accur.

    • @carultch
      @carultch 2 роки тому

      If it is built for it, yes.

  • @JP-kk5vw
    @JP-kk5vw 7 років тому +1

    Because I am in an old manufacturing zone, I have a true 240 Volt 3PH, 3 Wire Delta Service. Three balanced hots at 120V to ground. No ground wire. The conduit carries the ground. If I moved, I would have to use the 208V Wye service that you speak of At-Man. Because the 3 wire delta is not available in newer communities. Might still be available in the Buffalo area. Considering all the old Mfg. there. Also, under the 240 setup, a 10 HP 230V motor can make 10HP. Under 208 V, you are under volting so you will not make full rated HP. AND you will pull more amps which will make your meter count higher. Equaling a higher bill. I have to say I love my 3 wire Delta. I would not care for the all in one 208 Wye system. BTW. My 120/240 1PH is a separate service that comes in at the opposite end of the Bldg.

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  7 років тому

      Yes, even here National Grid and NYSEG will no longer install a 240V Delta system. They are all switching everyone over to 208 Wye as far as I know. I very well could be wrong on that, but last I heard that was the case.

  • @David-mo2zq
    @David-mo2zq 3 роки тому

    Ok ok ok ok ok ok ok ok
    Not as bad as
    Like like like like like like like
    But just as annoying

  • @louiehostetler7327
    @louiehostetler7327 3 роки тому

    I understand 208 I'm trying to find out how to get to277
    For my 480 volt 3-phase motor I am trying to build a rotary phase converter

  • @walteraustinr102
    @walteraustinr102 3 роки тому

    Thank you for stating the facts!! Explained perfectly. I know an electrician who can’t understand the 220 V 180° out of phase. We argue about this here and then. He wants me to admit I’m wrong. He’s just one of those who thinks whatever he says is right. A true jester, fool. I learned the voltage phasing years ago in the USAF. Then the fool was in the army ..lol No pun of our Army guys. We all served to protect our great country, no matter what branch of service 👍

  • @SilverthorneA27
    @SilverthorneA27 2 роки тому

    I really hope someone answers my question: You supply 2 hots to the equipment, but there are 3 wires.. what do you do with the 3rd?

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      The third wire is the neutral (or it could be a ground). If you have 240V equipment only, you don't need the neutral. But some 240V equipment contains some 120V components. In that case, you need the neutral.

  • @rigolfilo
    @rigolfilo 4 роки тому +1

    Thanks!
    My question was a bit different but this answered it, because I had always been told that in a three phase system the measurement from phase to phase was 220v.
    I guess I didn't pay enough attention at school and missed this important bit.

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  4 роки тому

      There are three phase systems out there with a line to line of 220, more common to find 208 now.

    • @rigolfilo
      @rigolfilo 4 роки тому

      @@AtManUnlimitedMachining My doubt was why 220v had 180 degrees offset while 330v had 120, why did it change from 180 to 120? Magic? Now I understand that 220v(208v) in a 3 phase system still has 120 degrees offset.
      I kind of feel like an idiot lol

    • @Jason-wc3fh
      @Jason-wc3fh 2 роки тому +1

      @@rigolfilo The 120 phasing is from transformer to transformer that comes directly from how a generator is wired with 120 degrees apart of rotation to generate the power. You get the 180 degree phasing on ONLY one transformer at a time by splitting the negative and positive charges right down the middle to completely oppose eachother since we're talking about alternating current.

  • @aspitofmud6257
    @aspitofmud6257 2 роки тому

    In understanding RMS it would be helpful to know what RMS stands for.
    Thanks.

    • @GH-oi2jf
      @GH-oi2jf Місяць тому +1

      Root Mean Square

  • @VladFredK
    @VladFredK 4 роки тому

    Yeah, didn't answer my question. So how come when I attache oscilloscope to 120 volts I will see one sine wave, when I attache scope to 240 volts I will see one sine wave. Is the scope stupid it doesn't see two sine waves? Thanks

    • @timbrackett1518
      @timbrackett1518 3 роки тому +1

      Because the explanation is inaccurate. Spitting 240 doesn’t create 2 phases out of 1 as was implied. If you measure from the neutral to each leg you are measuring 2 different polarities as you have changed the order of the leads.

  • @bencoss7003
    @bencoss7003 2 роки тому

    208 uh-oh watch out for the crazy leg.

  • @homefront3162
    @homefront3162 5 років тому +1

    I feel vindicated, I just explained this to a co-worker today and I was correct! I have no idea how I knew this.. Great video Sir!

  • @jolyonwelsh9834
    @jolyonwelsh9834 3 роки тому

    Yes but you would still need a buck-boost transformer to obtain 240 volts to operate some equipment.

  • @BestOutdoorFun
    @BestOutdoorFun 5 років тому

    I have a 240 volt that has 3 wires. A black, a white and a ground. I want to run a 120 volt from this. The 120 volt has a white a black and a ground as well. How do I do this?

    • @carultch
      @carultch 4 роки тому

      Get a single phase step-down transformer, with a KVA rating appropriate for your application. Configure it for 240V on the primary, and 120V on the secondary.
      You probably are located in a country where the mains voltage is 240V to neutral and 415V phase-to-phase, and they don't even supply 120V to the typical customer.

  • @austin3626
    @austin3626 4 роки тому

    if 3 wires in a 208V system are considered "3 phase" then WHY is 2 wires in a 208V system considered "single phase". Shouldn't it be "double phase" instead???

    • @timbrackett1518
      @timbrackett1518 3 роки тому

      There are 3 phases from the generator. Your service from the power company will be either all 3 or just 1 phase at whatever voltage it is stepped down to at the transformer. 3 phase uses 4 wires + ground. Single phase only needs 2 wires but will typically include a 3rd wire to the center tap of the transformer. This center tap will measure half of the full voltage. It is common to say each leg is 180 degrees out of phase with the other but that is not accurate. Referencing each leg to the center tap is simply measuring the opposite polarity of the same phase.

    • @carultch
      @carultch 2 роки тому

      Historical reasons. There is a 2-phase system that is now obsolete, and therefore the term "2-phase" is spoken-for. It used to use two phases that were 90 degrees apart, in order to improve the ability for motors to start. This is now obsolete, and motors on single phase systems use a starter coil and capacitor to get the rotor moving, in the event that they have the bad luck of starting in the rotor-lock position.
      I dislike the term "single phase" when referring to the 2 phases and neutral derived from a 3-phase WYE system. It's called single phase because you'll get just one single waveform when connecting across the two phases. I prefer calling it an open wye, but so far that term hasn't caught on. What it really is, is 2 phases that are each 120 degrees apart from each other, which therefore generate two 120V waveforms and one waveform across the phases of 208V.

  • @rockydippel7581
    @rockydippel7581 Рік тому

    Great video, you are a very good teacher, thank you for explaining this so well!
    good job Sir!
    Rocky

  • @godlugner5327
    @godlugner5327 Рік тому

    First video of yours I've seen but that last bit about FIRST robotics at the end made me a subscriber 🦾

  • @JohnJohn-nu8ql
    @JohnJohn-nu8ql 2 роки тому

    Hi! Why both peak at same time can measure 240? If they peak together there isn’t voltage potential difference between two leg still can measure voltage? I don’t get that, please explain thanks

    • @carultch
      @carultch 2 роки тому

      I have a Geogebra resource that answers this:
      www.geogebra.org/m/qsz3twyg
      The black wave indicates the voltage vs time waveform on line 1 (the black conductor) to neutral.
      The red wave indicates the voltage vs time waveform on line 2 (the red conductor) to neutral.
      The burgundy wave indicates black minus red, which is the voltage across the two line conductors.
      At any given time Burgundy Voltage = black Voltage minus red Voltage.
      It's not the voltage to ground that you measure black-to-red. It's the inter-phase voltage, that the burgundy waveform measures

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      You need to subtract instead of add. Voltage is the potential difference.

  • @panplayer
    @panplayer 3 роки тому

    So if one phase is 180 degrees out of phase with the other, wouldn’t the peak of one and the trough of the other add to 0?

    • @spruce_goose5169
      @spruce_goose5169 3 роки тому +1

      In relation to neutral yes. Not in relation to each other. To measure to eachother, the calculation is subtractive, since voltage is potential *difference.* -120-120=-240.

  • @RADIOACTIVEMASCULINITY
    @RADIOACTIVEMASCULINITY Рік тому

    This really helped me understand what’s going on with the 3 phase vs single phase! Is there a way to take the 3 phase 208 any get single phase 220?

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      With a buck boost transformer.

  • @dcoakley11
    @dcoakley11 Рік тому

    Best explanation of this I ever heard

  • @DFEUERMAN
    @DFEUERMAN 6 років тому +1

    my question folks: what's the RMS voltage when utilizing 3 hot legs? (when each is 208v RMS leg-to-leg and each is 120v RMS leg-to-neutral?)

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому +2

      Not sure what your asking, they measure leg to neutral (120) and leg to leg (208)

    • @jonathandonathan9689
      @jonathandonathan9689 5 років тому

      @@AtManUnlimitedMachininggreat video! still have one question. 240v 3 phase system, If you are reading 208v from leg to leg, and 120v from leg to neutral, can you still read 240v ?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому +1

      That does not have a straight forward answer. If you have a 208, Y connected service, there will be 120 leg to neutral. There is a service called a "high leg Delta" in which you get 240V leg to leg and its connected in a delta. They then add a center tap to one of the windings on the transformer to provide 120. This configuration has a major drawback of phase imbalance issues. The 120V loads can only be on one phase of the 3 phase system. With a 208/120 Y connection you can balance the 120 loads on all 3 phases.

  • @pedroaguilar3237
    @pedroaguilar3237 5 років тому

    Great video. Can you tell me how to wire a high bay metal halide fixture (120v,208v,240v,277v) to a.. I think a split phase (2 hots at 120v each and a physical ground)? I have not been able to get it to turn on it just buzzes. I wired a 277v to a hot, a common to the other hot and the physical ground green. Any help is greatly appreciated

  • @taiwanluthiers
    @taiwanluthiers 5 років тому

    So I have a question. I am in Taiwan, and my house/shop has a 3 phase supply. When I measure across any of the phases, I get 235 volts. However all 120v appliance is running through a transformer. What kind of system is this? Why is the transformer necessary, and why can't I just take one of the legs and run the neutral to ground?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому

      Because you have 235VAC from phase to phase, even if your connection was a WYE you would get 136VAC from phase to neutral. The transformer steps the phase voltage down from 235 to 120 for you.

    • @taiwanluthiers
      @taiwanluthiers 5 років тому

      @@AtManUnlimitedMachining So 220v appliances are more forgiving of voltage variations? As in 135v is going to burn stuff while for 220v counterpart it's not as critical? Because standard 220v appliance works fine connecting between phases but 110v doesn't. It seems like a weird system to require a transformer to get 110. In a 2 phase system in Taiwan when I measured across 220 I get 250v. Do they have different power plants putting out 1 phase vs 3 phase systems, because it seems the waveform is different, or how do they split it at the substation? My understanding is electricity comes out of a power plant as 3 phase...

    • @carultch
      @carultch 4 роки тому

      ​@@taiwanluthiers It's not different power plants putting out the different systems. It is the topology of the service transformer. Three phase comes from three magnetic couplings in the transformer between the utility's feeder, and the secondary they give to you to connect your service conductors. Single phase comes from just one of the phases on the utility's feeder, a single magnetic coupling in the transformer, and if it is a split phase system, they center-tap it to make two lines with equal and opposite voltage-to-neutral.
      Grid voltage also is a moving target, and it is a challenge for utilities to maintain a stable nominal voltage at your service. When a lot of load is present in your neighborhood, the voltage drops. When load diminishes, voltage rises. There are taps on the transformers that allow for moderate adjustments in grid voltage, to adapt to variations as new customers come online and substations are upgraded.

  • @joelhartlen4324
    @joelhartlen4324 4 роки тому

    Not drawn out at all, actually a really great answer I asked 2 journeymen one is usually great at explanations and he couldn’t do it this well. Awesome thanks so much ! Will be watching more

  • @joewest1972
    @joewest1972 3 роки тому

    Very good explanation. How would 240 volt single phase 50 amp outlet be wired from the 3 phase?

    • @Jason-wc3fh
      @Jason-wc3fh 2 роки тому

      It would only be coming from one of the 3 phases after a step down transformer at the hydro pole. The single phase is a SPLIT phase of only one leg of a 3 phase system. One waveform is negative, the other is positive at 180 degrees apart... You can see this in every residential area with visible hydro poles. You will see 1 transformer tied in to one of the 3 wires above to serve residential dwellings... When you see a cluster of 3 transformers close together, that's your 3 phase that is going to be feeding a commercial business/factory.

  • @aubreyroche5080
    @aubreyroche5080 4 роки тому +1

    THAT, was an Outstanding Explanation !!!

  • @palletjack654
    @palletjack654 2 роки тому

    Transformers usually don’t hang on telephone poles, they are power poles…

    • @GH-oi2jf
      @GH-oi2jf Місяць тому

      Correct. I learned that long ago from a friend whose dad worked for the power company.

  • @Fishnatic209Outdoors
    @Fishnatic209Outdoors 2 роки тому

    Awesome video thank you !

  • @StoneColdMalone
    @StoneColdMalone 5 років тому

    If you have a generator putting out 480v going to a transformer that says 277/480 Y on it, does that mean its stepping it down to 277? Or is that the rated input voltage to the transformer?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому +1

      A transformer labeled 277/480 Y will have a neutral point. If you measure voltage between two of the hot legs you will get 480V, if you measure the voltage from one hot leg to the neutral leg you will get 277V. You will find a lot of commercial lighting uses 277V so they can run on one leg of 480 without the need for another transformer.

  • @jolyonwelsh9834
    @jolyonwelsh9834 3 роки тому

    also known as the wimpy wye.

  • @terrym2007
    @terrym2007 4 роки тому

    can a 208v heater run with 240v supply?

  • @brockdelorenzo1120
    @brockdelorenzo1120 5 років тому

    I have a 3 phase 30 amp requirement for a water distiller but my house is the typical us single not a 3 phase. Can I still hook up machine by using three 30 amp single breakers or two doubles?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому

      Most likely not. You need to check with the equipment mfgr and see if it can be reconfigured to run on single phase power.

  • @radiomellowtouch
    @radiomellowtouch 3 роки тому

    Great explanation. 👍

  • @josephtese5037
    @josephtese5037 5 років тому

    I have an electronic dimming switch. It's powered by an L14-20 Plug. The device itself is a 120v device - Half of of the circuits its providing is powered by a 20AMP leg, as is the other. This is context so you don't say the following is absurd and dangerous. Often times, because the L14-20 is not accessible, I use a reverse Y-Splitter (x2 Male Edisons, combined into one female L14-20 Connector). I plug the x2 male edisons into two breakers, knowing they are on different breakers and PHASES. My question: Is there any disadvantage to plugging the two edisons onto different breakers, but the same phase? The advantage is accessibility.

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому

      If you plug them into the same phase you can over load the neutral line. For example, if both hot legs are in phase but on separate 20 amp breakers, you will be able to draw a total of 40 amps. Because there in phase the current will sum at the neutral and 40 amps will be on the neutral. Assuming you used the same size wire for all connections it will overload the neutral. When there on separate phases and each hot leg is carrying 20 amps then the neutral current in an ideal system would be zero.

    • @josephtese5037
      @josephtese5037 5 років тому

      I understand, now. Thank you so much!@@AtManUnlimitedMachining

  • @VladFredK
    @VladFredK 4 роки тому

    How do two combined sine waves for 120 volts become one sine wave for 240 volts? Thanks

    • @timbrackett1518
      @timbrackett1518 3 роки тому +1

      They don’t. Nowhere in an electrical system do you combine 120v lines. 120v lines come from splitting a single phase 240v service or from one leg of a 3 phase 208v service.

  • @troll_town_usa_pop_u
    @troll_town_usa_pop_u 4 роки тому

    Change the intro music and I'll subscribe.

  • @AustinRxxxx
    @AustinRxxxx 4 роки тому +1

    A follow up video of the differences between 480v 277v & 208v would be interesting

    • @carultch
      @carultch 4 роки тому

      277V is the phase-to-neutral conjugate voltage of 480V. In otherwords, the same 3-phase system has 480V between the phases, and 277V from any individual phase to neutral. Just like 120/208V, the ratio between them, is sqrt(3). Draw an equilateral triangle, 48 inches on each side. Find its center. Without a doubt, you'll measure 27.7 inches from that center to any corner. That's where the sqrt(3) comes from in this relationship.
      A general rule of understanding why we use higher voltages, is "voltage is cheap, current is expensive". You usually have to have enough "critical mass" of your power rating for this to hold true, but generally, it is more economical to use higher voltages for building high power devices and supplying power to them. In light commercial applications, the 208V is used for supplying power to high power appliances like the HVAC units, refrigeration, and motorized machinery, while the 120V is used for supplying power to receptacles and lighting that are a much smaller total of the power. In large commerical/industrial applications, many large scale loads require the 480V power. The 277V is commonly used for the lighting fixtures. A 277/480V service, will usually have a customer-owned transformer to produce 120/208V for the receptacle loads, and any other device needing a lower voltage. So you may have a 500kVA service at 277/480V for the building in general, while having 150kVA worth of 120/208V power on a separately derived system.

    • @realSamAndrew
      @realSamAndrew 2 роки тому

      @@carultch this is fantastic. You did a better job at explaining this than most videos. Would you be able to explain how you get 208v out of a single phase service? All I have seen is that 208 comes from 3 phase with each phase having 120. How do you get 208 from a single phase 120/240?

    • @carultch
      @carultch 2 роки тому

      @@realSamAndrew The short answer is, that you don't directly get 208V from 120/240V single phase. Not without a transformer. I can't think of a reason you would want to do this in the first place.
      There are loads that work on both 208V and 240V, so maybe that is what you have in mind. Common for big-ticket residential loads, like ovens and dryers. The 208V or 240V will run the heating element that is less voltage sensitive than the motor, while the motor would run on 120V (since it is less Watt-intensive, and the 120V is what these two grids have in common. These loads work better on 240V, because otherwise you'd only run at 75% power (i.e. 83% Voltage * 83% current). A motor load like that of an A/C system would need a physical adjustment of its coil taps, so that it can work on 208V instead of 240V. If you run motors on too little voltage than their rating requires, this could lock the rotor and damage the motor.
      My split-phase Geogebra resource:
      www.geogebra.org/m/qsz3twyg
      Burgundy = the 240V across the red and black wires
      Black = Line 1 at 120V to neutral.
      Red = Line 2 at 120V to neutral, opposite polarity from line 1.

    • @carultch
      @carultch 2 роки тому

      @@realSamAndrew Another kind of "single phase 208V" is the kind that feeds apartment buildings. The property gets a 3-phase service in the aggregate, which divides into sub-services for each dwelling unit. Usually, there is also a common loads service at 3-phase, for running general loads like exterior and hallway lights.
      Each dwelling unit gets a staggered pair of phases (staggered from what each neighbor gets), and the neutral. The dwelling unit therefore gets two live conductors that are 208V apart, and each 120V to neutral. I dislike the term "single phase" for this, but nevertheless, that is what the industry calls it. My preferred term is "open wye", since it is a partial grid from the 120/208V wye grid. There is no 240V brought to the dwelling, and using 208V instead of 240V has to be considered when big ticket loads are selected for the application.
      I would also instinctively call this "2-phase", but that is reserved for an obsolete system.

    • @realSamAndrew
      @realSamAndrew 2 роки тому

      @@carultch @carl thank you very much. Would this "2 phase" 208 system require a motor capacitor that is eliminated on true 3 phase?
      I watched an HVAC video today with a system having 208 service and it had a failed capacitor. Small commercial bldg and no details on whether the power was single or 3 phase. Can provide link if you want.

  • @killer6458
    @killer6458 5 років тому

    nice video but do you have any one wiring buck and boost transformers e.g. 208 to 240 etc I want to be able to understand the wiring schematics

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому

      Hello Jim, transformers are pretty straight forward, a primary and a secondary. From there the name plate and mfgr info will tell you how to wire it depending on your incoming voltage and your desired output voltage.

  • @nickledimez4012
    @nickledimez4012 5 років тому +3

    Excellent! Thank you! I’m actually in a machine shop class and I’m learning how to use the lathes and mills. I’m learning electrical as well. Looking forward to more videos!

  • @tedlahm5740
    @tedlahm5740 5 років тому

    Kindly explain why, WITH NO OPEN NEUTRAL, some current (unbalanced portion) does travel back to the center tap AND also some VOLTAGE must
    move it. I have NO SHOCK when touching the GUY wire outside of the property, going to the transformer? Thank you.

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  4 роки тому +1

      The neutral is referenced to ground. If your grounded and measure the neutral there should be no voltage difference. However, if you disconnect the neutral from a load and measure the loads neutral terminal you WILL get voltage because your completing the path to ground. This is why we use a 3 wire system with an independent ground wire and the Neutral and ground is only tied at one point in the main panel.

    • @tedlahm5740
      @tedlahm5740 4 роки тому

      At-Man Unlimited Machining Wonderful explanation of KVL Kirchhoff's voltage
      law. Open the neutral at a load, measure for voltage, your meter BECOMES
      AN ADDITIONAL LOAD. thank you.

  • @bobferrarotti7118
    @bobferrarotti7118 5 років тому +1

    Great video and explanation! Thanks for explaining so clearly and concisely.

  • @partisanguerrilla3167
    @partisanguerrilla3167 7 років тому +1

    Talking about power, I just was checking on a VMC10 to buy today. Glad I watched your vids on buying a used cnc.
    It was an interesting experience looking at the machine, as I got a view of another fadal across from it being thumb wheeled
    in the Y towards the front to demonstrate it and the limit switch was not working, popped the way cover up as it buckled up and pushed the front sheet metal of the machine outwards. oops, then I got too see how nasty that machine was under the way cover, made me really think about the work I would be facing possibly. One thing I would also ask, other than can I use my crowbar, is do you have any service records and receipt history on this machine? This was in a business I asked, and they did not, having run the machine and currently running the machine for over 2 years. All makes decision making a bitch!

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  7 років тому

      Nope, no service records to speak of.
      Fadal does not use limit switches at all, you wont find them. The machine was not cold started correctly which would lead to over travel.

    • @partisanguerrilla3167
      @partisanguerrilla3167 7 років тому

      I see...yes the machine did not start up right initially and then was powered back down and restarted, I believe then no cs command was entered. There was a storm hitting at the same time, but I got a good look under some way covers as a result ;). I think the whole visit may have been an omen to pass, or get ready to work your butt off getting and cleaning up this mess that hides behind the scenes. I keep watching your other vids on your vmc15, really impressed on all the information, equally impressed with Fadal. Started trying to understand what Centroid retro can do with one of these DC servo Fadal mills. I better find out how thick my garage floor concrete is, lol.

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  7 років тому

      Check this out, this is a plug in replacement for a Fadal controller. Game changer IMO.
      www.calmotion.com/527f-cnc-control-.html

    • @sethjohnson3240
      @sethjohnson3240 7 років тому

      We need to get Calmotion to send you one of these to review. I spoke with Calmotion and they said that this controller will have the biggest improvement on DC machines. Obviously, it will be an improvement for any machine, but I have the -5 CPU on an AC machine, so the improvement wouldn't be as great. Still, it seems like a huge improvement regardless. The 8gb of memory would be so nice! I am tired of DNC any 3d toolpaths.

  • @donaldmckee585
    @donaldmckee585 5 років тому

    1.73 is square root of 3 1.41 is square root of 2 208 /1.73 =120 great video

  • @samhickman3813
    @samhickman3813 5 років тому

    Great video! A follow up, are all modern 3-phase systems 208V? That is, if I got a 3 phase connect to support an EV Charger would my home now be more like a commercial property where the 240V dryer seems slow?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому +1

      The utilities like to install 208 3 phase for light commercial applications. It depends on your provider, but I don't think they are installing to many 240 3 phase services new anymore.

  • @amoore4363
    @amoore4363 3 роки тому

    I'm am an electrican and that was well said sir bravo.

  • @DryBayouGarage
    @DryBayouGarage Рік тому

    Great explanation, thx

  • @ronizaza3811
    @ronizaza3811 5 років тому

    Hello guys, so how I can make outlet for 208v?

  • @stevehoang5289
    @stevehoang5289 4 роки тому

    Excellent explanation sir. I sometimes confuse about this too and now I understand it. Thank you.

  • @yoho6348
    @yoho6348 2 роки тому

    High leg explained...

  • @michaelmardini346
    @michaelmardini346 4 роки тому

    Very clear. I am an engineer, not an electrical one, when i always wondered.

  • @footballfan2208
    @footballfan2208 5 років тому

    Most Informative - Thank you. Clarification question: From the description you gave, I would have thought that in the demonstration (reference 4:24 to 4:30 in the video ) that it would have been +180V then -180V (or more precisely +169.71V then -169.71V) versus the used reference of +120 then -120 {if measuring actual voltage} OR if you are measuring Vrms - then the reference to rms was simply left off in the video during those seconds and thus the 120V was actually 120Vrms??? Can you please clarify? Thank you kindly.

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому

      If I remember I think I did the whole video in terms of RMS. I should make a video on the difference between RMS and peak.

  • @AnwarAli-qu6ik
    @AnwarAli-qu6ik 3 роки тому

    Can i used two phase for lighting or not

    • @AnwarAli-qu6ik
      @AnwarAli-qu6ik 3 роки тому

      Can i used two phase for lighting or not

  • @jsalinas118
    @jsalinas118 6 років тому

    I want to wire a 240 3 phase machine to a 208 3-phase service do I just need to find the two lower legs?

  • @fishmonger7020
    @fishmonger7020 4 роки тому

    Good stuff right here. Exactly what I needed.

  • @SpiritofPluto
    @SpiritofPluto 4 роки тому

    Thanks! There were a few other tidbits I was able to gather from this one video-

  • @trollinforcement
    @trollinforcement 3 роки тому

    Best explanation I've seen of this yet

  • @cncma8496
    @cncma8496 7 років тому

    hi at-man
    please record one clip
    about complete axis motor repair and amp adjust
    gain setting and balance setting
    also clock card adjustment
    and
    powersupply check
    thx a lot 🙋

  • @davidsimental7154
    @davidsimental7154 4 роки тому

    Breh ur amazing

  • @juanvaldo666
    @juanvaldo666 3 роки тому

    Thanks for the explanation man.

  • @giovannimercuri5168
    @giovannimercuri5168 4 роки тому

    Best explanation of this concept I have ever seen.

  • @patdwyer5204
    @patdwyer5204 3 роки тому

    Thanks.

  • @MontesinoFamily277
    @MontesinoFamily277 4 роки тому

    Great way to explain things!! 👍👍👍

  • @yolo_burrito
    @yolo_burrito 4 роки тому

    The line voltage at the pole is “distribution” not transmission.

  • @yoho6348
    @yoho6348 2 роки тому

    480v high leg system?

    • @carultch
      @carultch 2 роки тому

      In theory, it could exist, where it is 480V phase-to-phase, and 240V phase-to-neutral on phases A and C. This would make the B-phase high leg 416 Volts to neutral. However, there is simply no application of such a grid.
      The delta topologies on a 480V system are usually either corner-grounded delta, or ungrounded delta.

  • @wolfrojo8940
    @wolfrojo8940 6 років тому

    Thanks this info help to connect 1 phase 208 volts motor @ 26 Amps.

  • @tedlahm5740
    @tedlahm5740 5 років тому

    Please. What physical characteristics in the CENTER causes/allows the phase
    to stop at the center tap. I know it is located at 1/2 of the coil turns but what
    SPLITS IT at that point. Is it because that point goes to ground? thank you.

    • @deidara1042
      @deidara1042 5 років тому +3

      Ted Lahm I’m just an apprentice, so this is just my theory.. it doesn’t “stop” there’s a wire tapped into the center and when a load is connected to the end of the coil and linked back to the center tap (neutral), then you’ve completed a circuit so the AC current will start to travel on that circuit. Then if you connect a load to the other side of the coil and back to the center tap(neutral) then the AC current will actually travel back and forth between the two legs of the coil and only the difference of the loads will travel back to the center tap

    • @deidara1042
      @deidara1042 5 років тому +2

      Ted Lahm also I believe neutral and ground are the same thing. Except grounds are connected to framing and any other conductor that could become live during a mishap. That “ground” is connected back to the center tap just like your neutral
      Current pretty much NEVER travels down thru the ground rod unless there’s a discharge of static electricity like from yourself or lightning. Cus only then is that electricity trying to travel back to its source(ground)

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому +2

      Nothing really goes to ground, it is there more as a reference. It is more how you connect your load. If the load is 120V and its connected to one end of the coil and then the center, it will be like the other half does no exist because there is no path for current to flow. When you connect a 240V load it will flow current through the whole coil and skip the center because nothing is connected there. You can have a 120V load connected to each half of the coil and because they have there own current paths each only sees 120V. Hope that helps.

    • @tedlahm5740
      @tedlahm5740 5 років тому

      Yes, self balancing of the load. Thank you. Also, as you stated in the beginning
      of the video, we MULTIPLY the volts times amps to get POWER factor.
      Higher voltage, less current needed for same power. Thank you.

    • @tedlahm5740
      @tedlahm5740 5 років тому

      At-Man Unlimited Machining Thank you.

  • @tedlahm5740
    @tedlahm5740 4 роки тому

    Very informative. Could of shown the star transformer (with neutral) and shown
    the math to reach 208 volts. Thank you. Wonderful video.

    • @Jason-wc3fh
      @Jason-wc3fh 2 роки тому

      The star (delta) transformer is basically an obsolete method of supplying 3 phase power. Reason being: Only one spot to tap for 120v between the 3 transformers which leaves a big load on one transformer to supply 120v to the building. There is other issues, but this is the main one. Whereas a Y transformer arrangement for 3 phase will allow all 3 transformers the ability to provide 120v to the building and it can be dispersed more equally to keep the loads similar to all 3 transformers.

    • @carultch
      @carultch 2 роки тому

      @@Jason-wc3fh What's the difference between a star transformer arrangement and a WYE transformer arrangement?

  • @SridharNiverty
    @SridharNiverty 4 роки тому

    Awesome explanation! Thank you !

  • @elektronikmaleinfach16
    @elektronikmaleinfach16 7 років тому

    i dont like in us that us have several differnet electrical systems and a lot of different sockets! in europe ( i hate global politics but in some ceses they are good ) we have normaly 2 systems! next we have to do at all countrys the same sockets and plugs! we have just one 3 phases system at 230 / 400v in us you have 120 240 singel phases and 120 /208 and 240 and 480 volt systems

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  7 років тому

      The voltages and frequencies of the electrical system in the US was mostly defined on the fly as the first power grids where built. I don't think you will ever see a world standard power system as the cost to convert would be huge. Maybe someday far off into the future when most things are using solid state drives that can except really just about any voltage and frequency you could see a world standard. There are still some things in the US that use 25 Hz power! Even that has not totally gone away. But once a 25 Hz service is disconnected it will never be reconnected without retrofit to 60 Hz. 240V systems are also no longer offered that I'm aware of. I think in the US they will most likely stay at 60 Hz, then 120/240 for residential, 120/208 for commercial, and 480 for industrial.

    • @elektronikmaleinfach16
      @elektronikmaleinfach16 7 років тому

      in germany it was in the early days the same! every company have ther own test system. per law it was set on 220 / 380 volt at 50 Hz. it were just a start if all european countrys have the same system they only alowd new insterlations for A 20 A 240V Brazilian socket based on the IEC 60906-1 standard. its easy to set in new insterlations all to 240V ! in us canada or japan you can in the first place set new sockets on to hot legs! at time japan can set up to 240 from 200. later split phase will be repleced to a hot and neutral system! or to a 240 480 volt split phase for large loads on single phase! we spend so much money into wars and shit ! so like it runs now we can just change over decades the frequency for all to for example 55 cycles! in capitalism its normal to replece stuff it works after few jears! all new generators and turbines can handle it and if all old systems are repleced we can crank the revolution in a long time up to 55! its more easy as all to 50 or to 60! remember they do it with com systems every few jears!!! byside in some places in europe railwais run on 16 1/3 or modern 16,7 Hz 15 KV

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  7 років тому

      The bigger issue is the appliances. Anything is possible, but you need to get a heck of a lot of people on board to do it. It is easier to bump a system by 10 volts then to double it and change the frequency. There are a lot of things that depend on a 60 or 50 Hz cycle. Even TV broadcasts still assume 60 or 50 Hz power cycles.

    • @elektronikmaleinfach16
      @elektronikmaleinfach16 7 років тому

      i know but most appliances dolt live 50 jears or so! i am not happy with switch mode power surplys but most tv systems work on that! heating elements ist no big deal . most electronic diveces can work for long time on boath 50 or 60 hz. so they can handle also everything between!! the only thing i get larger problems is induction motors or transformers they are to small to save money!! or diveces that ned the synchronus frequency like motor clocks ans stuff like that! but dont remember in germany we change evere some decade tv system so you need a new tv or a reciver ! i like to stop that but then wenn its all what make sence is on the same standart! you can run you 3 phase maschines on 60 there is no problem! on 59 the motors spinn a littel bit slower ans sucks a littel bit more current! but it still works. there a only few maschines they cant handel it.. to step the problem down i like to get 55hz ! every 10 jears 1 hz to the goal! for the frequency i take dekades of time! and after that i like to see stuff they build so well that is not nececery to replace after several jears! i dont like the economic and money system but even people they belive in that have to understand so i create new work places! look what germany do to create working places! they force people to by new shit lamps fillid with mercury :(( they will force people to fuckig electric cars!!! i am not good in english but i have some kwonlege about physiks! electric cars are more worse for healty and envioment than they technolegie we use today! even a man from chemyestrie proof it to me! we isulated old buildings and some architects tell me the homes suck less heating energy but they get mold. than we can replace the listed building to a new! industries and comercials renovate every few jears. custumers of the factory i worked for 11 jears replace there full maschine park after 2 jears. they dont care if the maschines work perfectly! i worked also a time for desy xfel ( hight energy physiks nuklear reserch... ) and i see how long stuff can used wenn its well made! so its possible but we dont do it! what i like to change is the unnececary replacmend to a replacemend were everyone have somthing from ti! after unite electric system we can produce to less the price because we dont need so many different stuff!

  • @BAEX2013G
    @BAEX2013G 3 роки тому

    Really good explanation!

  • @CrpisC-ios222
    @CrpisC-ios222 6 років тому

    so how do I get 208 v my tester , one line reads 120 the next reads 230 and the last 120 any idea why Im not reading 208

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому +1

      Are you measuring a single phase service?

    • @CrpisC-ios222
      @CrpisC-ios222 6 років тому

      yes two hot one ground .

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому +1

      A single phase system you will only see approximately two 120V legs and then 240V across both hots. You need a 3 phase service to get the 208.

  • @JoshHopkinsYT
    @JoshHopkinsYT 6 років тому

    So 240 is two phase 180 apart? Im a little confused. How do you wire that to a 240 plug? Two opposite phased hot wires, one neutral and one earth?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому +2

      It is not considered "two phase" it is commonly called "split phase". This is due to the way its wired at the transformer. There is one coil with a wire connected at the center, that is the neutral. If you where to look at each leg relative to the neutral line you will see two sine waves 180 degrees apart. If you just look at the voltage from one hot to the other hot you will get 240V. A 240 volt plug typically has just the two hot wires and a ground. Some will have a 4 wire connection with both hot wires, neutral, and ground. These are for devices that need both 240V and 120V.

    • @stephenbender7593
      @stephenbender7593 5 років тому

      @@AtManUnlimitedMachining But for 240V your graph showed two phases at a single point in time.

    • @carultch
      @carultch 4 роки тому +1

      @@stephenbender7593 That's a "coincidence". You can arrive at a 120/240V system, either with a 180 degree phase shift, or you can arrive at it, by negating your first 120V waveform. In terms of how it is produced in practice, it is produced by negating the first waveform. It produces two equal and opposite waveforms, that happen to mathematically be the same thing as two waveforms that are 180 degrees out of phase.
      It is really produced by center-tapping the 240V waveform, and defining the center at zero.

    • @carultch
      @carultch 4 роки тому +1

      @@stephenbender7593 In theory, you could produce the same 120/240 split phase system, with two actual phases, analogous to the way 3-phase power is produced. But we just don't do that in reality, as there is no practical reason for doing so.
      Three phase power is produced when there are three (or a multiple of 3) magnets interacting with a coil of wire, within the rotating machinery we call a generator. The 3 coils get a voltage induced at three different positions within the cycle, because they are spaced around the circle of the generator rotor's travel path, and pick up a different portion of the magnetic-electric interaction cycle. You could do the same thing by replacing 3 with 2, and make a system mathematically the same as a split phase system.

  • @thmpreservation
    @thmpreservation 4 роки тому

    👍 great explanation

  • @kalungalango4380
    @kalungalango4380 6 років тому

    What should the voltage be from line to line on a 120/208 3 phase? From line to ground I'm getting 122ish which seems normal but from line to line (a-b) (a-c) (b-c) I'm getting 199 - 201V .. what would cause this ?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому

      Line to line, 208, line to neutral, 120. Not sure what would cause high leg voltage with a low line voltage. Is your meter ok? It does not max out at 200 Vrms?

    • @kalungalango4380
      @kalungalango4380 6 років тому

      At-Man Unlimited Machining yes it's a 208/120 wye not 120/240 delta with 208 highleg delta. I tried with 3 meters brother and also on a 480/277 to make sure wasn't meter and from line side of disconnect because the problem started at a merry go round so I checked panel then disconnect. Could it be from transformer providing power? But if that's the case why am I getting 120 from each line to ground and only 199-202 from line to line?

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому

      Only thing I can think of is a phasing issue, maybe power factor is really screwed up?

    • @kalungalango4380
      @kalungalango4380 6 років тому

      At-Man Unlimited Machining idk we shall see haha I'll let you know when I figure it out. Thanks for the info btw

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  6 років тому

      No problem, please share when you figure it out, certainly a strange one.

  • @mmaad2165
    @mmaad2165 5 років тому

    Thank you
    Can you please describe the secondary windings of the transformer, is it a single windings or tow windings that winded in opposite directions???

    • @AtManUnlimitedMachining
      @AtManUnlimitedMachining  5 років тому +1

      A 3 phase transformer will have 3 windings that share a central core

    • @Do_the_Dishes
      @Do_the_Dishes 4 роки тому

      Concerning the secondary windings of the pole transformer. During manufacturing, when the reach the center tap, the begin to wind it in the opposite direction. This is how they get the phase to split the best I can tell.

    • @Do_the_Dishes
      @Do_the_Dishes 4 роки тому

      At-Man Unlimited Machining: That is true for a wye configuration but not a delta right?

    • @carultch
      @carultch 4 роки тому

      @@Do_the_Dishes No, that's not how it works. They continue winding it in the same direction, but provide an access terminal in the middle of the group.
      Suppose the utility distribution voltage is 12kV, just to get a semi-realistic value that will make the numbers easy for us. That is 50 times the 240V that we desire for each residential service. To build the transformer that generates 120/240V from this primary, it would be built as follows.
      The primary coil needs 50 times as many windings as the secondary coil. Let's suppose the primary coil has 1000 windings, corresponding to 12kV. This would mean, the secondary coil has 20 windings in total, corresponding to 240V.
      The secondary coil has all 20 windings in the same direction, around the same core. In order to split it for our neutral, after 10 windings, we cut the insulation, and we terminate the first half of the coil. Then we resume winding the coil in the same direction, as if we had never stopped in the first place. All 20 windings correspond to 240V, and each group of 10 windings corresponds to 120V.