Dirty Secret about the New 2024 Romex Wire Colors

Поділитися
Вставка
  • Опубліковано 3 січ 2025

КОМЕНТАРІ • 653

  • @SilverCymbal
    @SilverCymbal  2 місяці тому +60

    Thank you for watching - Hope you found this interesting!

    • @John-Smith02
      @John-Smith02 2 місяці тому +2

      1. Heads up. Apparently the bots who comment names to try and see the personal info are now just straight up saying random numbers and addresses, which if true, lends credence to the theory that they're trying to find personally identifiable information about the UA-cam channel. I can't confirm it because I don't think I've seen them comment street names, just people names.
      2. Do you do research on these topics or do you just know these or worked as an electrician or handyman? How do you know all this info, from gardening to electrical, etc.

    • @InconsistentManner
      @InconsistentManner Місяць тому +1

      14/2 w/ground, 12/2 w/ground, 12/3 w/ground, Etc. is Romex nomenclature just a little fyi for you. i have a 1000ft reel of 14/2 with no ground that is topped with tempered glass as my coffee table. Has about 300 or so feet left and the story is my uncle is a commercial master electrician and he left it at my dads house in 95/96. dad was going to scrap it in 2002 but I said id use it as a coffee table in my first home. almost everyone loves it.

    • @JohnCap523
      @JohnCap523 24 дні тому

      😂

    • @leeames9063
      @leeames9063 23 дні тому

      I was really hoping that the different color wiring was so I could designate one color for the kitchen, another color for the bathroom, and so on. Then when I need to troubleshoot an issue say in the kitchen, I can just look for the color wire for the kitchen.
      Oh well

    • @JohnCap523
      @JohnCap523 23 дні тому

      @@leeames9063 Yea, that way it decorates at the same time… 😜

  • @adamdejesus4017
    @adamdejesus4017 2 місяці тому +152

    ROMEX got the trade name from Rome, NY where it was first produced. Rome, NY is known as the "Copper City" because it had copper mills for making wires and Revere copper cookware.

    • @deadmanswife3625
      @deadmanswife3625 2 місяці тому +7

      And it's important because I have to pass through there when going up to the Adirondacks to get away for a month

    • @bahrben
      @bahrben Місяць тому +4

      I grew up in Rome and had no idea about the Romex connection. Thanks!

    • @mrgcav
      @mrgcav Місяць тому +1

      Sounds fishy to me. Prove it. Did NM cable come from New Mexico ??? What about BX cable ???

    • @jamesalles139
      @jamesalles139 Місяць тому

      @@mrgcav have you ever fished a cable through a wall cavity?

  • @pipisugbo
    @pipisugbo 2 місяці тому +647

    Noted - only use wire dated 10+ years old before doing my illegal DIY projects 🤣

    • @dwayne7356
      @dwayne7356 2 місяці тому

      A new market for thieves stealing copper from houses. Selling old dated wire to DYI-ers.

    • @tankerkiller125
      @tankerkiller125 2 місяці тому +40

      Was going to say, gatta get out and buy me some wire, so that when I do have a project 6 years from now I'm already backdated 6 years.

    • @dickslocum
      @dickslocum 2 місяці тому +2

      @@tankerkiller125 I bought a 150 ft roll in 1989 when I bought the house. still have a bit left

    • @ggsmith48906
      @ggsmith48906 2 місяці тому +16

      Ha! Exactly! The only reason they do this is so an inspector can date the wire in your house and tell if you pulled a permit!

    • @BK-pc3ei
      @BK-pc3ei 2 місяці тому

      @@ggsmith48906 the new standard is for safety and more easier to understand

  • @Uvoted4this
    @Uvoted4this 2 місяці тому +188

    The key here is to go to garage sales and auctions and buy Old Wire with old dates. That way you're covered no matter what.

    • @vincentstragier6628
      @vincentstragier6628 2 місяці тому +16

      Or the respect the code...

    • @peterdog8754
      @peterdog8754 2 місяці тому +4

      I have a few thousand feet of NOS nm cable for just such a purpose. 😂

    • @iamnotpresent
      @iamnotpresent Місяць тому +16

      @@vincentstragier6628 It's not about respecting the code.. If everyone was allowed to do their own work, to code, that would be fine. But people aren't even allowed to work on their own homes in some places!

    • @FireHazardMan103
      @FireHazardMan103 Місяць тому

      Or just use a wet cloth and some rubbing.

    • @whermanntx
      @whermanntx Місяць тому +3

      @@FireHazardMan103name is fitting for the advise.

  • @thomasleahy3767
    @thomasleahy3767 2 місяці тому +148

    Good info. I am buying a roll of each size now, for all of my projects ten years from now

    • @iratashman7202
      @iratashman7202 2 місяці тому +6

      At least you’re young enough for that 😊

    • @diltzm
      @diltzm Місяць тому +3

      Eh just use mc lol

    • @lkeil84
      @lkeil84 Місяць тому +4

      Might be a good idea as wire will probably cost 5 times as much then any way.

    • @1puppetbike
      @1puppetbike Місяць тому +2

      Richie Rich

    • @jprevard
      @jprevard Місяць тому +1

      🤣🤣Super clever 🤭

  • @karenstein8261
    @karenstein8261 Місяць тому +32

    It’s time to give credit where it is due - AND to separate fact from fiction.
    We owe color-coded Romex to Rex Caufield, who wrote in Fine Homebuilding magazine that he used spray paint for his convenience in sorting wire coils on the job site. A few years later and Southwire started marketing colored Romex.
    Color coding is NOT required; it’s just marketing. A few years back, one contractor ordered his cables in a custom color, just to reduce job site theft.

    • @thedamash1
      @thedamash1 47 хвилин тому

      we've had colour coded wires in Canada for like 25 years. at least since 2000

  • @evancombs5159
    @evancombs5159 2 місяці тому +146

    I feel like instead of using a different color for the 3s they should have used the same color but stripped. Having a color represent a combination of two different concepts is mentally more difficult for humans than color representing a single concept and strips representing another concept. Although, I'm sure they chose just to use colors only because adding strips would make the manufacturing process more expensive.

    • @uzlonewolf
      @uzlonewolf 2 місяці тому +5

      I was just thinking the same thing.

    • @quantumleap359
      @quantumleap359 Місяць тому +11

      Striped wire has been in wide use in other applications for decades. A striped wire would really stand out without being gaudy. The stripe could also indicate the color of the traveler wire. Oh well, what's done is done. Great, to the point video!

    • @tompw3141
      @tompw3141 Місяць тому +11

      Striped wire is fundamentally different to make. The plastic is injected around the conductors in a continuous process.
      Changing to a different single colour just means loading in different plastic.
      Stripes would require a whole new machine and process.

    • @l00k4tstuff
      @l00k4tstuff Місяць тому

      With all the homes starting to have solar, generators, and backup circuits, it seams to me some type of indicator would be helpful, too.
      As to striping the outside, as long as it's a longitudinal stripe, I can see how that will be helpful (especially considering the line above) because in an enclosure only an inch or so of outer jacket will be visible, and that's where the additional identification will be important.

    • @evancombs5159
      @evancombs5159 Місяць тому +3

      @@l00k4tstuff wiring I've seen that used stripes usually use diagonal stripes, so that is what I was imagining.

  • @shaneanderson1229
    @shaneanderson1229 Місяць тому +24

    I think the extra colors are a great idea. Just a hint for the DIY types, nail polish remover on a rag will wipe that printed date off the cable without bothering the jacket itself. You know, just for curiosity’s sake.

    • @Warhawk94
      @Warhawk94 7 днів тому +3

      Because a missing date won’t set off red flags to an inspector.
      Also, you gonna wipe off the date on the entire 200 foot run?

    • @Browniiie92
      @Browniiie92 2 дні тому +1

      ​@@Warhawk94 yes

  • @colinleslie2458
    @colinleslie2458 2 місяці тому +32

    At least some companies have been printing manufactured dates for quite a while. It was one of the ways I figured out which circuits were run several years after our house was originally built during one of the early homeowner remodels.

  • @95dodgev10
    @95dodgev10 2 місяці тому +49

    I'm glad they kept the common ones like 12/2 the same. I've been rewiring my house slowly so by keeping the 2 conductor wire colors the same that means my house won't be some weird hybrid caught in the middle of a major industry change

    • @someonerandom704
      @someonerandom704 Місяць тому

      are you following the national electric code though?

    • @95dodgev10
      @95dodgev10 Місяць тому +2

      @someonerandom704 I'm sure there's a few things I've done wrong like improper stapling or whatever. But when it comes to critical stuff I've been doing my best to either research it myself or I talk to my buddy that's an electrician. The work I've done so far is 100 times better than some of the sketchy crap I've found. The original work was done well for the time but any electrical tape and the fabric wire coating is all degraded. The diy stuff that was done was anywhere from poorly done to 1 step away from a fire hazard. One example was a 14g wire ran off a 20 amp breaker and that's one of the less sketchy things. Almost no junction box has a cover, some wires were ran into the box through the cover opening and only twisted and taped.

    • @not2tired
      @not2tired 9 днів тому

      FWIW Our civilization is some weird hybrid caught in a major industry change. So on occasions when it can't be avoided, what's one more frankenhouse?

  • @edwardconley5250
    @edwardconley5250 2 місяці тому +48

    I've been seeing some of these new colors at my local Menards, and wondered what was going on. Thanks as always for the great information!

    • @ChessIsJustAGame
      @ChessIsJustAGame 2 місяці тому +5

      Yep, same here. Wondered if it was some new "wokeness" stuff going on.

    • @jankington216
      @jankington216 Місяць тому +5

      ​@@ChessIsJustAGamewoke is when you know your rights and how the government works, what are you on about?

    • @ProleDaddy
      @ProleDaddy Місяць тому +3

      ​​@@jankington216 God, there's so many bootlicking troglodytes out there. Thank you for not being one.

    • @JohnQPublic345
      @JohnQPublic345 11 днів тому

      Menard's is THE BEST DIY store ! since moving to the west coast, i only have lowes or depot

  • @user-em6ie2be7x
    @user-em6ie2be7x 2 місяці тому +91

    Appreciate the information I've only ever seen Yellow & White Romex.

    • @deadmanswife3625
      @deadmanswife3625 2 місяці тому +4

      And gray for my flagpole lights

    • @deadmanswife3625
      @deadmanswife3625 2 місяці тому +2

      Oh yeah and I have orange on my water heater and my baseboard heaters on the porch

    • @steveurbach3093
      @steveurbach3093 2 місяці тому +1

      I have some pale blue 14/2 w/g from quite a while ago.

    • @gtbkts
      @gtbkts 2 місяці тому

      There's a pink wire that has 240 running through it to hook up my water heater. I don't know the rating on it. I should probably check it out😅

    • @lkeil84
      @lkeil84 Місяць тому

      That has, been since 2001 and there is orange for #10 wire, but not used often except for a dryer perhaps.

  • @GroovyGrandpa2
    @GroovyGrandpa2 28 днів тому +19

    They should make them smell like different fruits too, For us blind electricians. 😊

    • @nephilimshammer9567
      @nephilimshammer9567 7 днів тому

      They do. Also the conduit when cut smells like delicious

    • @jamiemorgan4146
      @jamiemorgan4146 День тому

      Even Better… Taste like the color! Maybe the inspector will lick it….

  • @2mustange
    @2mustange 2 місяці тому +47

    The trick with DIYing your own electrical is to do it right so if anyone questions you then you pull a permit to have it reviewed for after the fact

    • @Demopans5990
      @Demopans5990 Місяць тому +5

      Which leads to a second point. Pay now for the experience, or pay later after one of the cheap contractors botches the job again

    • @scottwhitcher265
      @scottwhitcher265 Місяць тому +13

      "Permit" implies that someone has the right to deny me to do what I have the right to do.

    • @rich7447
      @rich7447 Місяць тому +11

      @@Demopans5990 It's not that simple. I graduated from Electrical and Computer Engineering and am qualified to design powerplants in the state that I reside. However, I am not qualified to change out a receptacle in my own home. Do you see the issue?

    • @dallas5374
      @dallas5374 Місяць тому

      @@rich7447nope

    • @busnorth
      @busnorth Місяць тому +2

      I'm also a commerce electrical engineer architect. I draw it on papper. Do the math. But can't do my own work.

  • @jrob8931
    @jrob8931 2 місяці тому +41

    Nice job! Especially with your on-camera work: You look very confident and comfortable and natural facing the camera, which is not easy. Thanks for another great video.

    • @SilverCymbal
      @SilverCymbal  2 місяці тому +8

      Thank you for the nice word,s I really appreciate it

  • @themagiccoasterlover
    @themagiccoasterlover 2 місяці тому +56

    Manufacturer's putting dates in cables is a big reason theres a market for old cable. People will buy it up, sit on it for years and sell it for a marked up price to people looking to do home renovations.

    • @billrobert3226
      @billrobert3226 Місяць тому +3

      Aint no way you have a source on that info

    • @rightwingsafetysquad9872
      @rightwingsafetysquad9872 Місяць тому +9

      Source, experience. People tend to not write stuff down when they know they're trying to break the law.

    • @homestar92
      @homestar92 Місяць тому +4

      Can't really mark it up too much though - if the wire is so expensive that it's suddenly worth pulling a permit then the market for the old wire goes away.

    • @EnthalpyUplusPV
      @EnthalpyUplusPV Місяць тому +3

      Why would you go through the trouble of buying old wire from sketchy sources so you can wire your house wrong and maybe burn it down rather than just do it right?

  • @dwayne7356
    @dwayne7356 2 місяці тому +15

    Prior to 2024, the color was up to the manufacturer. I believe it is not in the NEC yet and is just a manufacturing thing. I had installed a baby blue 12 AWG in my house in the late 1980s. If you have a house built before 2024, do not trust the wire color without verifying the actual wire gauge. Color standardization did start until the 1990s on some wire gauges. Be careful.

  • @kennysboat4432
    @kennysboat4432 2 місяці тому +75

    Here's what not being able to pass inspection on diy work does: it makes it so people don't get inspected.

    • @TwilightxKnight13
      @TwilightxKnight13 Місяць тому +7

      As a retired master electrician, in my experience, only licensed professional electricians regularly obtain permits which is when the local inspector gets involved. More often than not, if the work can be done fairly quietly, handymen and DiYers don't get permits and thus never inspected. Plenty of kitchen renovations being done everyday without a permit or an inspection. I'm not saying its right, just that it happens. If you are careful, you can even replace a live service panel on your own and no one is the wiser. Of course if you have to get the local power company involved like increasing a service, say from 100amp to 200 amp, they will insist on an inspection before they will restore power.

    • @cch201992
      @cch201992 Місяць тому +1

      @@TwilightxKnight13i just added a 70 amp breaker and a 50amp breaker on my 200amp service on 8/3 no permits👀 70amp for EV charger and 50 amp for welder. It's my understanding if it's the homeowner doing the work no permits are required🤷🏼‍♂️

    • @SimonBarsinister
      @SimonBarsinister 27 днів тому

      ​@cch201992 Usually depends on the municipality. I've lived in municipalities that allowed you to do the work yourself and others that do not.

    • @palfruswyrmrest8321
      @palfruswyrmrest8321 25 днів тому

      @@cch201992 I don't know if permits are not required for homeowner-done work, but they are highly recommended. Some code requirements are not critical, such as the number of outlets on a kitchen counter wider than 11 inches, and some are, such as requiring a dedicated ground wire on a 300 foot long, 100 amp sub-panel to my barn. Fortunately, I asked several people at HD and the second guy gave me the correct information. Had that been an inspector, everything I did would have been closely inspected.

    • @rakashaagain
      @rakashaagain 25 днів тому +1

      @@TwilightxKnight13 I do most of my reno and electrical work, even replace breaker in my breaker box. It's easy and code is easy to read.

  • @OldLordSpeedy
    @OldLordSpeedy День тому +1

    Internationally we count all cable wires plus ground. So are typical 3G (G markes ground international saved earth with coded green/yellow.) and 5G. Typical use 1.5 mm² and 2.5 mm², for feed in into house 6 mm² and 10 mm². The range starts at 0.75 mm² for LED-lamps, over 1 mm², 1.5 mm², 2.5 mm², 4 mm², 6 mm², 10 mm², 16 mm², ... For house and factory buildings only copper wires allowed, only for outside the electrical company can use aluminium cables.

  • @danielotoole72
    @danielotoole72 Місяць тому +9

    A striped jacket indicating x/3 would have been better than 10,000 different colors. Thanks for the video. As a DIYer I saw the blue at Home Depot and thought they were just trying to differentiate from Lowes or something. Was only wiring up a closet light, so didn't investigate further.

    • @barryb3476
      @barryb3476 25 днів тому

      SouthWire and CerroWire manufacturer for both Mendards and Home Depot. Neither change their color for the distributors. Now, CerroWire does supply to other companies that have standard colors they use for their installations. Like a purple 10/3.

    • @palfruswyrmrest8321
      @palfruswyrmrest8321 25 днів тому

      Your stripe idea makes the most sense, but probably costs more to implement. The idea of one color per gauge is logical, I doubt the number of conductors is of the same interest to an inspector

  • @onecrazywheel
    @onecrazywheel 2 місяці тому +17

    Manufacturing Dates many times have been on NM cables for 20-30 years. I have beeen an electrician for 2 decades and all of Southwire Romex cable jackets have had dates. Even MC (Metal Clad) cable has inside clear ribbon manufacturing dates and wording on the inside ran with the conductors. Great video. I think it was Canada who first started using these colors many years ago. I would see the blue and pink NM cables in videos and found out that is what they would require up there. Im from Florida.😊
    Im an electrician in a hospital. We use AC cable all the time. Similar to MC cable snd it has a green jacket. It show that it is Healthcare Rated. We can use it in a Healthcare Facility then. 😅
    Great video. God bless.
    Jeff - Sunny Central Florida ☀️🙏

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому

      Lol yes the blue NM was to identify afci for bedroom circuits. There is some of that NM with 2pair and a bare... for gfi recepticals? Idk two circuits, because no neutral sharing... it makes the combos trip😂.

    • @john-hughboyd233
      @john-hughboyd233 Місяць тому

      The US has been copying the Canadian Electrical Code CSA C22.1 Part 1 for years

  • @danrich6448
    @danrich6448 2 місяці тому +11

    You can also buy a 14-2-2 wire that has 4 conductors (black, red, and 2 whites) and a ground. The jacket is white. 12-2-2 is also available and is yellow. Great for running 2 arc fault circuits together.

  • @richardb2795
    @richardb2795 2 місяці тому +5

    I work as a residential electrician. The first time I’ve seen blue 14/3 romex cable at our shop was last month. We are still going though our previous pallet of white 14/3. We have been using pink 10/3 for many months now but the brand we use is different from that shown in this videos.

  • @elitearbor
    @elitearbor Місяць тому +3

    Short, sweet, to the point, and nothing to draw it way out in time. Well done video!

  • @N20Joe
    @N20Joe Місяць тому +6

    I've seen customers get busted using new wire and claiming an old project a few times now. I might just buy up a few rolls and sit on them for when I do projects in my own house now!

  • @dcf8978
    @dcf8978 2 місяці тому +13

    New flavors???!?!? O was getting tired of Vanilla and Lemon... finally someone has answered my prayers!!

  • @igfoobar
    @igfoobar 2 місяці тому +17

    So the take home message is: buy plain THHN and put it in conduit! :)

    • @AtomicHermit
      @AtomicHermit 2 місяці тому +5

      It is dated too, but hard to read inside a conduit - which is also date stamped.

    • @Recreationaltrespasser
      @Recreationaltrespasser Місяць тому +5

      Date stickered, which should be installed facing the wall for aesthetic purposes

    • @theodorgiosan2570
      @theodorgiosan2570 Місяць тому +3

      Or use MC/BX.

    • @jamesherrin3655
      @jamesherrin3655 Місяць тому

      Cannot put Romex in conduit. Especially in the ground.

    • @davisladd6473
      @davisladd6473 Місяць тому +1

      Conduit has a date on it as well.

  • @johnbeaudin
    @johnbeaudin 25 днів тому +1

    I'm not somebody likely to do this kind of work, but I was very entertained and educated by this excellent video.

  • @TowerThree
    @TowerThree 2 місяці тому +24

    The new colors for the /3 is so the inspectors can see it for switches. All new switches need a neutral in the box, so no more
    /2 to a switch

    • @foogod4237
      @foogod4237 2 місяці тому +2

      It can also help to identify 240V circuits, and feeder circuits with a shared neutral, as being something different than the ordinary outlet/light circuit runs...

    • @KaiserTom
      @KaiserTom 2 місяці тому +5

      You can do 2 conductor for a switch, you just need to feed the switch then the light. You also only need one switch in a lighting circuit to have a neutral, so the 2nd switch on a 3 way can be line, traveler, and switched hot and not need a neutral.

    • @billrobert3226
      @billrobert3226 Місяць тому

      Remember there are many exceptions to the nuetral in a switchbox rule. anything with conduit, and if more than one switch controls a light and the boxes are within sight of eachother, only one needs a neutral

    • @billrobert3226
      @billrobert3226 Місяць тому +1

      ​@foogod4237 unless it's a 2 wire 240! Although that is less common in modern appliances, i still haven't seen a 240 water heater with a nuetral and I would assume that would be the case unless you have some fancy water heater with built in electronics like a screen or wifi

    • @1djbecker
      @1djbecker Місяць тому

      @@billrobert3226 Older appliances used 120V for lights, motors, timers and controls. With LED lighting, inverter-driven motors and world-compatible electronic controls is is easy to foresee a day when there won't be a need for a neutral on the dryer and range circuits either.

  • @user-hm5zb1qn6g
    @user-hm5zb1qn6g 2 місяці тому +4

    Excellent, informative, no-nonsense video presentation.

  • @vikingranch6377
    @vikingranch6377 2 місяці тому +4

    Nice rundown, I’d noticed the change, but hadn’t realized that they weren’t just brand coloring

  • @pfcrow
    @pfcrow Місяць тому +2

    Thanks. I was wondering why all the Romex in my house was white, regardless of whether it was a 15A or 20A circuit. I had thought they had messed up, but now I see that it's simply that the wiring predates the introduction of yellow (just barely). Thanks!

  • @ericbaker8807
    @ericbaker8807 2 місяці тому +2

    Used the pink 10-3 to run a new dryer line at my grandparents house recently. I was pretty confused initially when I went to Lowe's to pick up some wire haha. Didn't know they changed color until I googled it.

  • @bjportnoy
    @bjportnoy 2 місяці тому +31

    4:32 snitches get stitches

  • @Species-lj8wh
    @Species-lj8wh 2 місяці тому +4

    Glad homeowners can do there own electrical work in my state. Still need inspections and to follow 2013 IECC codebook.

  • @Brian-Burke
    @Brian-Burke 2 місяці тому +15

    I had no idea Southwire owned Romex. Great video and good info. Thank you.

    • @SilverCymbal
      @SilverCymbal  2 місяці тому +11

      Of all the products I use, wire is so important. I just messed with some 40 year old outdoor boxes, and having the wire still be pliable and not fall apart shows how important the quality of this stuff is.

    • @Brian-Burke
      @Brian-Burke 2 місяці тому +2

      @@SilverCymbal Agreed. I'm big on paying more for quality and reputable brand names.

  • @StevenSokulski
    @StevenSokulski 4 дні тому

    Very interesting. In my home town, the major electrical contractor for new construction had so much Romex stolen that they started ordering theirs with custom colored and labeled jackets. Basically it was a way to easily prove the providence of the cable to the cops so that the contractor didn't have to work too hard to prove that it had been stolen.

  • @VideoArchiveGuy
    @VideoArchiveGuy Місяць тому +1

    Mental note to Sharpie over the date on the cables. 🤣

  • @ClubhouseGardens
    @ClubhouseGardens 24 дні тому

    This is amazing for a DIY guy because it empowers me to make sure i know what I'm doing before I do a project.

  • @durvius2657
    @durvius2657 2 місяці тому +10

    Honestly this is really cool. Even the dated wire. I'm a fan of easily accessible transparency.

  • @gnic76
    @gnic76 2 місяці тому +5

    So be sure to keep an extra roll of wire around for later work, just so you can pass it off as old work. 😂

  • @toTheWatcher
    @toTheWatcher 2 місяці тому +1

    Super helpful and honesty a change that has been needed for a long time

  • @karlbrundage7472
    @karlbrundage7472 Місяць тому +4

    Fortunately for me, I live in a county that doesn't require inspections beyond the construction- electric meter-base and the septic tank and drain-field.
    I wired my house with 12-2 throughout, except for the kitchen range and the hot-water tank. I like to over-build and I was tired of having the lights dim in my older home whenever someone turned on a hair dryer.
    My advice: Upgrade your wiring. You won't regret it...............................

    • @greggv8
      @greggv8 22 дні тому +1

      No 14 gauge for my home wiring. I have a huge roll of yellow jacket 12/2 that I picked up for $60 at a yard sale years ago. Can't go wrong using 12 gauge on 15 amp circuits. Ensures an extra safety margin. I've heard there's an addition to the NEC for 16 gauge wire that's exclusively for circuits that only have LED lights, but nobody makes 16 gauge yet.
      Replacing all your incandescent lights with LEDs will cut your power bill *and* reduce the load on your wiring.

  • @RedHuntsman
    @RedHuntsman Місяць тому +2

    I bought and new custom home in 2010 and I noticed that all the wire was yellow except for heavier gauge wire. They had wired the entire house without any 15amp circuits. I never blew a breaker in that home.

  • @davemeise2192
    @davemeise2192 Місяць тому

    Good explanation. I wondered what the new colours were all about at our local Home Depot. I couldn't get consistent answers from staff.

  • @user-tv5dt3nm9y
    @user-tv5dt3nm9y 2 місяці тому +3

    Which one has glow in the dark sheath?

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому

      Copper clad by the sea...give it a few years, it glows. Maybe AFI can make it safe? I don't care for it, cu is not that much more....

  • @JohnQPublic345
    @JohnQPublic345 11 днів тому

    its about time! ive been an electrician since 1996. yes, i can tell the gauge just by looking at the wire, but color-coding is a great idea.
    i just discovered that they make 12 / 2 / 2 (two sets of hot, 2 sets of neutral) romex

  • @everettgreenwood4338
    @everettgreenwood4338 5 днів тому

    I used to be an electrician, and plenty of wire brands already have manufacture dates on them and they are fairly common in my area

  • @davidbowser
    @davidbowser Місяць тому

    Depending on the age of your home, BX might also be ungrounded (old 2 prong outlets). Almost all the BX in my house is ungrounded and I have been slowly replacing it or running ground wires when replacing outlets and light fixtures.

  • @danlux4954
    @danlux4954 Місяць тому +1

    2:37 google shows in Canada. This blue NMD 90 14/2 wire is coded for bedroom outlets terminating at Arc Fault Circuit Interrupters (AFCI).

  • @munozinni
    @munozinni 2 місяці тому +3

    Hola 👋 señor Silver Cymbal 👋😃👋that was a great video very informative and for a minute what I thought when I saw the pink wire I thought the lgtv is sticking its nose in the electrical industry now 😩😫that’ll stink to deal with that but fortunately it’s all for identification only thank you for the information keep up the great content…Saludos!!!👋😃👋

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому +1

      Saludos, el arcoiris... se lo llevaron como bandera...y pintaron los cables...😮.

  • @rickhobbs3313
    @rickhobbs3313 24 дні тому

    I work at a local Lowe’s in their Electrical & Lighting department. Yes, we are stocking the new color coded wire by Southwest wire.
    I admit that I came from the alarm industry, I’ve never been or worked as an electrical contractor and I always tell customers to check with an electrician because not one. I’m learning a lot from this and different videos.
    That being said, I understood you to say that xx/3 w/ground has a the third (usually red) conductor as a traveler for applications that have multiple switches. May I now see it schematically how that is. However, I thought that a three conductor w/ ground was for specifically a 220VAC circuit. Someone said to me that a 220 circuit was wired in old homes with a two conductor W/ground. How is that possible? Is the ground being used as a neutral wire? Thank you for allowing me to as this question.
    If you have another video that explains it, please note it.

  • @jessegarman7899
    @jessegarman7899 Місяць тому

    I appreciate coming across your video. I will be doing a new house build in about six months and it never occurred to me. That yellow was for 12 gauge. I am specifying 20 amp circuit solved throughout the house and I wanna make sure that that is what happens.

  • @scratchdog2216
    @scratchdog2216 Місяць тому +1

    Honestly thought this post was intended as a humorous poke in the ribs at certain aspects of modern culture. Fortunate to have lots of old wire in the trade here for our own use. This all makes complete sense from an inspection POV.

  • @HayesJC
    @HayesJC Місяць тому

    Lots of DIY projects out there getting called by inspectors. I just inspected a place with only 12/2 wire on every light and outlet. 20+ junction boxes in the attic and 15 in the basement. Only a handful of 20A breakers.
    Wire color makes inspecting things like this so easy.

  • @MIGHTYX2010
    @MIGHTYX2010 2 дні тому +2

    Dumb my opinion when they went to three conductor they should have just put a line or a stripe ring around the same color indicating that it just had a third conductor in the wire not a completely new color

  • @MCW1955
    @MCW1955 2 місяці тому +2

    A very professional video.

  • @matgaragepaul
    @matgaragepaul 14 днів тому

    When I built my detached garage a few years ago, (2018) I ran 12/2 for the 110v circuits, and 12/3 for some light duty 20 amp 220V circuits (VFD's for a couple little 3 phase machines). As I recall, the 12/3 cost almost twice as much, but only has 1 additional wire. Ouch. I did pull permits and get all inspections (rough in and final). Cost a few bucks, but alot cheaper than any issues that would come up if something were to happen, or when I sell this place. Plus I take pride in the inspection stickers. I did my homework, and passed inspection on the first visit.

  • @richardlea818
    @richardlea818 Місяць тому +6

    I just ran into this going to buy some 12/3 the other day. They’re charging roughly double for the fancy new purple coating. Neat.

    • @Enlightn76
      @Enlightn76 Місяць тому

      incorrect. They are charging nearly double for the 1 addtional conductor. been this way for a decade or more regardless of color.

    • @richardlea818
      @richardlea818 Місяць тому

      @@Enlightn76 obviously 3 wire is more expensive than 2 wire, but i paid $55 dollars for a run that only cost $35 ish dollars a few months ago. I’ve bought wire before man

    • @dallas5374
      @dallas5374 Місяць тому +1

      Bidenomics

  • @rolandsolomon7728
    @rolandsolomon7728 2 місяці тому

    Thanks for the detailed, yet simple explanations.

  • @jeremywatts2768
    @jeremywatts2768 2 місяці тому +3

    Its nice that you dont have to break out the micrometer to ensure that its 14 (1.66mm) or 12ga (2.06mm)

    • @hamjudo
      @hamjudo Місяць тому

      Micrometers are way to fiddly. I just use a milliohm meter, a tape measure, and a calculator.
      A regular ohm meter has two test leads with one conductor each. They suffer because they have to subtract out the resistance of the test lead itself. A milliohm meter runs a known current through one conductor to each test probe and has a sense wire to measure the voltage at the test probe. These are sometimes called 4 wire meters.
      The fancy versions let you choose the test current, so you can overwhelm noise from magnetic or capacitive coupling, or use a wee tiny current if something sensitive might come in contact with the conductor under test.
      Oh wait, that's for testing traces on printed circuit boards. For house wiring, I look at the color, read the label, or compare the wire to a known sample. It's a good thing I only do wiring on my own property.

    • @ps.2
      @ps.2 Місяць тому

      Or you can just try to bend it. You cannot possibly confuse the two then, as 14ga is soooo much more flexible it's not even funny. As an amateur, when working with 12ga wire for switches or receptacles, I almost dread stuffing the excess into the box while closing it up. Whereas with 14ga it's simply never an issue.

    • @jeremywatts2768
      @jeremywatts2768 Місяць тому

      @@ps.2 If you saw the thick sheathing on the conductors and casing for my wire, you'd question it too.

    • @syitiger9072
      @syitiger9072 Місяць тому

      U can easily tell the difference between 14 and 12

  • @famitory
    @famitory 2 місяці тому +2

    would be nice to see an official sollution for running the 10v control signals for dimmable LED lights in paralell with the power inside one cable.

    • @SilverCymbal
      @SilverCymbal  2 місяці тому +1

      I agree, I worry also for the folks that ran pink for low voltage data cabling as this may create some confusion there too

  • @imark7777777
    @imark7777777 Місяць тому +1

    I'm glad they did it but I was definitely shocked to see the bold color choices.

    • @syitiger9072
      @syitiger9072 Місяць тому

      Lol thought the wire manufacturer went woke

  • @bluenetmarketing
    @bluenetmarketing Місяць тому +1

    Great information! Thanks.

  • @kliajesal4592
    @kliajesal4592 13 днів тому

    Aspiring Sparky here. Thank goodness for color coding!

  • @lezzistarsmith
    @lezzistarsmith Місяць тому +1

    Finally! Make some damn good sense, glad industry stepped up & likely to be code enforced

  • @busnorth
    @busnorth Місяць тому

    I like this idea. Trouble is, in the 60 they had blue and black with white. I don't remember the gauge but I did use a lot of the sky blue. Every room had it's own 15,20 amp breaker and lights were shared. Some rooms had more then one lights on separate wires and yes 2 light switch. There were many dedicated individuals circuits. At least 5 plug boxes pre room. I'd help my dad after school wire new homes and insulate then sheet rock with nails.

  • @BigD1395
    @BigD1395 2 місяці тому

    Very informative, I've never done a lot of electrical work but it's nice to know now that we own our own home.

  • @HelloKittyFanMan
    @HelloKittyFanMan Місяць тому

    Cool video, thanks. I didn't know about the colors past yellow. Even just 4 years ago in 2020 I bought a bit of 12/3 that was still in the yellow sheathe.

  • @senseijay51
    @senseijay51 Місяць тому

    I remember installing some other colors back in the 80s. Notably, there was a light blue NM 14 ga if I recall.

  • @claymeister00
    @claymeister00 2 місяці тому +3

    we also have Red romex for Electric heat The conductors are red and Black. it is the same colour whether its 12/2 or 10/2.

    • @spikester
      @spikester 9 днів тому +1

      Yup, red romex 12/2 & 10/2 was commonly used to denote 240V split phase circuits, be it baseboards or water heaters. As early as the start of the 90s at least I recall. The white stuff was used for 120V.

  • @PerrySummers
    @PerrySummers Місяць тому

    First time seeing one of your videos.
    GREAT informational piece.
    Liked, and subscribed!

  • @Digital-Sparks
    @Digital-Sparks 10 днів тому

    This as others have mentioned is more for marketing than anything else, but also it would likely appeal to people who don't know what they are doing or know what they are looking at when trying to deduce whats going on with the electrical circuits they are looking at. As an Electrician who has worked in PLC cabinets with literally tens of thousands of wires that are all the same color seeing this is humorous to say the least. You got yourself some cute wire there my friend.

  • @joshm3342
    @joshm3342 2 місяці тому

    Essential info, well presented. Thanks!

  • @patrickfirst5614
    @patrickfirst5614 2 місяці тому +1

    Your content is always interesting and relevant. I as wondering, haven't they come out with 16/2, for lighting circuits? I thought I saw a video a few months ago, but the 16awg romex wasn't fully approved yet. I could be mistaken.

    • @greggv8
      @greggv8 22 дні тому +1

      For LED lighting circuits that only have lights.

  • @ChoiDuong0944
    @ChoiDuong0944 15 днів тому

    Very informative. Thank you.!

  • @scotteebee
    @scotteebee 2 місяці тому +3

    What about the new stuff coming out for 10A breakers?

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому

      Cat 5 with power! Cctv did a PoE system on cat5 12v would definitely smoke the rj45 plugs..😂. Led lighting .... probably 20 or 25 bulbs... and at that number I don't think that 10 Amp would trip....😮 😅 imo 14awg is small enough 😅😅...

  • @phildelgiudice3448
    @phildelgiudice3448 12 днів тому

    Nice job. Great channel too.

  • @mike95826
    @mike95826 2 місяці тому +1

    Didn't they also add "foot" markers to make it easier to know how much cable you had without having to measure? I have seen it on some kinds of cables but no sure it is on all NMC yet.

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому

      Ol coax rg6 on dss and rg59u on broadband....
      Obsolete now....fiber 🎉😊

    • @OldLordSpeedy
      @OldLordSpeedy День тому +1

      This I found on my old LAN cables from 1984 too. Typical for industry to count cable length equal in feets, inches, miles, or meter. So do you not need extra equipment for measuring at working places.

  • @BartlettTFD
    @BartlettTFD Місяць тому

    GREAT information. Thanks 👍

  • @Nudnik1
    @Nudnik1 7 годин тому

    Excellent idea 💡

  • @mattb9664
    @mattb9664 2 місяці тому +1

    I want to know more about changes to the actual AWG measurement...I have 14 AWG in white Romex jacketing throughout my 1975 house, but it seems like it's actually 12 AWG because of how stiff and durable it is. When I buy new White-Romex 14 AWG..it's extremely easy to work with and bends very very easily. Did they actually thin out 14 AWG while still being able to call it 14 AWG?

    • @jrherita
      @jrherita 2 місяці тому +1

      Is the old wire aluminum instead of copper, or actually 12 gauge?

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому +1

      ​@@jrheritathe older wire is stiffer, and the new is softer to work with... noticed the other day, a 50a range cord....2 # 8 and a pair of # 10 they used to be #10 on the 30a dryer plug... and #6 was what the stove took. 😮

  • @TwilightxKnight13
    @TwilightxKnight13 Місяць тому

    Orange for #10 has not always been dedicated. For years, orange was used primarily for UF - underground feeder - cable. It was a point of confusion for many homeowners and DiYers

  • @iceman9678
    @iceman9678 Місяць тому

    What will the 10amp wire color be? 🤔

  • @sparkydstoolboxtalk1024
    @sparkydstoolboxtalk1024 28 днів тому +1

    The cause for the change in color is less for inspection purposes, and more so Southwire can make more money. Inspectors are electricians, and electricians can visually identify a three wire from a two wire romex by eye. Southwire has a history of tweaking their products to try to get more sales, and the rest of the industry quickly follows. For example about twelve years ago Southwire star making sim-pull pre lubricated wire for use with conduit, which boosted their sales. These companies have no incentive to change unless it makes them more profitable, or building code changes.

  • @kimstockdale632
    @kimstockdale632 2 місяці тому +1

    14-2 includes 3 conductors, but the ground doesn't count. I should have known that, but didn't. Thank you for clarifying.

    • @syitiger9072
      @syitiger9072 Місяць тому

      Ground isn’t classified as a conductor

  • @annnnonnymous
    @annnnonnymous 2 місяці тому

    Quick and informative, good video.

  • @LethalMercury
    @LethalMercury Місяць тому

    I had heard that a 16 gauge cable had been approved for LED lighting on 10 amp circuits, is this true? And if so, what color would it be?

  • @rf159a
    @rf159a 2 місяці тому +1

    The metal jacketed cable is typically called MC Cable. BX Cable is generally old cable without a ground. They were permitted to use the jacket of the cable as a ground. That is no longer allowed and all MC Cable contains a ground wire.

    • @sqeekykleen49
      @sqeekykleen49 2 місяці тому

      Metal clad, yes, and then there is AC armored clad... bx was the transition from knob and tube... then NM came along.... 😊

  • @WackoMcGoose
    @WackoMcGoose Місяць тому

    Home Depot garden employee here, this explains quite a bit for when I have to help out in electrical! ...Still confused as to _why_ they don't count the ground wire in the number of conductors...

    • @theodorgiosan2570
      @theodorgiosan2570 Місяць тому +2

      Because it's not a CURRENT CARRYING conductor. It's only the ground (safety) so it should never normally be carrying current. Some manufacturers do say 14/3 w/ ground for instance. But originally the cables had no ground and were called whatever gauge/2 or /3. So when they added the ground they didn't change the name because that would confuse everyone buying wire.

    • @thelight3112
      @thelight3112 Місяць тому +2

      Because you can't use it for anything except grounding. A 12/2 wire can have a neutral and hot for 120V circuits, or two hots for 240V. You can't use the ground wire, for example, as a neutral to add a 120V outlet off of a 240V one.

  • @Rottwiler44
    @Rottwiler44 Місяць тому

    It’d be useful if there was something like this for 0-10v control cable for easy ID.

  • @RyanDuffy
    @RyanDuffy 2 місяці тому

    The X/3 wires are also used for lights with dimmers or smart switches.

  • @MrFiver1111
    @MrFiver1111 2 місяці тому +1

    In Spain they are black or white for normal and then the green is for halogen free and orange for fire resistance.
    The wire size is printed or engraved in the insulation in mm²

    • @OldLordSpeedy
      @OldLordSpeedy День тому +1

      In Spain they use only 2.5 mm² for most projects, just hob with 4 mm². All very over protective for sure after all other European countries use 2.5 mm² for hob and 1.5 mm² for sockets. 😂 We all have 230 volt only.
      My LED lamps use 0.75 mm² and 1 mm² normally. But these days are the copper prices mostly stable and it makes no difference if you use higher thicker copper wire as usual.

  • @SnowblindOtter
    @SnowblindOtter 29 днів тому

    As a former Southwire employee, I can say that from the distribution side the different colors were a godsend for quality and inventory control in the CSCs during the few months I actually got to handle them. Now if only they can do the same thing with the MC, NMC, and UT, nothing is more frustrating than a quality error because two nearly identical materials are sitting next to one another.

  • @ourv9603
    @ourv9603 Місяць тому

    All those new colors may be available but only for special order. My Home
    Depot only has the old tried & true White-Grey-Black & Yellow on the shelf.
    !

  • @ajbrant3296
    @ajbrant3296 29 днів тому

    In the past you used to be able to buy 2 conductor romex. Whenever I lookup pricing for romex I always specify w/g that insures that I am always getting a ground wire. It actually is how it is sold BTW.

  • @whochecksthis
    @whochecksthis 6 днів тому

    Another change to the 2023 NEC going forward is the introduction of 10 lighting circuits, and of course, there will be #16/2 and 16/3 NMC to go with it, and, yes, there will be distinct colors for that lighting wire. I think it’s a Carolina blue, for the two, and a similar purple for the three…

  • @matthewhuszarik4173
    @matthewhuszarik4173 25 днів тому

    Agree the different colors should have been for different amperage and then you can see how many wires it is at the end.

  • @theseattlejim
    @theseattlejim 2 місяці тому +1

    Keep up the good work

  • @brianbeasley7270
    @brianbeasley7270 Місяць тому

    Wow! That's informative. Thanks.