I was talking about inducer motor when it's connected to outlet run all time but when I connected to 120 v wires from furnace then run the inducer only runs about 12 seconds & pressure switchs are closing k
11 місяців тому+1
Have you checked how much voltage the inducer motor is getting from the control board? If it is low, then either there is a bad wire connection or the control board is bad. If the voltage is around 120v, then there is actually something wrong in the exhaust system. Have you watched this pressure switch video? It might give you more ideas of where to look: ua-cam.com/video/wqIVYlgUSyI/v-deo.htmlsi=4jvVJWpu3OKp2KK8
Hola una tus videos son muy buenos para aprender. Pero tengo una pregunta cuál es la temperatura que regularmente tiene que tener el termostato para saber si está calentando bien. ?
el inducer motor solo trabaja 10 Segundos y los pude parar con mis manos y Tengo el codigo de error un flash Todo el tiempo es un good man 2 stages sera que el inducer ya esta mal ? Gracias me alegraria tu respuesta feliz ano
Tengo un problema , la caldera cuando la enciendo marca error 2 , pero si saco la manguera del forzador y soplo al presostato me prende el forzador ,libera el gas y el chispero y arranca la caldera , donde puedo tener el problema ? En la plaqueta o en el presostato?
Cambia el presostato o donde antes de cambiarlo checa al final de la manguera que va al inductor del monoxico inducer motor desconecta la manguera y con un pedazo de cable delgado que entre mételo asta donde llege pues puede ser que este sucio y este no esta succionando el aire
Los vídeos me los traduce otra persona. Me resulta difícil responder preguntas porque no hablo español. Utilizo el traductor de Google para leer comentarios y responderlos, lo que puede ser inexacto y causar confusión. A menos que sea una simple pregunta sobre reparación, normalmente no respondo.
@ i was asking I have Goodman furnace then stop 10 seconds after inducer star and I can stop the inducer whit my hand easy but I connected directl to outlet and runs constantly but I found then the limit switch in the blower housing it's tripping & look like manual reset switch and the error light blinking all time lockout all time pressure switch s are working tank very much
11 місяців тому+1
@@adolfoodiaz So did you connect the inducer motor or the blower motor to an outlet? What specific error code is the furnace blinking? I didn't really understand if this was an overheating issue or a pressure switch problem. Try turning the power off to the furnace and turn it back on. It will show you a different error code at first until it tries a couple of times and then goes into a lockout.
Gracias genio por compartir tu conocimiento con nosotros!
No hay duda de que tú eres el mejor técnico del mundo. Feliz fin de semana
Gracias por compartir todo los que sabes maestro.
Muy bien
Gracias por el vídeo crack si no enciende la calefacción el presostato esta bien y no marca ningún error es la placa electrónica el problema.
Excelente explicación, gracias
Hola puedes explicar sobre calderas eléctricas de 230 voltios.
Gracias sos un genio
Gracias
I was talking about inducer motor when it's connected to outlet run all time but when I connected to 120 v wires from furnace then run the inducer only runs about 12 seconds & pressure switchs are closing k
Have you checked how much voltage the inducer motor is getting from the control board? If it is low, then either there is a bad wire connection or the control board is bad. If the voltage is around 120v, then there is actually something wrong in the exhaust system. Have you watched this pressure switch video? It might give you more ideas of where to look: ua-cam.com/video/wqIVYlgUSyI/v-deo.htmlsi=4jvVJWpu3OKp2KK8
Hola una tus videos son muy buenos para aprender. Pero tengo una pregunta cuál es la temperatura que regularmente tiene que tener el termostato para saber si está calentando bien. ?
👍👍👍
👉💬🙏👍
Saludes brother no tiene un video de cada parte así como este
el inducer motor solo trabaja 10 Segundos y los pude parar con mis manos y Tengo el codigo de error un flash Todo el tiempo es un good man 2 stages sera que el inducer ya esta mal ? Gracias me alegraria tu respuesta feliz ano
Saludes bro 😎 todas las partes se verifican con el símbolo de Homs
Por qué. Mi. Valenton. No. Enciende. Nada. Pero si. Tiene. Power. ??
Tengo un problema , la caldera cuando la enciendo marca error 2 , pero si saco la manguera del forzador y soplo al presostato me prende el forzador ,libera el gas y el chispero y arranca la caldera , donde puedo tener el problema ? En la plaqueta o en el presostato?
Cambia el presostato o donde antes de cambiarlo checa al final de la manguera que va al inductor del monoxico inducer motor desconecta la manguera y con un pedazo de cable delgado que entre mételo asta donde llege pues puede ser que este sucio y este no esta succionando el aire
Por no nos contestas
Los vídeos me los traduce otra persona. Me resulta difícil responder preguntas porque no hablo español. Utilizo el traductor de Google para leer comentarios y responderlos, lo que puede ser inexacto y causar confusión. A menos que sea una simple pregunta sobre reparación, normalmente no respondo.
@ i was asking I have Goodman furnace then stop 10 seconds after inducer star and I can stop the inducer whit my hand easy but I connected directl to outlet and runs constantly but I found then the limit switch in the blower housing it's tripping & look like manual reset switch and the error light blinking all time lockout all time pressure switch s are working tank very much
@@adolfoodiaz So did you connect the inducer motor or the blower motor to an outlet? What specific error code is the furnace blinking? I didn't really understand if this was an overheating issue or a pressure switch problem. Try turning the power off to the furnace and turn it back on. It will show you a different error code at first until it tries a couple of times and then goes into a lockout.