Setting YK Level Sensor York Chiller

Поділитися
Вставка
  • Опубліковано 30 лис 2024
  • Was on a PM inspection when I found the liquid level not looking right on this YK. I found the original reason the level wasn't correct so we were able to resolve the root in the process.
    Stop struggling with Chillers!
    chilleracademy.com/p/intro-to-chillers
    Be supported and trained now!
    Get 8% off at TruTech Tools with promo HVACTIME
    www.trutechtoo...

КОМЕНТАРІ • 23

  • @HVACTIME
    @HVACTIME  Рік тому

    I have produced a 6 page Technical Reference Guide. hvactime.shop/products/yk-tech-sheet

  • @henryching3960
    @henryching3960 6 місяців тому

    Saddle wear on the support sheet in the subcooler bundle. Yep make sense.👍 well said.

  • @EverythingHVACR
    @EverythingHVACR Рік тому +4

    Always great content! Thanks, Holden.

  • @takethe101totarzana4
    @takethe101totarzana4 Рік тому

    Lot of good information there. Thanks for sharing.

  • @paramboytv7378
    @paramboytv7378 Рік тому

    Thank you.!

  • @sterlingarcher46
    @sterlingarcher46 Рік тому +2

    Great video mate 👍 could you explain how to accurately check for the liquid level reading calibration, meaning how do you know if the machine reads the level properly or if it's out of bounds .
    Cheers Holden 👍

  • @compslubamba7114
    @compslubamba7114 Рік тому

    Great video!

  • @hvacrnortheastern2110
    @hvacrnortheastern2110 Рік тому

    Great video l have a problem. We have two 700 ton chillers YK variable primary configuration the plant . When chiller 2 is on without chiller 1 on .When OT above 80 WTH 58 RH we have a over 90 degree going out to cooling tower & 75 degrees coming back chiller .When both chillers run it drops down to 85 degrees with a 75 degree.We check split across the condenser and it’s not plugged . The flow is good it over 1200 GPM bypass at 0 on the BMS which mean it going out to building. We did have York check out they can determine what caused this it never ran above 85 degrees in last 10 years all the log on got on this machine.

  • @teeba2001
    @teeba2001 Рік тому

    At first Thank you.That’s what I really saw about lowering the level sensor to come over the head pressure which causes turbulence obviously . Good luck

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Рік тому

    Just filed it away in the ole memory bank. Thank you good sir

  • @jonnymac31
    @jonnymac31 Рік тому

    Cool, man

  • @adrianperez5628
    @adrianperez5628 Рік тому

    FieldPulse is great. Can’t say the same about the P software.

  • @nellAyaR2034
    @nellAyaR2034 Рік тому

    Those level sensors will get out of calibration quite often. Could have changed even from when it was started up

  • @arc3075
    @arc3075 Рік тому

    There are various lengths to the LLS for these chillers

  • @donnellbaxter8050
    @donnellbaxter8050 Рік тому +1

    Do the have training videos .

  • @Soufiane-of4vd
    @Soufiane-of4vd Рік тому +1

    What's HVAC Meaning ?

  • @calex9398
    @calex9398 Рік тому

    😮👍