  • @Reptiloid-85
    @Reptiloid-85 6 днів тому

    Please tell me that in order for the electric motor to work, do you need to constantly send a signal to the digital inputs DI4 or DI3, or is a pulse signal from the button sufficient for it to work?

  • @vuongpilot5808
    @vuongpilot5808 5 місяців тому

    Hi Sir, I have CTs with ratio 300:1A, Can I use CTs for project with UMC100.3?

    • @ambassadorkees
      @ambassadorkees 5 місяців тому

      Yes you can. See 4:14 onwards: Set CT ratio to 300, i.e. Current factor 30.000%. Take note that secondary wiring must be in correct phase direction. If wrong, you get negative power or wrong rotation direction.

  • @Raja8809-z2q
    @Raja8809-z2q 2 роки тому

    Sir what is check back settings 1.current & Simulation in Umc 100 relay.

    • @botniaelman4092
      @botniaelman4092  2 роки тому +1

      Hi Reshav, check back is a function checking whether current is running when it's supposed to. Does that answer your question?

  • @arifpathan7787
    @arifpathan7787 2 роки тому

    WHAT DIFFERENCE BETWEEN UMC 100 VS NUMERICAL RELAY

    • @botniaelman4092
      @botniaelman4092  2 роки тому

      UMC's first task is advanced motor protection based on exact current measuring. Programmable functions are an addition.
      A numerical relay typically won't have out-of-the-box most controller functions like DOL, REVERSE, Actuator etc function Blocks that's are 100% integrated with analogue measurements, over- under- and unbalanced load protections, restart inhibit options based on # starts/hr or heat dissipation modelling.
      And a lot more.

  • @josemanuelcastellanosgarci9353

    Dónde puedo conseguir el software

    • @botniaelman4092
      @botniaelman4092  Рік тому

      Hi Jose, in Standalone no software is needed.
      If you have the need for a larger installation and especcially custom logic, than the required software is availble on ABB Marketplace: Field Information Manager or FIM UMC Edition.

  • @hiloufalakhdar1065
    @hiloufalakhdar1065 3 місяці тому

    I have a problem in UMC100 ---The error appears. Error 17:application ....Anyone help me?