Thank you for the quality of the video. I would like to ask about discharge valve in visualisation takes the discharge valve variable defined in GVL FIO or the control signal ? and y of the PID block normally is the output of the process not the control signal ?
Thanks for your compliment. DischargeValve variable is a real value between 0 to 10 that controls a control valve in FactoryIO and in this case it is like a disturbance in the system. Output Y of PID block is exactly the control signal. Output of the process is the feedback signal and in this case is Level PV (ACTUAL input of PID block).
Excellent video, just found it on YT. Is there any short tutorial, what sw I need and how to install, where to download from, what licenses do I need etc?
Thank you for the quality of the video. I would like to ask about discharge valve in visualisation takes the discharge valve variable defined in GVL FIO or the control signal ? and y of the PID block normally is the output of the process not the control signal ?
Thanks for your compliment.
DischargeValve variable is a real value between 0 to 10 that controls a control valve in FactoryIO and in this case it is like a disturbance in the system.
Output Y of PID block is exactly the control signal.
Output of the process is the feedback signal and in this case is Level PV (ACTUAL input of PID block).
Excellent video, just found it on YT. Is there any short tutorial, what sw I need and how to install, where to download from, what licenses do I need etc?
Thanks for your compliment, watch the following video.
ua-cam.com/video/Lt07vfT4oNg/v-deo.html
Is there a way to change the control action of the PID? From Direct acting to Reverse acting?
Set P as negative value to invert the control of the PID function block.