How to troubleshooting drink vending machine's cooling system while on location

Поділитися
Вставка
  • Опубліковано 18 жов 2024

КОМЕНТАРІ • 68

  • @GlitchedAngel21
    @GlitchedAngel21 10 місяців тому +3

    Thank you as a new vending machine owner who’s machine stopped cooling I greatly appreciate this because I don’t wanna pay someone a but load to come out and take a look and now thanks to this I have the confidence to check for myself!

  • @koutakleinschmidt343
    @koutakleinschmidt343 Рік тому +2

    Wow, must be a very good refrigeration mechanic you got there!

  • @SandipMehta-q6e
    @SandipMehta-q6e 8 місяців тому +1

    Great video and very helpful information. I did the tests and condenser and evaporator fan works fine along with thermostat. I noticed next to evaporator coil - notice a chunk of ice build up. After thawing it, ran the 15 mins test as you recommended, I see some frost. What would cause the ice build up next to Evaporator coils (looks like kidney bean)?

  • @jdvanguy296
    @jdvanguy296 5 місяців тому

    Dude, your videos are saving my ass, I'm new to the business and your videos have helped me greatly. Thank you for what you do.

  • @josephburns1037
    @josephburns1037 10 місяців тому

    Great video. Thanks Alex.

  • @jasmingresham2108
    @jasmingresham2108 8 місяців тому

    This is such an informative video. My machine is triggering the breaker making it go out at its location. Do you know if that is because of the fan or the condenser?

  • @dustymorrison6744
    @dustymorrison6744 8 місяців тому

    Just watchedbuour video very helpful after the tests i come to learn my compressor is not turning off. Inthought it wasnthe thermostat. So i replaced it and found this problem. Does that mean i need a new compressor? Im new to vending machines.

  • @h.b4517
    @h.b4517 5 місяців тому +1

    I have a KM series machine. It's only a year old and its getting louder. From your video I believe it's the evaporator fan. The one that is always on, what should I look for if it is getting louder? I removed the back and made sure it's not sure it's not sucking up dust. I just don't know what to do now.

  • @aedinquinn8687
    @aedinquinn8687 Рік тому +1

    Dud refrigeration tech replace compressor? What was diagnosis? Aedin

  • @wallysensei
    @wallysensei 10 місяців тому

    Hello, recently my 501e went warm and the machine is tripping the outlet whenever the compressor is plugged in within the machine.. Is it time for a new compressor? Thanks for all the info you provide

  • @sampatel2021
    @sampatel2021 11 місяців тому

    Thanks for the video and info. I checked my Dixie narco 276e machine and evaporator and condenser fan is fine but not cooling.
    I did the 15 mins test as per video and no frost in the evaporator coil. Does this signify the compressor is bad or leak?

  • @judycruz6023
    @judycruz6023 Рік тому +1

    Hi. My Royal 650 has a lot of ice build up around the entire evaporator coil. How can I thaw it out while preventing any leaks at the location? Where should drip pans be placed? Should I remove the chute like you did in your test?

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +1

      You will want to unplug the machine and let the ice melt off while keeping a towel near the bottom of the machine to soak up any overflow water. You can also use a hair dryer to help accelerate melting the ice. Please do not chisel or poke at the ice as this can damage the evap coil.

    • @Oasis_Vending
      @Oasis_Vending Рік тому

      ​@@VendingMachineSupporthow do you test the electronic temperature sensor on a Royal 650?

  • @UFObuilder
    @UFObuilder Рік тому

    Thanks for the information 👍

  • @d.o.cthebarber9096
    @d.o.cthebarber9096 2 місяці тому

    Hello there and thank you for your very very helpful videos. So my question is checked the condenser fan and it was good then the evaporator fan and it did not turn on so did the evaporator coil test and it froze up like in the video does that mean it needs to be charged too or is that caused due to the fan not working?

    • @FunnyRandomz4U
      @FunnyRandomz4U 2 місяці тому

      It either means the fan has gone bad or the relay has gone bad. You can check to see if your evaporator fan is running in the back. That will be a pretty clear sign it is time to replace your evaporator fan.

  • @amason9801
    @amason9801 Рік тому +2

    hey do you have anymore info on the vendos I just bought one and would like to find more info or videos on it

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +1

      I hope to have some recorded in the future.

    • @austingrant5660
      @austingrant5660 Рік тому

      Same here bro there no videos on them i got my compressor working right ,i can,find the evaporator fan well I mean I can't find a way to get to it , anyways. You should,post a video of your vendo machine

  • @lentil61
    @lentil61 7 місяців тому

    Thank you for your videos. They are awesome. I have a Vendo 720 and the evaporator it's icing over. I'm not sure how to test the thermostat to see if it's bad before I have to replace the compressor. Any help?

    • @fields5003
      @fields5003 3 місяці тому

      Did you ever figure it out?

  • @flawlesssnipes630
    @flawlesssnipes630 4 місяці тому

    So it looks like it’s my compressor fan do you have a video of a replacement ?

  • @burnoutawd
    @burnoutawd Рік тому

    I have a dixie narco 276 just restored the entire machine. Replaced the compressor housing with a new compressor and rebuilt evaporator and condenser. I noticed the compressor will run 15min on and 15min off ranging from 35°-37° new thermostat. This unit is installed in my basement which is about 65°. Is this the normal cycle? Or should I start looking for some kind of air leak? I also for the first time fully stocked the machine full of room temp cans and it took almost 6 hours to reach 35 degrees. My evaporator in 15 minutes looks exactly like the one in your video. I found quite a few other videos that say that is perfectly normal, including the company that I bought the refurbished compressor deck from lol. When you had yours looked at, did they say there was something wrong with it??

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      From your description it sounds that everything is working ok in your machine cooling wise. Drink vending machines are not energy efficient like your typical modern refrigerator.

  • @richardbohnert1140
    @richardbohnert1140 Рік тому +7

    Ok one thing that we should do with these machines is blow out your condenser coils. This should be the first thing that you do. I work on ice boxes for a ice company. If you can't see thru them it's not a good sign.

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +2

      Excellent tip Richard. I should have mentioned that. Thank you for sharing.

    • @RandyNO6
      @RandyNO6 8 місяців тому

      Hey when you say blow them out what do you mean? And what would you suggest doing that with?

    • @richardbohnert1140
      @richardbohnert1140 8 місяців тому +1

      You can do that with compressed air.

  • @joewilliams5283
    @joewilliams5283 Рік тому

    I recently purchased a Vendo 516. The condenser isn't getting cold. I can't find ANY information on replacements. Do you have any suggestions or if there are replacements for it?

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +1

      The Vendo 516 is an older Vendo unit and new units are hard to come by. I would look for a locally owned and independent HVAC mechanic or appliance repair to have a look at the unit. These cooling decks are very simple in the grand scheme of cooling units.

  • @nicholasdcarlson
    @nicholasdcarlson Рік тому

    My compressor is hot and the soda isn’t cooling but the tubing feels cold thanks for your help!

  • @beatricecarrizales2296
    @beatricecarrizales2296 5 місяців тому

    I have a vendo 721 and my evap is completely frozen when i open machine cond fan isnt on but wondering if i have a eco system machine how would i be able to tell?

  • @Era_JustBelieve
    @Era_JustBelieve Рік тому

    My location lost power recently and reset my whole Royal 650 drink machine. Prices went to .50 cents and now it’s cooling warm air. What’s the exact settings for this machine to get it cold ?

  • @donnieb7818
    @donnieb7818 Рік тому +1

    I just bought a royal 660-9 & having the same problem with the machine , I can't get the compressor to turn on when it's plugged into the power harness but when I unplug the compressor & plug it into an extension cord the compressor kicks on no problem, I'm brand new to this vending business & would appreciate your expertise, Thanks!!!

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +1

      @Donnie B From your description and trouble shooting steps. It sounds like you could have a faulty refrigeration relay. The Royal 660 was designed by Coke-Cola but manufactured by Royal Vendors for Coke Asset Operators. The 660 shares some similarities to the Royal 650. I have several videos about the Royal 650. Two of which deal with the refrigeration relay. This relay can be tested from the control board to determine if it opens and closes.
      The 660 uses a four button programing as the Royal 650 uses the a three button programing. Though the concept I show in the videos can be applied to the 660.
      How to test the Royal FRIG relay: ua-cam.com/video/yIgDyCrBk4Q/v-deo.html
      Troubleshooting a Royal FRIG relay with a voltmeter: ua-cam.com/video/5SYYrIn3tYs/v-deo.html
      If the relay opens and closes when tested with a voltmeter then the issue is the actual power junction assembly that the compressor plugs in to. I hope the gets you pointed in the right direction. Thank you for watching and supporting.

    • @donnieb7818
      @donnieb7818 Рік тому

      @@VendingMachineSupport Thank you sir, I'm gonna take a look at it today, I appreciate the info Thanks 👍

  • @raulperez5471
    @raulperez5471 Рік тому

    Compressor seems to work and the evaporator coil is getting cold but I don't see The frost built as seen on your video. I can see light frost on the sides and on the tube in the front.

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      Your unit may be low on charge or has a blockage in the lines. Might want to call in a HVAC mechanic.

  • @ethanirwin3615
    @ethanirwin3615 Рік тому

    I’m try to diagnose my Dixie-Narco and it fails the thermostat test but it also doesn’t get frosty on the coils. Should I replace the thermostat and try the frost test again?

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      @Ethan Irwin If the evaporator coils did not get frosted over within 15 minuted when connecting the compressor directly to power (which bypasses the thermostat). Then replacing the thermostat will not produce a different result. Make sure when you tested the compressor you did this with the machine unplugged from the wall and the compressor connected directly to power via an extension cord.

  • @raulperez5471
    @raulperez5471 Рік тому

    My condenser fan takes time to turn on is that a concern? When it turned on, I moved the Thermostat to 0/0ff and the fan turned off. Does the fan take a while to turn on or is it supposed to be immediate

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      Typically the condenser fan should start as soon as power is applied to it. Unless there is a time delay device which I have only seen once. If the condenser fan is taking some time to start up there is a good chance that it is also not running at full RPM. In turn reducing the amount of air that is pulled through the condenser coil and over the compressor head. This causes overheating and problematic cooling issues.

  • @nelsonrosado4215
    @nelsonrosado4215 2 місяці тому

    The magnets aren't spinning fast enough on my vendor jet spray machine. What can I do to speed them up

  • @josedavidgamez5026
    @josedavidgamez5026 Рік тому

    So what is happening when the coke cans are over freezing literally lost like 40 cans due to them bursting in machine . It was winter in Texas but last month could drinks have over froze due to outside temperatures?

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      You need to establish what is the temp inside you machine. Stick a thermometer in the machine. You are looking for temps between 40F to 36F. Diet drinks freeze at 34F while other type of drinks and water will freeze at 32F. If the temp in your machine balances out between 40F and 36F after letting the machine run for a few hours. Then the freezing cold be due to outside temps.

  • @ricktumaniec6820
    @ricktumaniec6820 Рік тому

    I have an 85 coke machine, cools great but the condensation won't drain to the pan or through the hose to the pan. how do I unclog it?

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      Try running a long brush through the pipe.

    • @brianiswrong
      @brianiswrong Рік тому

      Or connect a few cable ties together and poke it down the drain hole (under the evaperator) until you see it poke out the end of the tube.

  • @thirdgearboogie2210
    @thirdgearboogie2210 Рік тому

    AMS 39 VCF
    That keeps leaking water on the floor. How do I fix this.

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +1

      There is a drain hose that takes the water coming from the pan that sits beneath the evap coil and deliveries it to the drain pan. Check to make sure the hose is attached correctly or not clogged. Also make sure the hose is actually sitting in the drain pan.

  • @franciscaramirez2342
    @franciscaramirez2342 Рік тому

    Hello sir so i got a beat up choice vendo machine and i mean the i had to do body work to it the door was bend Ll bad anyways i was real proud of my self cus i fix the door i also got the compressor and the fan aslo the condenser n fans anyways so i was excited right but once i check it to see if it was cold i was shocked it was not cold becus everything was good any ways i been try to see whats up with that and my guess is could the capillary tube need to be replaced cus its look bad its all original from the late 1960s any ways hope to hear from you sir gracias

  • @geminivending
    @geminivending 10 місяців тому +1

    Hey 👋 there

  • @MichaelBeechy-zn8vo
    @MichaelBeechy-zn8vo Місяць тому

    who do you call to come out and service them

  • @soup3rd609
    @soup3rd609 Рік тому

    The whole back part and pipes are just pure frost and it’s not warming up the drinks. What might be the exact issue for that?

  • @jamalhinds1
    @jamalhinds1 Рік тому

    So my Coils are froze up in a block of ice, I check the thermostat like you said in the video turning it until the compressor kicks on and off. While the compressor is off I was able to hear the blower fan behind the block of ice also I can see the compressor fan spinning. I shut the machine down for a day to let ice thaw to visually inspect the coils there was some slight browning at the bottom but not much. With the machine back on for a day I returned and the ice started build back up, please help.

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому

      What happened to the evap coils after running the compressor directly to power for 15 minutes with the machine unplugged?

    • @jamalhinds1
      @jamalhinds1 Рік тому

      The pass through is on the left side of my machine. Will the deep refrigeration unit on DSV still work

  • @scottytroublefield205
    @scottytroublefield205 Рік тому

    Mine is freezing up can you tell me what may be causing it??? DN 501e

    • @scottytroublefield205
      @scottytroublefield205 Рік тому

      My motors at bottom and top are working.

    • @VendingMachineSupport
      @VendingMachineSupport  Рік тому +1

      Possible could be the thermostat not shutting down the compressor or the machine is leaking outside air in.

  • @jesusdiosdado4974
    @jesusdiosdado4974 5 місяців тому

    My compressor came on but my fan don't come on