  • @marcia122487
    @marcia122487 3 роки тому

    We have two turbocor compressors that were replaced due to bearing faults. Do you offer rebuilding services? If so, how can i get information? Im in florida. Thanks

    • @DanfossClimate
      @DanfossClimate  3 роки тому

      Please contact: +1 (850) 504-4800 or write an e-mail to: turbocor.training@danfoss.com

  • @toyinorodare4072
    @toyinorodare4072 4 роки тому

    How can I attend your Compressor train Class because I want to set up a Compressor repair and Service Line.

    • @DanfossClimate
      @DanfossClimate  4 роки тому +1

      Hi Toyin,
      You can learn more about our Turbocor® training opportunities here: www.danfoss.com/en/products/compressors/dcs/turbocor/#tab-learning
      Or you can get in touch with our Turbocor® training team by shooting an email to turbocor.training AT danfoss DOT com
      Hope that helps!

  • @BisDatQuiCitoDat
    @BisDatQuiCitoDat 4 роки тому

    Dear Sir. Is there a chance to buy the step motor driver tester?

    • @DanfossClimate
      @DanfossClimate  4 роки тому

      The stepper motor tester is not a tool that we offer, however it may be found at an electronics or supply store.
      You can also move the worm gear using a pliers or similar tool as shown in this video.
      Functional testing of the IGV can be done when connected to the compressor. See our IGV Verification video: ua-cam.com/video/b_B6pJYph0w/v-deo.html

  • @yogaanandhtanggaraju8502
    @yogaanandhtanggaraju8502 Рік тому

    We have installed 2 units of water-cooled chillers (390RT, 3 compressors per chiller) at a hospital in Malaysia. Facing a "peculiar" situation with the compressors (one from each chiller) where the IGV is not opening beyond 26% (max). We have tried replacing the backplane assembly card, alomng side the PWM, serial etc - still no solution. We have tested the IGV motor opening pattern using programme (laptop) and it works - it does fully open to 110% but that's not the case when the chiller is operating. We have also dismantled and visibly checked the IGV - looks fine.
    ANY IDEA OR CLUE WHY THIS IS EVEN HAPPENING? IS THIS AN IGV RELATED ISSUE OR SOMETHING TO DO WITH THE COMPRESSOIR ITSELF? APPRECIATE SOME ASSISTANCE HERE - ISSUE NOT SOLVED FOR ABOUT 10 MONTHS NOW (MANUFACTURERS/VENDORS HAVE TRIED)

    • @DanfossClimate
      @DanfossClimate  Рік тому

      We are checking with our experts and will get back to you.

    • @DanfossClimate
      @DanfossClimate  Рік тому

      Hi again.
      Please reach out to our local expert in the Asia Pacific region:
      Derek Foong King Soon
      Technical Support & Services Manager
      +63 2898 8268 8
      +63 2827 1121 2
      Thank you

    • @yogapratama8087
      @yogapratama8087 5 місяців тому

      Bro,the problem already solved?i have same case with u,

  • @cikokustamsi1453
    @cikokustamsi1453 3 роки тому

    Does he aware, the wire installation of the step motor is not proper, wires are too long, twisted and gets metal contacts that can damage the wire insulation by vibration?