    Hey @hvacwithdrewman98 thanks for all these great videos. I have a question my indoor unit just randomly leaks my filter is clean and charge it good. I took off the cover and it seems to be running off one of the lines where the coils are connected on the inside unit .& runs down and drips randomly. Any ideas on how to fix this? Could it be that thermostat little wire hanging should that be in a certain position?

    • @hvacwithdrewman98
      @hvacwithdrewman98  День тому +1

      @@thegreatest2ever could be the insulation around the copper pipes.. check that first.. the do sweat

    • @thegreatest2ever
      @thegreatest2ever 19 годин тому

      @@hvacwithdrewman98 yes it seems to be dripping off the indoor unit coil one of those little tiny copper lines can those be wrapped? The lineset copper lines running from the back of the machine outside are all wrapped good

    • @hvacwithdrewman98
      @hvacwithdrewman98  11 годин тому +1

      @@thegreatest2ever yes they both need to be wrapped, insulated... Slightest gap or tear will drip.. try to tape up and you can see