This just happened to me. The unit is mounted pretty high up on the house so I just killed power completely. Waited 120 seconds and made sure all the breakers were set before hitting the main so everything came on in sync. AC back. Hopefully was just a glitch from a bad breaker we had last week.
Bon I have a VRV4 that gets the U4-01 errors 2-3 times week. When we cycle off the unit it works for a couple day and then the error comes back. What are your thoughts?
Check indoor unit got link to smoke detector or fire alarm. May the alarm cause error U4. By my experience,the kitchen smoke detector intermittent short circuit cause aircon erreo U4.
Hi vrv 4 model 18 hp master and slave unit I'm changed for control pcb for master unit then I'm switch on the AC AC start but 10 number indoor that all AC is bringing for timer what's the problem
Hello sir, I have a similar problem, when I try to perform a test operation by pressing BS2, in T01 I get the error U403. I have 6 cassette and all with thermostat, with 1-10 it recognizes the 6 cassettes, and when I perform the test 2-05 it also works for me, but the starter does not perform it. how can I solve that. Thank you.
@@BonMj is auto charging always done first? And I have not replaced the main pcb yet, but it does not perform the test run. Where is the DS1 and DS2 setting??
Same here on 20+ years old Daikin inverter. Power cycle of the whole equipment "fixed" the error. Weird... but thanks for the idea :)
👍
This just happened to me. The unit is mounted pretty high up on the house so I just killed power completely. Waited 120 seconds and made sure all the breakers were set before hitting the main so everything came on in sync. AC back. Hopefully was just a glitch from a bad breaker we had last week.
👍👍👍
Thnxx for information
Thanks
@@BonMj W/C Sir
verry good job
Thanks
Good work sir
Thanks
@@BonMjsir Daikin VRV 4 single outdoor one compressor faulty please e
@@expertair8641 the only way is replace compressor.
@@BonMj AC all brand work sir
You
请问一下,我的daikin 也是出现U4,是需要联络daikin 的technician还是其他technician也行呢?
有经验的都可以,如果你担心就直接联络Daikin
Hi, my Daikin R407C has U4 code. Can you please give me some idea how to rest it? Thank you
Bon I have a VRV4 that gets the U4-01 errors 2-3 times week. When we cycle off the unit it works for a couple day and then the error comes back. What are your thoughts?
Check indoor unit got link to smoke detector or fire alarm.
May the alarm cause error U4.
By my experience,the kitchen smoke detector intermittent short circuit cause aircon erreo U4.
Hello sir..., thanks you for sharing your knowledge sir.what is the minimum thermistor value sir.pls replay sir.,
Daikin is 16k ohms by ambient temperature around 30c
@@BonMj thanks you sir.,
Nice information
Thanks
Hi bon, do you have video for daikin u8 error code please thanks
Dun have.
Check the remote controller main/sub setting
If wallmounted,please check the main/sub switch at receiver pcb
Thanks bon i have a look in the indoor pcb
Teacher, I like to see ur video how to do multi condensing pump down system. Let said indoor one unit eev v body choke. How do I do pump down system?
I suggest you manual pump down better.
Hi sir ,
In vrv 4 unit ,, connected 12 indoor unit and only 1 unit show u4 error and all 11unit cooling ok . What's the problem?
Check comunication wire
Thanks @bon Mj. Do you know how to bypass U4 when at least x1 indoor unit shut down ? (breaker off ) ? Thanks
Off outdoor power supply and on back , press reset button.
If the indoor pcb faulty, suggest u take out the communication wire and reset.
Hi vrv 4 model 18 hp master and slave unit I'm changed for control pcb for master unit then I'm switch on the AC AC start but 10 number indoor that all AC is bringing for timer what's the problem
What is the error code, you try off and on back power supply,afterthat need to test run.
@@BonMj I'm that AC contr PCB is defective so I'm changing the control PCB and I do test run but indoor unit is timer lite is blinging
@@gothandaraj860 what is the error code.
Are you set the deep switch
@@BonMj m yes I set dip switch settings but is not working
@@gothandaraj860 dun set dip switch.
Adjust back to off.
Cheers.
Thanks bro
有一台vrv 全部室內出u4 outdoor 有電源 電相正常 hp2長閃 hp3 hp8 長亮 master control 閃燈 怎麼辦
试关电十五分钟再开会,按reset多过5秒
@@BonMj 試一下 謝兄地
I have the same problem for vrv3. But mine still the condenser is not running
May be insufficient gas
Vrv 4
Last time fcu 4 use now 3 only how tow to rest
Off outdoor power supply and on back, press return button more than 5 second to reset
今天check 到一台4mks 80 三台内机blinking 出U4 . 发现CU control board 没有灯显示。reset了也不行!不确定是filter board 还是control board 坏!直接让他换了台外机!
这个model问题比较多
👍👍👍
Thanks
All indoor unit same like this
Hello sir, I have a similar problem, when I try to perform a test operation by pressing BS2, in T01 I get the error U403. I have 6 cassette and all with thermostat, with 1-10 it recognizes the 6 cassettes, and when I perform the test 2-05 it also works for me, but the starter does not perform it. how can I solve that. Thank you.
If auto charging system, you need to auto charging after that test run
@@BonMj but test run does not start, I get U403, it is probably the PCB?
@@JoseANTONIO-hl7yp you replace the main pcb?
If yes,check the DS1 and DS2 setting.
Afterthat auto charging and then test run.
ua-cam.com/video/RleCvum-bEQ/v-deo.html
if new installatio, follow this video, 1st auto charge after test run
@@BonMj is auto charging always done first?
And I have not replaced the main pcb yet, but it does not perform the test run.
Where is the DS1 and DS2 setting??
hello sir,what happen vrv4, all fcu error u4,and cu led 000 light,transmission cable cu to last fcu no issue
May be one of the indoor pcb got problem
Boss where to download the error code diagnosis in pdf. Thanks you
Google