Fire Alarm Test FAIL - Smoke Shutter Fun

Поділитися
Вставка
  • Опубліковано 7 вер 2024
  • Hotel Inspection - Addressable nightmare; testing two smoke shutters that drop to prevent smoke from the lobby/atrium getting into the 2nd floor hallway. Naturally I assumed that the smoke head on the other side would trigger it. Negative.
    Yes, we could have looked through the programming but that requires digging up all of the device numbers - in this case usually that means finding the module or just scrolling through hundreds of them in the panel programming. Easier to just start tripping things.
    As you can see, one of them didn't work. After determining that no one really knew who was supposed to deal with them I poked around above the ceiling and found the trigger mechanism - it's a solenoid that releases a cable which holds back a giant ratcheting mechanism - hare trigger barely describes it. It was too tight and the solenoid couldn't do it. I got it working, sort of - the shutter was in need of adjustment and maintenance - we notified the vendor.
    This doesn't "fail" the inspection overall - but it's not an insignificant problem.

КОМЕНТАРІ • 8

  • @JMANWiSS
    @JMANWiSS 8 років тому +2

    I like these videos. they are interesting

    • @brettman273
      @brettman273  8 років тому +2

      Well thank you, nice to hear!

  • @Goldenrod636
    @Goldenrod636 7 років тому

    We are all waiting for more videos.

  • @Darcfoxx101
    @Darcfoxx101 7 років тому

    Wait what on earth is a smoke shutter?

  • @GaryBeltz
    @GaryBeltz 8 років тому

    Why did you say "Uh oh!" at the end of the video?

    • @FireAlarmNZ
      @FireAlarmNZ 8 років тому

      because the second smoke door wasn't operating

    • @brettman273
      @brettman273  8 років тому +2

      Because I'm a smartass, and yes, because the thing didn't work.

  • @Goldenrod636
    @Goldenrod636 8 років тому +1

    Ew gross! Advances.