Earth Fault Loop Impedance Zs 100% or 80% Values On Site With Matt. Calculations Using BS 7671

Поділитися
Вставка
  • Опубліковано 30 лис 2024

КОМЕНТАРІ • 95

  • @GSHElectrical
    @GSHElectrical  2 роки тому +1

    How to Calculate Total Earth Fault Loop Impedance - Applying a Temperature Factor to R1 + R2
    ua-cam.com/video/jF5Gf04GnlA/v-deo.html

  • @cumberland1234
    @cumberland1234 4 роки тому +15

    Just a few things I'd like to add (sorry if it comes across like I'm being pedantic):
    The difference between the 100% values in the regs book and the 80% values in the OSG are that the regs book is for a conductor at it's maximum operating temperature, the OSG values are maximum measured values with a conductor at 10 degrees C for a 70 degrees C conductor.
    The 80% comes from the simplified temperature coefficient for copper which is 0.004 per degrees centigrade and a difference of 60 degrees, giving a factor of 1.24 which the reciprocal is around 0.8 or 80%.

    • @Jo3yW
      @Jo3yW 2 роки тому

      Thanks for that. I just noticed the values were different, and 80% lower in GN3. And yet I can't see ANY reference to the 80% correction factor in 7671, GN3, or OSG. WHY?? Why can't the IET put a little note explaining things like this? I just spent 150 quid on the latest set of books. Why do they want to confuse me?!

    • @cumberland1234
      @cumberland1234 2 роки тому +1

      @@Jo3yW There is a note at the top of P140 of the OSG and P172 of GN3 saying a correction factor (divisor) of 1.25 is used.
      I agree - they don't make easy reading, 80% is the reciprocal of 1.25 hence instead of dividing by 1.25 you can multiply by 0.8. I think it really ought to be 1.24 but it probably doesn't make much difference. I think the older guidance notes back in the 16th edition days were easier to read or maybe I'm just getting old! Back then we used a three quarter rule of thumb.

    • @Jo3yW
      @Jo3yW 2 роки тому +1

      @@cumberland1234 Yes, you're right, I see it now! I don't have an eye for the small print as yet. I was looking for 80% when I should've been looking for 1.25.
      Also, to be fair to the IET, under Table 41.3 in BS7671 there are notes referencing operating temp adjustments. The first (only?) reference I can see to the 0.8 factor is on p410 Appx 3, in the equation to take into account increase of temperature due to load current.

  • @ishkebab
    @ishkebab 4 роки тому +28

    You do realise the 80% value is a temperature adjustment from the bs7671 values at maximum 70 degrees operating temperature, as the cables under test are at site temperature conditions and a 20% difference in temperature hence adjusting the 100% value by 0.8 otherwise known as ‘the rule of thumb method’
    If the resistance is too high at ‘cold conditions’ during initial verification then at load conditions the resistance will rise above the maximum 100% value so yes we don’t exceed the 80% value but it’s nothing to do with the voltage , that has been taken into account with the Uo x cmin (218.5 volts) value given in your example as 1.37 ohms.
    See appendix 14 for more information.

    • @stevensmith4449
      @stevensmith4449 4 роки тому

      ian adams your right cmin gets used at the design stage to make sure circuits will trip in time when the Uo is at the minimum that the regs allows.
      Also when a circuit is first switched on it is at ambient temperature 20 degrees? So the PSCC/PFC Will be at it's highest value,so these fault currents must be lower than the protective devices Icn rating!

    • @markgilder9990
      @markgilder9990 3 роки тому

      Thank you for the explanation of Uo X 0.95 that makes sense. Then the 80% value rule of thumb temperature adjustment from cold to hot (operating temp of cable under load) 👍🏻

  • @naturalremediescheshire
    @naturalremediescheshire 3 роки тому +3

    Really useful refresher video with page references and clear explainations. Thank you for taking time out to put this together 👍

  • @JoeRobinsonTraining
    @JoeRobinsonTraining 4 роки тому +8

    Cracking video Mr. Matt. Hopefully lots of learners are using the excellent resources here on GSH Electrical during this period.

  • @rmmj7james293
    @rmmj7james293 3 роки тому +1

    One GSH's best videos. Well done, gents.

  • @jmohammad3762
    @jmohammad3762 4 роки тому +5

    Argubaly the best explanation on this subject. Clear and concise and well explained Matt. Thank you sir

    • @GSHElectrical
      @GSHElectrical  4 роки тому +1

      Thanks Jay 👍

    • @jmohammad3762
      @jmohammad3762 4 роки тому +2

      Always a pleasure to watch GSH UA-cam videos. I've enhanced my knowledge through your visual learning. Keep up the good work it's much appreciated by the electrical industry Electricians.

    • @GSHElectrical
      @GSHElectrical  4 роки тому

      Thanks for another amazing comment Jay 👍

  • @ashmanelectricalservices4318
    @ashmanelectricalservices4318 4 роки тому +9

    It's worth mentioning the maximum permitted earth fault loop impedance recorded on the schedule of test results should be the 100% values.

    • @kirkadams9530
      @kirkadams9530 4 роки тому +1

      Thanks!

    • @Daz_sz
      @Daz_sz 3 роки тому

      Good shout out was confused thanks

  • @wallbouncer9655
    @wallbouncer9655 4 роки тому +6

    Great work Matt

  • @ChernoBueno
    @ChernoBueno 3 роки тому +1

    Thank you so much 😊 I absolutely love learning about the electrical world!

  • @gbelectricks
    @gbelectricks 4 роки тому +4

    Cracking video, ceep them coming👍👍

  • @abrehamish
    @abrehamish 3 роки тому +1

    Thank you for your detailed explanations.

  • @andrewhaynes5976
    @andrewhaynes5976 2 роки тому +1

    You made that calc pretty hard work. Using simple algebra, you divide by 0.8 to go the other way.

  • @pgpdude
    @pgpdude 4 роки тому +3

    Hi to convert from 80% values to 100% the easiest way is to divide by 80 this will give you the value of 1 % then multiply by the percentage that you need i.e. 100 or for instance if you need the 90% value just divide by 80 and multipy by 90. Also to get 80 % value from 100% value divide by 100 and multiply by 80. this is a lot easier to remember and calculate without using fractions. otherwise great video though. Kind regards Peter

  • @steveday7510
    @steveday7510 3 роки тому +1

    Excellent Video Matt

  • @richardwash6678
    @richardwash6678 4 роки тому +2

    Brilliant video Matt, good explanation. 👍

  • @thomasskinner4064
    @thomasskinner4064 2 роки тому +2

    Great video, I understand the principle of using the 80% rule, when your verifying your results. When you do your testing sheet tho, in the Max Zs column you use the 100% valve in the regs book right? But when your actually testing your looking for below the 80% value and if it's over needs further investigation. like when you carry out insulation resistance and have a result between 1 and 2 M ohm, although it passes it requires further investigation.
    Thanks for the video and hopefully my question makes sense

  • @SLimbu-nf9or
    @SLimbu-nf9or 4 роки тому

    An outstanding well explained video with all guidance better than classroom. Thank you Matt.

  • @brianoceallaigh8714
    @brianoceallaigh8714 4 роки тому +6

    good one Matt...

  • @no_short_circuit
    @no_short_circuit 4 роки тому +2

    Thanks Matt. As an adult learner I understand your explanation. I have studied this and really struggled with the temperature correction (mentioned in other comments). I get the 70 degrees in the regs versus site temp will affect the resistance (Zs) but any chance of doing a similar video to explain the maths behind that.

  • @subjude101
    @subjude101 Рік тому +1

    Thanks so much for this video.

  • @ashmanelectricalservices4318
    @ashmanelectricalservices4318 4 роки тому +11

    Brilliant video, great work Matt, very well explained 👍

  • @scarcxy
    @scarcxy 2 роки тому +1

    Thank you for this video.

  • @angelofranklin1
    @angelofranklin1 3 роки тому +1

    The only issue I can see without doing any calcs is the case where you may need to use a D type MCB in the DB due to the load type but are using a B type 100 amp MCCB in the SMDB upstream, I would imagine you will need to do some work on the discrimination study.. However, very well explained Matt thank you.

  • @jordangallacher276
    @jordangallacher276 4 роки тому +1

    Great video on this subject matt , I would love to see more like this from yourself 👍

  • @callumsimpson7483
    @callumsimpson7483 3 роки тому +1

    It says in the OSG to get the 1.1 number to 1.37 you times it by 0.275 as the on site guide figure is at 10 degree ambient temp and the bs7671 is at 20 degree ambient temp

  • @ryanmorris101
    @ryanmorris101 2 роки тому +1

    Great video!!!

  • @bashirahmed1965
    @bashirahmed1965 3 роки тому +1

    Excellent -well presented.

  • @MrFryfish
    @MrFryfish 13 днів тому +1

    Smart. Cheers!!👍🏻👍🏻👍🏻

  • @JohnBond-k9b
    @JohnBond-k9b Рік тому

    Excellent video very helpful cheers

  • @triplerjm2353
    @triplerjm2353 4 роки тому +1

    another stunning video, well explained even that I am still on my Diploma L2 but I have topped up a knowledge. Thank you.

  • @mark1784
    @mark1784 4 роки тому +3

    Would I be right in saying the 100% figure in BS7671 is used for design stage, then the 80% figure in the OSG is used for testing?

  • @chrissmith7259
    @chrissmith7259 3 роки тому

    Level 2 Exam on Tuesday after Corona Virus Testing. Great video.

    • @GSHElectrical
      @GSHElectrical  3 роки тому

      Checkout online the eFIXX apprentice hub for questions to help with level 2

    • @chrissmith7259
      @chrissmith7259 3 роки тому

      @@GSHElectrical Thanks, that's really helpful.

    • @chrissmith7259
      @chrissmith7259 3 роки тому +1

      @@GSHElectrical Matt, I got 95% and your eFIXX certainly helped fix it for me. Thanks for letting me know just before the exam, which is really appreciated. Anyone else coming up to your exams should check out this valuable resource, Like everytjing GSH Electrical does and Subscribe.

  • @georgedumitrescu9473
    @georgedumitrescu9473 4 роки тому +1

    Great explanation Mat. Well done. I do prefer to use a much simpler way of working the required values using the rule of the “thirds”. Anyway, brilliant job. Thank you.

  • @deniscotter525
    @deniscotter525 3 роки тому

    Yes Man, respect, great help.

  • @sandymcnair5298
    @sandymcnair5298 4 роки тому +2

    Instead of working true fractions to convert from 80% to 100%. I use 100÷80 = factor of 1.25. As you use actual figures it is easier to see for those that don't do maths.

  • @cleversonsouza1439
    @cleversonsouza1439 Рік тому

    Thank you for doing it!

  • @aleksandergjoni888
    @aleksandergjoni888 4 роки тому +1

    Like. Very well explained 👍

  • @Jordan-yc3fs
    @Jordan-yc3fs 4 роки тому +10

    The sound of that pen on that paper is making my blood boil😁

  • @alunroberts1439
    @alunroberts1439 3 роки тому +1

    Dam good very clear good job

  • @imrangassafe
    @imrangassafe 4 роки тому +1

    thank you for this great video

  • @rrenvrrenv8014
    @rrenvrrenv8014 4 роки тому +1

    In plain English
    The 80% figure compensates for the cable being tested being colder during the test than it would be under fault conditions

  • @boden7815
    @boden7815 4 роки тому +2

    On a eicr what should be put in the table? On my 2391 we were told we had to write the 80%value in but that we can make a note on the side of the 100% value. However someone else told me that no you put the 100% value on the table nothing else

  • @cumberland1234
    @cumberland1234 4 роки тому +2

    I feel very old now - the old 230v value and the new 230x0.95 value - I remember it being 240v back in the 16th edition days!!

    • @angelofranklin1
      @angelofranklin1 3 роки тому +2

      They come out with all this but in reality, when you check the voltage on the secondary side of the transformer it's always 240 + volts, when you check at your distribution board nine times out of ten it's over 235 volts, Thank God we are out of Europe. with this harmonization rubish.

    • @cumberland1234
      @cumberland1234 3 роки тому

      @@angelofranklin1 I don't know if it will change now to be honest. I know we used to use 240v in our calculations as this is the Uoc ie at the transformer. The efli included the wiring from the transformer. Now we seem to be bending over backwards to make things more complicated and difficult for ourselves.

  • @kirkadams9530
    @kirkadams9530 4 роки тому +1

    Great video! Thanks

  • @martinh7620
    @martinh7620 4 роки тому +1

    Hi Matt i think this is amazing tutorial video i like GSH stuff sure but wow this is on a different level can you do some more, that will be so cool to see math behind all of it. it makes so much more sense .thanks guys

  • @fernandez571
    @fernandez571 2 роки тому

    What values do I put in the max Zs column on test sheets? 80% or the 100% values?

  • @nickpreece7516
    @nickpreece7516 Рік тому

    What about if you were doing "live testing only* on an EICR? Wouldn't the EFLI values then already be at "operating temperature" and should you then use the 100% max values when verifying the results?

  • @earthrelated
    @earthrelated Рік тому

    Thank you so much !

  • @Khanjan-si8me
    @Khanjan-si8me 4 роки тому +1

    Thank you do more video plz 🙏🙏❤

  • @paulmorrey733
    @paulmorrey733 4 роки тому +3

    Thanks

  • @quick1two
    @quick1two 4 роки тому +1

    You could also inverse the calculation - 1.1 ÷.8 = 1.375 ohms

  • @stevethomas5849
    @stevethomas5849 2 роки тому

    In the NICEIC Certificate Pads it has 80% at 1.08 ohms for a type B 32

  • @dragonboy1533
    @dragonboy1533 4 роки тому +4

    👏👏

  • @mij.londoner
    @mij.londoner 4 роки тому

    Great video
    Good explainations,
    At 8:10 you mentioned 80% (1.1) x 1.25 fig .. how do you achieve the 1.25 figure and what does it represent. Many thanks

  • @markhorton8578
    @markhorton8578 4 роки тому +12

    Good grief, you sure know how to make a simple calculation look complicated.

  • @MrPowellfactor
    @MrPowellfactor 4 роки тому +1

    The time/current tables 3A4(type B) and 3A5(typec) say 0.1 sec to 5 seconds the other ,3A6 (type D)has two columns 0.4-5 seconds, why is this?

  • @jonathanrose456
    @jonathanrose456 3 роки тому +1

    Divide by the percentage then multiply by 100.
    (1.1/80)*100=1.375ohms
    Simples 🤗

  • @MFayyyad
    @MFayyyad 2 роки тому

    how we get the BS 7671 soft copy?

  • @Spark101.
    @Spark101. 4 роки тому +18

    You literally just done the same sum in multiple ways to make a very simple calculation seem more complicated! Lol!

    • @GSHElectrical
      @GSHElectrical  4 роки тому +1

      🤣

    • @mb-electricalservices
      @mb-electricalservices 4 роки тому +2

      This is exactly why I fear maths and calculations in exams. You're expected to break it down to ridiculous levels to essentially come up with the same answer. :(

  • @arb7395
    @arb7395 4 роки тому

    Is it applicable for all types of earthing system TNS, TNCS, TT, IT .... Thanks

  • @markhorton8578
    @markhorton8578 4 роки тому

    Those log graphs often miss out the 9th lines to avoid line 10's looking like a really thick one. You just have to imagine it is there, very close to line 10.

  • @garethatkinson7765
    @garethatkinson7765 4 роки тому

    Quick one I hope, Ze on tncs 0.09ohms all good, but the manufacturers max zs on bs88gm fuse @400A 0.076. I have looked at other protection devices. Is my only option to try and lower the Ze from supplier ?

    • @TheBigstve
      @TheBigstve 3 роки тому

      Or introduce parallel paths.

  • @sulphuroxide1
    @sulphuroxide1 4 роки тому +2

    B x 5
    C x 10
    D x 20
    95% of 230
    Simples

  • @peterfitzpatrick7032
    @peterfitzpatrick7032 4 роки тому +5

    1.1 divided by 0.8 (the 80%) gives the answer quicker... 🙄😏

    • @electrodellinstallations556
      @electrodellinstallations556 4 роки тому

      Peter Fitzpatrick very true. I was suppose to say that way too. As many of the learners are having to understand fractions I concentrated on that but should of done your way too 👍

  • @bankraid2183
    @bankraid2183 4 роки тому +2

    When I’ve been testing the software on iPad says max zs 1.37 for B32 and I’ve always passed anything between 1.1 and 1.37, is this wrong?

  • @jamesdevlin2143
    @jamesdevlin2143 3 роки тому

    Yeah the reason behind the 80% and 100% here is off. The '100%' max Zs given in BS7671 is based on conductors at operating temperature 70*C. The '80%' max Zs given in the OSG is based on conductors at 10*C as they are likely that temperature when testing. Later when they're operating at 70*C the resistance will increase - it's accounting for that change.

  • @mariuskiudulas4498
    @mariuskiudulas4498 2 роки тому

    What’s the point then putting 100% value in the Regs book and then put 80% in the OSG? Why not just put 80% in both books ( ok you can change the formula in the regs so to understand where and what 100% Zs is on particular breaker but why not just add multiplication of 0.8 ( Zs= ( 230*0.95*0.8)/160= 1.1 ohms and then you get your 80% anyway and no confusion about what value you should take as acceptible Zs. I could be wrong but it come across like that to me..

    • @GSHElectrical
      @GSHElectrical  2 роки тому

      How to Calculate Total Earth Fault Loop Impedance - Applying a Temperature Factor to R1 + R2
      ua-cam.com/video/jF5Gf04GnlA/v-deo.html

  • @yetifanuk
    @yetifanuk 4 роки тому

    Isn't the 7671 value The 95% value ???????? CMIN ?????