I COULDN'T REALLY FIGURE OUT WHAT HAPPENED

Поділитися
Вставка
  • Опубліковано 27 гру 2024

КОМЕНТАРІ •

  • @tavidx
    @tavidx Рік тому +55

    carriers are bad for a weak capacitor causing 1 fan to run backwards and then they act as an intake outtake fan and lock both out on high pressure. Sometimes it takes a gust of wind to start 1 of them backwards then by the time you check it the thing looks fine.

  • @letter2steve
    @letter2steve Рік тому +46

    I love the fact that you are a younger dude doing old school troubleshooting tactics.
    It's quite refreshing to see reason and logic applied to fixing stuff.
    As a Canadian IT person trying my best to so the same, it's very refreshing to find others on the same track.

    • @DJSubAir
      @DJSubAir Рік тому +5

      Your are good person please keep doing good work!

    • @coolingexperts1580
      @coolingexperts1580 Рік тому +5

      Yep, there's a BIG difference between a "wreak-nition", & a technician

    • @letter2steve
      @letter2steve Рік тому +4

      @@coolingexperts1580 OMG wreak-nition is such a perfect term. Never heard that. Love it.

    • @burningdust
      @burningdust Рік тому

      It’s always a disappointment and frustrating to see the wrong people hired into a position. Parts swappers , no troubleshooting ability.. wreck-nicians

  • @richiegarcialopez13
    @richiegarcialopez13 Рік тому +9

    Extremely thankful for your channel, my father makes a real good point when he says that my generation has a lot of tools that his did not, UA-cam being one of them !

    • @HVACRVIDEOS
      @HVACRVIDEOS  Рік тому +1

      I will discuss this on my Livestream this evening 5/1/23 @ 5PM (pacific) on my UA-cam channel HVACR Videos come over and check it out ua-cam.com/users/live6F1EzlQ4ZE8

    • @reynaldos1chorizo
      @reynaldos1chorizo 2 місяці тому

      ​@HVACRVIDEOS i know im late on this video. but ive found restricted filter dryer causing high head pressure and low subcoolong on these unit's, but both were locked out so maybe a fan, and i also check the temperature on the condenser fans with a temp gun. im in arizona so i have seen fan stop right in front of me and check the temp it was at 195⁰. its a habit of mine to check fan temps during PM'S. i know you're thorough, and i try to be thorough as well. question, how long have you been in the trade? p.s. i have a bit of ADHD . just mentioned that in case you notice my comment is all over the place. thank you for your videos. i watch them and try troubleshooting along with you and see if i can come up with a similar diagnosis. ill pause after you provide more info and see if my thought process is in the right direction . im 1 year in, and im learning every day in the video and in your videos. take care and stay safe out there!

  • @1234bosses
    @1234bosses Рік тому +2

    Where is the dirt leg for the fuel line ? Be sure to check Condenser Fan Bearings. I used to check heat exchanger for holes. Could be time for a new unit.

  • @gregdennis3523
    @gregdennis3523 Рік тому +58

    The most challenging problems are the ones you can't duplicate.

    • @craigthepony6259
      @craigthepony6259 Рік тому +2

      Cars be like when you take it to the mechanic

    • @aaronbrandenburg2441
      @aaronbrandenburg2441 9 місяців тому +1

      That in any type of intermittent problems that can and will occur.
      Or that it takes a very specific sequence of several different events to get a problem to occur!

  • @devandoucette4782
    @devandoucette4782 Рік тому +6

    In situations where there is lockouts but no definitive code to tell you why it locked out. I will always do the full visual of the belt filters etc. but will always run the unit in its current condition to see what my readings are with the dirty filters or whatever may look out of sorts. Can sometimes help take away some of the uncertainties.

    • @Elisummit845
      @Elisummit845 Рік тому +3

      What I was thinking. I would have left the dirt filters in there and see what the readings are.

  • @andrewgilbreath1331
    @andrewgilbreath1331 Рік тому +4

    Chris looks to me like you nailed the issue that was a good bit of dirt that came out of the condenser coil, that combined with nasty filters and a good hot day 85+ could have kicked it out on high head. You have to think about the difference an 85+ vs a 70 degree day makes. That or with the dirty filters and a cold morning could have frozen it out.

  • @fshn76
    @fshn76 Рік тому +11

    Great video! It always drives me nuts when I am not 100% sure of what causes a problem. Glad I am not the only one that talks to themselves when troubleshooting.

  • @moconnell663
    @moconnell663 Рік тому +3

    I do factory service on fiber optic equipment for the broadcasting industry. The first thing I do after a visual inspection for obvious damage is to clean the fiber ports. After I've done that, 90% of units go though the test procedure with flying colors. I won't contaminate my lab tools with cheeto dust or bong resin or boogers, or whatever else field techs manage to smear onto their fiber optic assemblies.

  • @KevinOsborne1987
    @KevinOsborne1987 Рік тому +19

    Damn. I love fault finding but it's SO frustrating when you can't replicate the fault!! I know the pain! But you did everything you could do!!

  • @michaelthurber2660
    @michaelthurber2660 Рік тому +8

    Enjoy the topic. As a thought consider NU22, it is a close match to R 22, but by no means is equivalent, BUT much cheaper. If the unit was even in good condition, I too would go r-22, but take a look at the TP chart as a comparison. As temps at outdoor ambient gets higher the similarities fade... In addition the only think that comes to mind for the CLO fault MAY be a corroded connection or something like that, but since I also doubt it, I still have to mention it. SHit happens when you are not there and like the person below me said, "It never happens while you are there. The CLO are also notorious for corrosion. My .02
    MPT...

  • @gregmercil3968
    @gregmercil3968 Рік тому +2

    I’m always glad to see a video on one of these, since I got into commercial over 3 months ago it seems like 90% the equipment I come across are these Carrier Weathermaster/maker/takers. Though lately I’ve had a run of Lennox RTU’s.

  • @mypindiwala
    @mypindiwala Рік тому +4

    I had one unit with lock out board.occasionaly was giving me same lock out symptoms with 407c. Finaly I by passed that board and never had lockout issue again.

    • @Elisummit845
      @Elisummit845 Рік тому +3

      I once had a low pressure cut off keep cutting out so I bypassed it, never had a low pressure cut out on that unit again 🤣. I'm just messing with you, this thought just popped into my head so I had to lol. Btw if I would be in your shoes I would probably do the same.

  • @davidberger4726
    @davidberger4726 Рік тому +2

    So, If you change the refrigerant you kind of, have to re - engineer the unit!! That takes a bit!! It's a lot of fun but it can be a pain! All in all, well done!!

  • @naoumhalamoutis1960
    @naoumhalamoutis1960 Рік тому +4

    you would see that dirty condenser on the high pressure gauge

  • @HVACRTECH-83
    @HVACRTECH-83 Рік тому +7

    Once you ran it towards the end of video and building load came down to normal, I agree with you that circuit one looks like restriction in liquid line/or orifice. The second circuit though may be normal. Really helpful if there's a manufactures charging chart for the fixed orifice systems, if not I use a universal total superheat chart for fixed orifices. Indoor wetbulb/ outdoor drybulb gives you you're target superheat. when load comes down to normal in the building its not uncommon to see low evap superheat even as low as 2 like you had, without a chart to work off of its hard to tell if you're overcharged or if you need to dive in deeper. I don't work on hardly any fixed metering devices these days, pretty rare where I work which is why the charts are a life/system savor

  • @extracrazyguy
    @extracrazyguy Рік тому +2

    Wax clogs in the metering lines .. 407c and R22 both hate alkyl and mineral oils in high heat environments.
    So im willing to bet that you have some wax junk in the metering device that really only shows up when the machine is loaded down in the heat.
    ALSO those glassfloss filters are possibly overkill for someone who doesnt keep regular maintenance .

  • @Geyer128
    @Geyer128 Рік тому +1

    You are lucky. Where I liveR22 is banned since 2015. My heat pump is using R22. If there is an issue with refrigerant circuit, it must be replaced. As long as it is working, it may stay :)

  • @Tgaguy33
    @Tgaguy33 Рік тому +2

    Hello from New Zealand. my first thinking is that blocked filters give you a colder evap coil due to lower air flow therefore lower heat absorbsion, this then reduces suction pressure due to reduced superheat and therefore lower head pressure. I would lean toward anti freeze stat lockout before high head pressures. clean filters and better airflow will help resolve that possibility. How many sensors in the fieldpiece kit? Love you videos! Our R410a is slowly being replaced by R32. large VRV still R410. single splits are generally R32.

  • @graham354
    @graham354 Рік тому +7

    For stage 2 you said it may be restricted but your super heat was 3-4 f. Wouldn’t a restricted fixed office tube cause high superheat?
    Thank you for your videos! I watch everyone!

  • @marioramirez6741
    @marioramirez6741 Рік тому +4

    It's funny this video came out because I've had 2 carrier systems do the exact same thing. One was a new install. Compressor was off on thermal. Upon reset there was no obvious sign why. Amp draw was good, pressures, tightened all connections, good temperature split etc... Still not sure what happened to this day.

  • @xiar5546
    @xiar5546 9 місяців тому

    I love how every condenser I’ve seen that you look at is almost always trashed. Even new ones you get are sometimes trashed.

  • @krisrosvold5007
    @krisrosvold5007 Рік тому +1

    Your clue on this one is the control wiring. The freezer Stat cuts off both compressors. Since it's the only safety that kills both, that's the issue. Can't prove it with gauges, but I'll be dollars to doughnuts that the coil froze up, triggered the freeze stat, and Bob's your uncle.

  • @DavidCuff-q2u
    @DavidCuff-q2u 10 місяців тому +1

    First stage is a wild card because of the 407C so the numbers are goung to be slightly off. Second stage with a sh of 2 doesnt really tell me there is a restriction in the fixed orifice. These units are notorious for restriction in fixed orifice but it's usually accompanied by slight or heavy frost at the orifices. Bottom line is the C coils are junk and the entire unit should be replaced. Great video!

  • @user-hj5le6lo9w
    @user-hj5le6lo9w Рік тому +3

    Condenser fan amperage increases when the cover is fully on. That one condenser fan reading 1.3a may actually be running above fla. Great vid!

    • @kenneth9271
      @kenneth9271 Рік тому

      Good point

    • @throttlebottle5906
      @throttlebottle5906 Рік тому

      it should be lower current with cover on, because it makes more resistance and lower total air flow, which takes the load off the blades and motor, which in turn increases rpm somewhat.
      the current will nearly always go down, unless it's some ECM cruft or something that adjusts speed to keep CFM the same.🤓

    • @user-hj5le6lo9w
      @user-hj5le6lo9w Рік тому

      @@throttlebottle5906 That would be correct if we were talking about a centrifugal blower like you’d see in the evaporator section. With an axial fan it’s the opposite. Applying more static/resistance to the axial fan increases the load on the motor increasing the motor’s amperage. I’m also assuming that were talking about non ecm or the typical psc motor.

  • @edilsonserafim4784
    @edilsonserafim4784 Рік тому +2

    Nice video,i am wondering if when the stage one compressor was replaced with 404R they didn’t purge while brazing and drier currently have a restriction

  • @nonamesplease8228
    @nonamesplease8228 Рік тому +2

    How would a dirty condenser cause high subcooling? If you're not rejecting enough heat with a dirty condenser then you would have low subcooling

  • @rockercover
    @rockercover Рік тому +4

    The way you started the video; *don’t shut the AC power off* ; thought maybe this Carrier system had alarm / error code memory, (circuit board module). (Which would be a unique Carrier system for the year you indicated). 😳

  • @joemorales9093
    @joemorales9093 Рік тому +3

    Have had good results w/ 422D....427A has been an issue 8/10.....

  • @tracysellman1562
    @tracysellman1562 Рік тому +1

    Chris, have you thought if a high-wind incident, on this unit, caused the fans to spin backward causing the lock-out from high-head pressures? I had a few problems with Sportsmen Outdoor Store and I had the same type of issues. For the life of me, everything checked out, I came back 3 times in one week, and on the last visit I was on the roof taking a break just going through everything in my head, and just then a 60mph gust knocked me off my feet, I swear I was in a tornado and could not stand back up for about 30 minutes until everything got back to normal and herd A/C units dropping out like flys, all on high head pressure lockouts, I went aww-haa lol ordered high wind should kits for all the units, Problem solved never had an issue with that location ever again.

  • @skanteroar
    @skanteroar Рік тому +1

    I’ve had those clo boards lock out after power outages and or power surges

  • @chadhartsees
    @chadhartsees Рік тому +1

    As a 'civilian' who likes to watch your videos, I'm surprised the industry hasn't incorporated gauges and temperature probes into the units themselves and the electronics, so that the board would know exactly the performance and a tech could later on know that there's a leak based on pressure loss over time, or what the head pressure was the night before when there was a failure, or see how the system was performing when it was working through a history download off a dashboard.

    • @chadhartsees
      @chadhartsees Рік тому

      @@kingbilliam2654 Do they really? Can a modern system monitor it's own charge and other vital data points live? Because those things you mentioned seem like yes/no safety cutoffs, vs being able to monitor a leak and other performance in realtime from an Internet dashboard or a plug in readout. Heck, 20 years old, they could have done that 30 years ago. This is kilobytes of data, you know? Small stuff.

  • @sercasti
    @sercasti Рік тому +3

    Great video. Rookie question, why didn't you probe the leads of the lockout boards before resetting the unit? That would have given you a hint

  • @YuShudNoe
    @YuShudNoe Рік тому +3

    Is it possible a pressure switch can be starting to fail ?

  • @ZRock7771
    @ZRock7771 Рік тому +1

    Don't forget that CLO board also reads compressor amps as well. I would've checked compressor amperage see if it was on the higher side.

  • @jacobkane3935
    @jacobkane3935 9 місяців тому +1

    Can you make a video or explain further how the switch from r22 to newer refrigerant causes issues?

  • @BrewSquad
    @BrewSquad Рік тому +1

    Almost 100% it tripped the freeze stat because of the filter blockage and the 407 taking way too long to even out so it probably froze the evap coil. That would explain why both comps were locked out.

  • @dashcamandy2242
    @dashcamandy2242 Рік тому +1

    I agree with you, this particular unit is overdue for replacement. Or at the very least, new coils; but the question of diminishing returns rears its ugly head again.
    I'm a huge proponent of "repair over replacement," but sometimes it's just not worth it.

  • @joeyf504327
    @joeyf504327 Рік тому +1

    didn't you say it out loud at 13:30? Only one freeze stat, plugged filters, so the evap gets cold, set the freeze stat and locks out both compressors at once.

  • @justynbrading7444
    @justynbrading7444 10 місяців тому +1

    If this was me, I would have confirmed which lock out you had. I also would have ran it without pulling filters, ect because I’d want to see what it was doing at the conditions they had. Also, if I saw low superheat and high subcooling then I might have tried to weigh out the gas and make sure you weren’t overcharged & then weigh it back in. I know you pressures weren’t crazy high but it’s just a way to confirm you charge was correct if you weren’t 100% sure. Troubleshooting units outside of their typical life span that are in rough shape are fun haha

  • @johnriff85
    @johnriff85 Рік тому +2

    Notes to customer: Unit tripped on high head due to being broken ass pile of bullshit running on tech provided spite and tears. Replace or fuck off IDC lol.
    These are the things that go through my head when dealing with stubborn customers.

  • @throttlebottle5906
    @throttlebottle5906 Рік тому +1

    maybe a brownout or phase loss stopped the fans/blower, assuming they're single phase. the compressors may have kept on chooching, depending on building load/backfeed.

  • @phillip5397
    @phillip5397 Рік тому +2

    I’ve seen too many of those compressor lock out boards faulty themselves.

  • @moonlightacmaintenance3232
    @moonlightacmaintenance3232 Рік тому +1

    I had one that had a loose terminal on the freeze stat that would intermittently fail.

  • @fvfgx
    @fvfgx Рік тому +1

    Did you check the blower amps because the adjustable pulley looked kinda big
    Ppl like to tighten the belts by making the pulley bigger causing the amps to go over the rating, geting hot and going off on internal limit causesing the freeze stat to trip

  • @coryevangelista310
    @coryevangelista310 Рік тому +3

    NU22 has always done me well on Copeland (non trane related) older equipment. Have you noticed any differences between 407C and NU22 in the summer in terms of better or worse subcooling and or super heat?

  • @douro20
    @douro20 Рік тому +1

    That foam gun looks very similar to the one sold by Nexgen.

  • @MattTrevett
    @MattTrevett Рік тому +1

    You're up on this roof all the time!

  • @adam7868
    @adam7868 Рік тому +1

    Second stage had a slight overcharge first stage i would say weak valve on the compressor or wrong refridgerant

  • @417HVAC
    @417HVAC Рік тому +5

    FreezeStat cuts both cutouts. 407c in circuit culprit. Cutout of freeze out at 44.8°.

    • @prettycureforever7102
      @prettycureforever7102 Рік тому +2

      And he said 22 starts out pretty low too or either the customers turn down the thermostats too low during the harsher of summer that could cause a lock out since 22 and 407 ain't really strong or efficient

    • @417HVAC
      @417HVAC Рік тому

      @@prettycureforever7102 check where the 407c circuit starts out at.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Рік тому +1

    Awesome video Chris....thanks for helping make the trade just that much better

  • @bm03431
    @bm03431 Рік тому +2

    What do the professionals here think about the "soft-start" devices for residential a/c units advertised on the internet and other youtube videos?

  • @naoumhalamoutis1960
    @naoumhalamoutis1960 Рік тому +2

    Wondering if you have a bad indoor fan motor tripping on thermal overload?

  • @Osirus1156
    @Osirus1156 Рік тому +1

    Out of curiosity with the open top of the drain clean-out do animals or anything ever get stuff stuck into it? Just curious why it doesn't have a little vent cover.

  • @ersham13
    @ersham13 Рік тому +1

    wondering how high sub cooling(cold refrigerant) equals dirty condenser?? metering device problem..........

  • @krz8888888
    @krz8888888 Рік тому +6

    I thought high subcooling meant that the condenser was overachieving by cooling the refrigerant too much, not being plugged up, TIL

    • @HVACRTECH-83
      @HVACRTECH-83 Рік тому +4

      High subcooling is the result of liquid backing up in condenser do to a number of reasons. System capacity is reduced when this happens. You can have high subcooling however from a restricted condenser as well. This happens because the head pressure rises more than normal and increases your ctoa. Therefor you'll have a larger temperature difference between refrigerant saturation and ambient which results in more heat transfer than normal conditions even though the condenser may be plugged or fan not operating as designed,ect. T.d. is everything. Also a good example of why you don't even want to check for system operation until you have confirmed your coils and filters are clean and you have correct system airflow, or waterflow depending on what you're working on

    • @jac6541
      @jac6541 Рік тому +2

      High sub cooling reading Also occurs when your condensor is extremely dirty or when condensor coils are brittle and not enough heat is rejected from condensor.

    • @2centsbear638
      @2centsbear638 Рік тому

      ​@@jac6541 subcooling is how low the temp is compared to sat temp. So the refrigerant could be backed up by a plugged part and is sitting in the coil for longer giving it more time to cool

  • @chrisparkinson9237
    @chrisparkinson9237 Рік тому +1

    R407c can cause high head pressure if system is low on gas or it hasn't been fully charged in liquid phase, the total opposite to what you would expect from say R22. Its a nightmare of a refrigerant

  • @Etorfason
    @Etorfason 8 місяців тому +1

    With that high if subcooling, and you being after the drier, I would think plugged drier. You were condensing 30° above amb. So nothing looks like a head pressure problem. I would say the r22 was over plugged drier.

  • @jeremyhall7495
    @jeremyhall7495 Рік тому

    Awesome video, great information, thanks !

  • @johnwalker890
    @johnwalker890 Рік тому +3

    Good job Chris, Might end up buying one of those Dad hats later on, after I figure out my budget, Because of Bidenflation.

  • @natek327
    @natek327 9 місяців тому +1

    It seems like it could be a fan issue to me. Could be a failing fan hence the different current draws, but I'd also be curious if the fan blade was loose as you noticed the one blade was a bit low... maybe it was slipping at certain temperatures

  • @FrNMGuy
    @FrNMGuy Рік тому +2

    I wonder if during high ambient, the resistance in the fan motors decreases enough for them to go off on thermal overload.....and lower ended capacitors would exacerbate the issue

  • @bobbymcnutt8046
    @bobbymcnutt8046 Рік тому +1

    Is it possible that either the low or high pressure switches are getting weak?

  • @thegun98
    @thegun98 Рік тому

    Thats weird. I've had like a few brand new York units at target doing the same thing saying freezestat but when they are tested all numbers are near perfect and the unit runs totally fine with no issues and the problem never returns. Still makes me question how a freeze stat only fails once and the issue never returns.

  • @steveurbach3093
    @steveurbach3093 Рік тому +3

    That 1 fan seems to be slower than the other. You said was same motor.

  • @landonferguson7282
    @landonferguson7282 Рік тому +2

    Could it lockout if the lockout board read too high of amps on one of the compressors?

    • @user-hj5le6lo9w
      @user-hj5le6lo9w Рік тому

      I think those lockouts will only go off on low to no amperage

  • @zekenzy6486
    @zekenzy6486 Рік тому

    Great Video. Thank you for sharing

  • @HVACRTECH-83
    @HVACRTECH-83 Рік тому +3

    Man I really don't love those double stacked coils, so hard to tell how good you're cleaning it. Every one I come across I just assume is plugged between the two.

  • @BlackMan-ld9fl
    @BlackMan-ld9fl Рік тому +1

    If the thermostat was calling for cooling, would it not read 0 volts?

  • @keepnitkool9042
    @keepnitkool9042 Рік тому +2

    I’d check pressures with filters in first

  • @chevydmax237
    @chevydmax237 Рік тому +4

    You had the cover open air was bypassing the condenser

  • @joshstevens9826
    @joshstevens9826 Рік тому +4

    Two things. One you ran the rtu without the original filters. So, you didn't ru it with the same conditions as the lock out. Very well could have been low pressure, as dirty as the filters were.
    The other thing is high sc is not dirty condenser. That would be low sc. Looks to me like that ckt was over charged. High sc low sh.
    Just my two cents

    • @jphvac5725
      @jphvac5725 Рік тому +2

      20° sc is normal on those 7.5ton carriers. Work on that same model all the time and when recharged to factory charge it’s usually right at 20°.

  • @byrd203
    @byrd203 Рік тому

    why did you mix the refregratant 407c on st1 R22 on ST2 should the unit have the same on both stages

  • @hvacboy5591
    @hvacboy5591 Рік тому +2

    Is it just fixed orfice metering devices that you had trouble with R407c?

    • @HVACRVIDEOS
      @HVACRVIDEOS  Рік тому +1

      yes Ive had good luck with 407c on txv systems

    • @jphvac5725
      @jphvac5725 Рік тому +1

      @@HVACRVIDEOS my guess is the switch from mineral oil to Poe causing restrictions. However we both know high head pressure from intermittent condensor motor/dirty coil can easily cause those piston metering issues also. Have had lots of those units and still do.

  • @mrgreen9086
    @mrgreen9086 Рік тому +3

    I would probably weight in the charge for both circuits especially 2nd stage

    • @richardbartlett6932
      @richardbartlett6932 Рік тому +1

      You should always weigh in the refrigerant to the label. Once you remove that low charge high charge you can go fault finding
      Far too many techs chase their ass round and round rather than doing the basics first
      My first ever boss told me " never assume" best bit of advice ever.

  • @naoumhalamoutis1960
    @naoumhalamoutis1960 Рік тому +1

    Can you do a training video on leak repairing R290A units?

  • @crazydan2327
    @crazydan2327 Рік тому

    Why didn't you patch up that square opening in the service door I see that on all carrier units

  • @Goldstacker1972-kp2bh
    @Goldstacker1972-kp2bh 9 місяців тому +1

    Did you say y1 and y2 were using only one wire to control both circuits,?

  • @crazydan2327
    @crazydan2327 Рік тому +1

    The one near the open service door is drawing more amperage its moving more air

  • @daveyt4802
    @daveyt4802 Рік тому +1

    Where is the main control board? Errors? Not a fan of Carriers. Pretty large open hole cover there. Dual layer condenser coil? Dirty in between?

  • @brianporter447
    @brianporter447 Рік тому +1

    What kind of oil you got running with that 407c?

    • @HVACRVIDEOS
      @HVACRVIDEOS  Рік тому

      POE oil

    • @brianporter447
      @brianporter447 Рік тому +1

      I have no problems with 407c. I actually replaces both compressors about 2 years ago in that same model. That's the first i have heard of anyone having issues. Not to say techs don't. But sorry to hear that.

  • @commenter5469
    @commenter5469 Рік тому +1

    I guess Chris got a little hot. 😁
    Don’t know where the conclusion of high sub cooling explained the condenser fins being dirty. Air flow problems would actually cause lower sub cooling.
    The liquid line restriction - that’s what will cause the high sub cooling.

  • @MichaelCowden
    @MichaelCowden Рік тому

    Can you list some specific things that would be criteria for deciding when a 407C conversion isn't going to work well, as in this case?

  • @joshpearson1693
    @joshpearson1693 Рік тому

    Can you go to 22 from 407c with the poe oil

  • @garageink74
    @garageink74 Рік тому +1

    I find when these are locked out and you can’t find an issue you will end up coming back to change a condenser fan motor sooner rather then later.

  • @MariosACandRefrigeration
    @MariosACandRefrigeration Рік тому +3

    perfect time to use r422b like everyone else.

  • @thaddeusfeldhouse6174
    @thaddeusfeldhouse6174 Рік тому +1

    By the looks of that condenser, it looks like the fins are delaminating from the coil.

  • @davidhazas7162
    @davidhazas7162 Рік тому

    If that second circuit is restricted then wouldnt your superheat be high too not 2 or 3 degrees, overcharged maybe, and dirty coil causes no subcooling not high subcooling right. Probally going off on high pressure on hot day. Not 70 degree day.

  • @dylanmovchan6139
    @dylanmovchan6139 8 місяців тому +1

    Has anyone ever in the history of HVAC ever checked return air ductwork?

  • @kylenicks991
    @kylenicks991 Рік тому

    Try using MO99 in place of R22

  • @coolingexperts1580
    @coolingexperts1580 Рік тому +1

    Can't wait to get off work, then I catch myself watching others work, WTF ??? LOL

  • @gabesreef
    @gabesreef Рік тому +5

    My app crashed and caused no sound. Really thought you went 3 for 3 there 😂😂

    • @HVACRVIDEOS
      @HVACRVIDEOS  Рік тому +3

      No i triple checked this one....

    • @gabesreef
      @gabesreef Рік тому +1

      @@HVACRVIDEOS 🤣👍🏾

  • @michaelkuprian01
    @michaelkuprian01 Рік тому +2

    I would of knocked the cinder block down the return.

  • @snoopyjc
    @snoopyjc Рік тому +1

    Just placed an order at True Tech Tools and used the BIGPICTURE discount code - thanks!!!

  • @grudd61
    @grudd61 Рік тому

    Uda man! Thanx for sharing!

  • @Hvacmaniac97
    @Hvacmaniac97 Рік тому

    finding that needle in a hay stack. just slap a new one if not move to the next call

  • @kat2641
    @kat2641 Рік тому +2

    Sorry but I must disagree with you for a little bit. I think you actually had it pegged ..let’s put it in a equation..
    A…… filters were from what I seen at least 75% plugged.
    B….. condenser coils were close to 30%
    On a package unit; if we have a restricted air flow over the coil that screws with our return temps an pressure . An while I will agree the condenser coil was not terribly bad that too is going to effect our Temps an pressures.. I am ( only guessing here) but I am thinking we had a possible coil freeze.. but even tho 22 is bad for us we have to admit 22 would run an work in impossible conditions…and the cooling curve over all is way different than 407 . .. Actually I hate 407 because it is?? I personally think the mix percentage is and was screwy from the get go. I will agree the unit is on its last leg but I think you DID peg the problem! it just was not a stick out like a sore thumb definite cause problem .. 😂 So I am disagreeing that you “didn’t” find the problem ❤
    Edit… question?what would of been our results if we had left the dirty coil filters in to begin our troubleshooting 🤔🤔 I am betting we might of re-created the original problem.. but I have done the exact same thing you did. An pulled them out an had a retired HVAC friend with me that day an he said Man I wouldn’t do that . Why Bob??0.0 He said first your trying to find what caused the unit to lock out right ? Well yea but Bob I can see they are plugged an a problem… laughing. Bob was a mentor to me, and he had three times experience I had. Wish he was still alive. I wish I knew what he had forgotten over the years.

  • @walterpena2430
    @walterpena2430 Рік тому

    All those carrier units suffering from restrictions on the fix orifices for next time

  • @danpresson
    @danpresson Рік тому +1

    Awesome video

  • @naoumhalamoutis1960
    @naoumhalamoutis1960 Рік тому

    Have you used the R32 refrigerant yet?