anu sukat ng battery mo? or pweding sira na dc bus capacitor mo. ma check mo muna voltage ng mga battery. tapus replacement ng capacitor pag okay naman ang batery.
Hello sir, Eaton 93e 15kva gamit ko, may problema po sya DRIVER VOLTAGE FAULT. pinalitan na po motherboard at interpiece daw yun ng service provider namin, pero ganun pa rin po problema.
yes, sir. this model is hard wire so basically you need to connect wire directly at the back of UPS and the other end of wire with outlet to connect your PC..
hello! please assist here... my UPS indicated that there is unbalanced input voltage, how can i solve this... am new into this UPS technology, i have never done one before.
did you check the battery? voltage must be 240vdc positive and 240 negative total of 480vdc at float when charging it is 500 up.. if yes, next is the PSDR problem check the fuse or replacement of whole board.
Hello sir. My UPS kmi eaton 93e 80kva power module over temperature ang error ano po kaya ang sira at mgagawan pa b ng paraan para maayos? thank you po.
reset sir wala na, patayin at buhayin lang sir.. A500 po ay charger fault , charger malfunction po.. check nyo po mga fuse ng charger or using Ampmeter test mo sir kung my ampere reading..
@@3dfire thank you for the reply. By the way sir nag generate po ako ng logs using eaton software. tapos ito po yung lumabas. Ano kaya po ibig sabihin nito sir. Status - Current Active Alarms or Faults Fault Site wiring fault that can come of Phase neutral inversion on single phase UPS. Bypass input status in fault Charger internal failure Battery is discharging MBP disconnected Fault
ah ok naka sitewiring fault sya kaya di nag charge. Anu po model ng UPS mo sir? anu gamit mo na program sir? punta ka ng setting sa program disabled mo sir ang site wiring alarm.
di ko lam yang program na yan sir, pero check mo sir kung my settings para sa site wiring disable madisable mo sir. pag wala po download mo sir yung Eaton Service tools po or UPS companion sir..
That, alarm is over charge, or recharge voltage is too high.. posible check first the batther voltage, and voltage for each bank and total votage and individual voltage of battery check..
sir mag kno po yan
san po location nyo sir?
I have F704 error on the 10kva, any idea? We have changed the faulty components on the main board
F704 is Failed inverter.. If possible, disconnect the power
to the load, switch the UPS off and
back on again. restart the UPS.
i have F305 error on startup, can you give me some idea?
anu sukat ng battery mo? or pweding sira na dc bus capacitor mo. ma check mo muna voltage ng mga battery. tapus replacement ng capacitor pag okay naman ang batery.
Hello sir, Eaton 93e 15kva gamit ko, may problema po sya DRIVER VOLTAGE FAULT. pinalitan na po motherboard at interpiece daw yun ng service provider namin, pero ganun pa rin po problema.
ohh sir, eh dapat gumana na yun sir kasi motherboard na pala pinalitan sir.. my isa pa nun sir sa control board sir.
@@3dfire Gumagana naman po sya sir, kaya lang bumabalik din po alarm niya. Salamat po pla sa reply.
Sir ask kulang ano bah wirings mo sa input , sakin kasi sir. RSTN pero 220v lang ang pwede? Pa help naman sir
hindi po sir, dapat kung 3 phase naka 380 400 o 415 ag voltage po natin with neutral at grounding po.
sa gantong model.
Can i connect pc directly to it? How?
yes, sir. this model is hard wire so basically you need to connect wire directly at the back of UPS and the other end of wire with outlet to connect your PC..
hello! please assist here... my UPS indicated that there is unbalanced input voltage, how can i solve this... am new into this UPS technology, i have never done one before.
what is your source? 3phase or single? what model and capacity of your unit?
for 9E 10kva up. for sigle phase is your jumper wire is connected?
@@3dfire its 9E20Ki Model, 3phase supply
@@3dfire you mind sharing a video on how i can solve the unbalanced voltage,
did you check the battery? voltage must be 240vdc positive and 240 negative total of 480vdc
at float when charging it is 500 up.. if yes, next is the PSDR problem check the fuse or replacement of whole board.
Sir my wring diagram k po b ng ups.to to panel box .changed over switch
wala sir, pero drawing ka sir check ko nalang.
Can you halep m'y l have one 10 kva i nid installation electrical for strartd thanks you
Eaton brand sir?
required upstream breaker sir is 60A.
sir,
i bought 20kva Eaton 9E but the battery came with out Rack how do i connect the battery with UPS Tower Sir
under warraty sir?. send me an email sir crisf2004@yahoo.com
EBM sir, or other battery? then below the breaker at the back of UPS there is a terminal fuse for the battery..
Hello sir. My UPS kmi eaton 93e 80kva power module over temperature ang error ano po kaya ang sira at mgagawan pa b ng paraan para maayos? thank you po.
Sir good pm, ganu katagal napo ang unit? my PM contract po ba sya?
@@3dfire nsa 6 years n po sir.dati my contractor nag ppm now po wla n kaya naghahanap panibagong contractor
need yan sir ma service san para ma check talaga sir, kasi posible ang part na mismo ang my problem sir..
pasa ko po contact nyo sir sa mga nag huhundle nyan..
@@3dfire thank you sir
Юпиеса работи много по добре когато е проектиран напрежението на батерията да е поне 384 волти. Тоест поне 32 батерии.
sir may lumalabas na A600 pano po ang gagawin ?
Pacheck po sir nga battery? ganu katagal napo ang battery, anu po mga sukat.? base po kasi sa alarm wala po sya nakikitang battery.
Boss, meron akong UPS 10kva Eaton 9E, nagpalit ng mga mosfet then gumana sya tapos nagkaroon ng error A502 need ba mag reset? thanks
A502- ay pweding sa battery masyado mataas na ang voltage, or mababa, pweding sa charger din.
sir may nerereset ba if nagpalit ka ng battery nito? may error code din kasi sya na "A500".
reset sir wala na, patayin at buhayin lang sir.. A500 po ay charger fault , charger malfunction po..
check nyo po mga fuse ng charger or using Ampmeter test mo sir kung my ampere reading..
@@3dfire thank you for the reply. By the way sir nag generate po ako ng logs using eaton software. tapos ito po yung lumabas. Ano kaya po ibig sabihin nito sir.
Status - Current Active Alarms or Faults
Fault
Site wiring fault that can come of Phase neutral inversion on single phase UPS.
Bypass input status in fault
Charger internal failure
Battery is discharging
MBP disconnected
Fault
ah ok naka sitewiring fault sya kaya di nag charge. Anu po model ng UPS mo sir? anu gamit mo na program sir? punta ka ng setting sa program disabled mo sir ang site wiring alarm.
@@3dfire eaton 9E 6000i (9E6Ki). Eaton SetUPS po gamit ko na software sir.
di ko lam yang program na yan sir, pero check mo sir kung my settings para sa site wiring disable madisable mo sir.
pag wala po download mo sir yung Eaton Service tools po or UPS companion sir..
sir San po kmi makakabili Nyan mag Kano po yan
anu email mo sir and complete name nyo po. pa sendan ko po kayo price sir.
Pls can you make videos on ups 9355 eaton 12KVA.... and speak english pls
Oh My Goodness !!!! Man! ! Speak English or put English subtitles ....
You are making it hard for everybody here !!!
ok sir. on my next video.
hlo sir this ups A 502 error code coming
how to reset this alarm
That, alarm is over charge, or recharge voltage is too high.. posible check first the batther voltage, and voltage for each bank and total votage and individual voltage of battery check..
Why it have alert sound
You take me about it
again?.. alert sound of?..
you mean sound during power On?
walang simumation to bypass mode
anu unit po sir?
awesome . pls speak English