Good evening, I would like to ask you a question, I hope you can help me, I have a m340 with the included tcp port, as it would be to access the atv600 registers, I do not have a NOE module
Hi Mr, I saw that you use RD REF and WR RED with value "0" is that the modbus registers, because I saw after that in the VFD the modbus register, one begins 3201 and the other in 8501. What I'm missing in this configuration?
if you look this pdf , its programming manual for atv9xx series media.distributordatasolutions.com/schneider/2016q2/fef677e41765147443ac338c0ffc3ad128a2d0f9.pdf look for page 540 and 541 so you can see the Address of the first input word is 3201 (EtA) and Address of the first output word is 8501(CMd).
Hi Moises, the procedure is very similar when using the Modbus TCP ethernet card on the ATV71 or ATV61. There are some small differences that you must be aware of. The scanner table will be a maximum of 11 words read and write, however the first word in each is a reserved word and needs to be ignored.
Good video
Excelente video, muy completo!
Exelente video, por favor puedes hacer el video con M580.
Hi. Did you have the actual drive connected when simulating?
Good evening, I would like to ask you a question, I hope you can help me, I have a m340 with the included tcp port, as it would be to access the atv600 registers, I do not have a NOE module
Hi Mr, I saw that you use RD REF and WR RED with value "0" is that the modbus registers, because I saw after that in the VFD the modbus register, one begins 3201 and the other in 8501. What I'm missing in this configuration?
if you look this pdf , its programming manual for atv9xx series
media.distributordatasolutions.com/schneider/2016q2/fef677e41765147443ac338c0ffc3ad128a2d0f9.pdf
look for page 540 and 541 so you can see the Address of the first input word is 3201 (EtA) and Address of the first output word is 8501(CMd).
For me also same doubt
No it's not Modbus registers, it's IO Scanner address. in your VFD you set it up.
this procedure is the same for a ATV 71 ? on a Ethernet card?
Hi Moises, the procedure is very similar when using the Modbus TCP ethernet card on the ATV71 or ATV61. There are some small differences that you must be aware of. The scanner table will be a maximum of 11 words read and write, however the first word in each is a reserved word and needs to be ignored.