Why an Air Conditioner Coil FREEZES! Examples, Procedures, Troubleshooting!

Поділитися
Вставка
  • Опубліковано 30 чер 2024
  • In this HVAC Training Video, I go over the Reasons Why an Air Conditioning Coil, Tubing, and Valves could FREEZE! I show how to Troubleshoot to know if you have a Liquid Line Restriction, Low Refrigerant Charge due to a Leak, or Low Indoor Airflow and find the Problem! Supervision is needed by a licensed HVACR Tech while performing tasks as Experience and Apprenticeship garners Wisdom and Safety.
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our Related Videos
    • Frozen Evap Coil Troub...
    • Frozen Evap Coil, Trou...
    • Liquid Line Restrictio...
    • Low Indoor Airflow Pro...
    • 20 Causes of Low Indoo...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Educational Books, E-Books, Workbooks, Cards, Posters, and PowerPoints:
    All Our Educational Products on Our Site: www.acservicetech.com/store
    All Our Educational Products on Amazon: amzn.to/48pDd82
    Mini Split Book and E-Book on Our Site- www.acservicetech.com/mini-sp...
    Mini Split Paperback on Amazon- amzn.to/3ytHJSs
    Mini Split Paperback on TruTech Tools- www.trutechtools.com/BooksGui...
    Refrigerant Charging Book and E-Book: www.acservicetech.com/ac-book
    Refrigerant Charging Paperback on Amazon: amzn.to/46xTeHf
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Our HVACR Online Resources!
    Our HVAC Calculators: www.acservicetech.com/hvac-ca...
    Our Newest Articles: www.acservicetech.com/articles
    Try our HVAC/R Quizzes! www.acservicetech.com/quizzes
    Our Other Resources: www.acservicetech.com/resources
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Tools Used in Our Videos!
    Tool Links on Our Site: www.acservicetech.com/tools
    Our Tool List on Amazon: www.amazon.com/shop/acservice...
    Support the Channel by purchasing tools through TruTech Tools!
    Use this link www.trutechtools.com/?aff=8
    Save 8% at checkout using code "acservicetech"
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Follow Us On Our Social Media & Podcasting Channels!
    Patreon: / acservicetech
    Facebook: / acservicetech
    Instagram: / acservicetech
    X: / acservicetech
    LinkedIn: / ac-service-tech-llc
    Tiktok: / acservicetech
    Spotify: open.spotify.com/show/74KXLz5...
    Apple Podcasts: podcasts.apple.com/us/podcast...
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    ⚠️ Disclaimer:
    Information in this video is intended for educational purposes only. Any work related to the topics in this video should be performed by licensed technicians or by apprentices under the supervision of licensed technicians. AC Service Tech LLC is not responsible for any possible damages or injuries caused by the use or misuse of any information provided.
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    #hvacr #hvacr #hvactrainingvideos #hvactraining #hvactraining101 #acservice #acservicetech #evaporatorcoil #coil #freeze #procedure #troubleshooting #TXV #frozencoil #liquidline #restriction #refrigerant
    ▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬▬
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal.

КОМЕНТАРІ • 126

  • @keovongvilaykeo4799
    @keovongvilaykeo4799 2 роки тому +3

    What happen when A/C continuous running none stop, don’t that cause system to freeze up ?

    • @acservicetechchannel
      @acservicetechchannel  2 роки тому +5

      Absolutely if there is not enough heat to absorb because the indoor temp has dropped down way too low. However if the temp inside remains the same due to a high heat load then no it shouldnt freeze. If it freezes, that means that you likely have a low indoor airflow problem.

    • @keovongvilaykeo4799
      @keovongvilaykeo4799 2 роки тому

      @@acservicetechchannel thanks for advice I think so too airflow issues EWC Zone Control

    • @workingshlub8861
      @workingshlub8861 Рік тому

      bad thermostat

    • @gunasekar4764
      @gunasekar4764 Рік тому

      In case if oversize txv is installed then indoor evaporator coil and compressor will get ice formation pls could you advise

    • @ContinentalAC_Tom
      @ContinentalAC_Tom Рік тому +1

      @@acservicetechchannel ON 🎯 🎯 🎯 💪🏼 💪🏼 💪🏼

  • @Matthew-jr1xr
    @Matthew-jr1xr 4 місяці тому +6

    Why go to college when you can watch this guy's channel? Haha. Watch the adds, like, comment, subscribe, whatever you can do to help him out. Lord knows he's helping us. 👌

  • @billb.4901
    @billb.4901 2 роки тому +18

    Nice video. Your explanations are top notch. I learn so much from your videos. I really appreciate all of your effort to pass along your knowledge.

  • @ed78vette
    @ed78vette 2 роки тому +11

    Dude, you’re OUTSTANDING! I thoroughly enjoy your tutorials. Keep up the great job.

  • @coldfinger459sub0
    @coldfinger459sub0 2 роки тому +7

    Saved into my favorites category for HVAC to pass along to others 👍

  • @MichaelHernandez-lc2wb
    @MichaelHernandez-lc2wb Рік тому +8

    What a perfect, concise, and clear explanation. I cant thank you enough!

  • @JohnDoe-gk4kn
    @JohnDoe-gk4kn Рік тому +3

    Thank you. I have a liquid line restriction issue. Now I can speak to my AC guy and tell him quit screwing me over your fired. My guy has been leading me from one thing to another charging me a fortune. Today he said its a leak I need a new Furness but he never perform a pressure test.

    • @alexandronegrete2997
      @alexandronegrete2997 2 місяці тому

      You can do that with gauges or pin point the leak you still need certain lincenses to buy refrigerant

  • @edwinjewell5359
    @edwinjewell5359 2 роки тому +3

    Craig You are the
    Guru of Air Conditioning.

  • @Salty5hoe
    @Salty5hoe 8 місяців тому +1

    Learned more from this video than the college I went to in less than 20minutes

  • @stevenhyn3498
    @stevenhyn3498 2 роки тому +2

    Graig - You were born for a big reason. Thank you so much !

  • @vernroach3413
    @vernroach3413 2 роки тому +3

    Another good one...Even my brother understood it and he's not in the trade...Thanks again.

  • @natureventurememowi
    @natureventurememowi Рік тому +3

    Sir, you're an amazing teacher. So clear and concise. Thank you!!

  • @andresbs5947
    @andresbs5947 10 місяців тому +1

    I understand English but i have many friends in the field that only speaks spanish! I wish u had this videos translated much love! ❤❤😊

  • @AIthings82
    @AIthings82 9 місяців тому +1

    Always so well explained, this guy taught me a lot to improve my skills several years ago. Certainly learned more with him than at school. 😀

  • @joecooksey4331
    @joecooksey4331 2 роки тому +5

    Off topic, but you did a video a while back on p-traps. That video is SAVING me $$$. Here's why. 4 ton split 13 years old. It did NOT have a p-trap, but had a decent trickle of water coming out the PVC. I never thought much about it until I watched that video. I installed a Rectoseal trap and dropped the humidity 3-4% (46-47%) inside allowing me to turn the thermostat up 2 degrees. I now have an excellent stream of water coming out the drain! THANKS A MILLION!

  • @drz400sy9
    @drz400sy9 2 роки тому

    Great Video. My unit started to show water at the evaporator and shut down. Like you mentioned, it was actually my blower motor. Thanks for confirming my issue. Interesting it happened a few days after a HVAC cleaning and addition insulation around to copper tube at the condenser unit.

  • @luke9129
    @luke9129 2 роки тому +3

    Concise, tactful and as always a well thought out explanation Craig. Bravo sir on another video well done!!!

  • @robertovaldez2984
    @robertovaldez2984 2 місяці тому +1

    Good information, thank you.

  • @thecoolguy23
    @thecoolguy23 10 місяців тому +1

    Kink in the lines could be another reason for refrigerant restriction!! 👍👍👍 Good video 🤩🤩

  • @bassealhvactech2505
    @bassealhvactech2505 2 роки тому

    this is a great piece. thank you Mr. Craig. i am so loving it

  • @dougjones4987
    @dougjones4987 2 роки тому +1

    Thats quite the mic for an hvac guy. Great info thanks

  • @raulo1225
    @raulo1225 2 роки тому +3

    Craig you are a master always enjoy your videos

  • @taiwanluthiers
    @taiwanluthiers 9 місяців тому +1

    I got a mini split with a capillary tube metering device, and when I charge the system the suction pressure (and only suction) will stop at about 45-50 psi (R22) where the saturation temp is about -5C. It doesn't matter how much refrigerant I add after this, the pressure will not go up even if I end up putting in more refrigerant than what it says on the name plate (basically an overcharge). So I end up just stopping when the AC works reasonably well and not freeze the coil.

  • @johnt9684
    @johnt9684 2 роки тому +1

    Awesome video thank you

  • @prudent8538
    @prudent8538 Рік тому +1

    I think you went through all of the issues! Bahaha amazing!

  • @khalidsr1
    @khalidsr1 11 місяців тому

    Excellent explanation, many thanks😊

  • @Sido42785
    @Sido42785 20 днів тому

    Thank you so much for this amazing work

  • @Mudcat597
    @Mudcat597 2 роки тому +1

    Nice presentation and great information. Thank you for sharing!!

  • @rayalvarez7780
    @rayalvarez7780 2 роки тому

    Thanks again for these videos I’m learning so much from them keep them coming.

  • @sunilthaivalappil5229
    @sunilthaivalappil5229 Рік тому

    Very nice presentation Thanks

  • @allanfsecusana12
    @allanfsecusana12 13 днів тому

    Thank you so much for sharing

  • @gregtoczko4819
    @gregtoczko4819 Рік тому

    Excellent explanation of the problem. I can watch your videos for hours.
    Downflow system: what may cost liquid (refrigerant line) to sweat?
    The evaporator coil is freezing only on the lower portion of it ( not always)- according to you it's sign of liquid line restriction. Liquid line is always cold and sweating (most of the time but not always).
    Suction line is always warmer than liquid line.

  • @lugongguo8125
    @lugongguo8125 2 роки тому +1

    Thank you so much for explaining so many reasons. Gave a like and keep learning. 👍

  • @albertgarcia9662
    @albertgarcia9662 Рік тому

    I enjoy your videos.There is so much to learn. Your boots are much easier to follow . I'm going to college to learn to receive a certificate HVAC. I'll be buying your books hopefully soon. Again thanks

  • @deohbolik1
    @deohbolik1 2 роки тому

    Thank you for the wisdom.!!!

  • @rainman7769
    @rainman7769 2 роки тому +1

    Thanks for the easy explanation

  • @1DeltaT
    @1DeltaT Рік тому

    Thanks Craig, top notch

  • @keovongvilaykeo4799
    @keovongvilaykeo4799 2 роки тому +1

    Always appreciate your hard work thanks you again

  • @hvacinstalacije1985
    @hvacinstalacije1985 2 роки тому

    Thank you Craig

  • @williamserver4332
    @williamserver4332 2 роки тому

    Great video. I wish I had these videos 20 years ago when I was green. Even now they help

    • @acservicetechchannel
      @acservicetechchannel  2 роки тому +1

      I wish i did too. The best advice I was given when i couldnt solve a problem was to go out to the street, clear my head and then go back to the service call and keep trying! There were no videos to watch or answers found online or a way to search online while at the customers house!!!

  • @thesilentonevictor
    @thesilentonevictor 2 роки тому +1

    Well put together

  • @htownnc713
    @htownnc713 2 роки тому

    Nice video got your book also Im self taught thanks for the good videos! Still have more to learn.

  • @phillipjoy1305
    @phillipjoy1305 2 роки тому +1

    You got to love Craig.GREAT VIDEOS 😜

  • @fernandoescobar692
    @fernandoescobar692 Рік тому

    Clear like water, thanks

  • @chrismammedaty5215
    @chrismammedaty5215 Рік тому

    The Vapor line at Work froze. The Filter Drier was outside. It was frozen on the Evaporator size of the Filter Drier only. The problem happened because of a Failed Blower Motor Capacitor. Thank you for your videos.

  • @NzelumChukwuebuka
    @NzelumChukwuebuka 2 роки тому +6

    Easy as it should be.
    Craig, do you have an indepth video on liquid line restriction, causes and how to diagnose it. Why will half of the evaporator core freeze for liquid line restrictions instead of entire coil?

    • @NzelumChukwuebuka
      @NzelumChukwuebuka 2 роки тому

      @@electricboogie709 before the refigerant would have reached the exit of the evaporator core it must have frozen completely due to very low pressure resulting in lower temperature below freezing point, thus not enough refigerant to pass completely through the system, this is also dependent on the level of restrictions caused by the orifice. I seem to get it clearer now. Thank you Boogie et Craig

    • @HVACRTECH-83
      @HVACRTECH-83 2 роки тому +3

      @@NzelumChukwuebuka not quite, the refrigerant won't ever freeze, only the moisture in the air will freeze onto the coils surface and the distributor tubing. Only part of the evap freezes because the coil is starved of refrigerant which is what is making the pressure low and in turn the temp below freezing on the coils surface. Assuming proper load on the evap, the refrigerant will still boil off into a superheated vapor as it works its way up the coil which will leave the coils surface at that portion above the freezing point of water. If you had a starved coil as well as improper load,the whole thing would be frozen. But this partial freezing will only take place on this design of coil where the refrigerant feeds into one side and exits the opposite,bottom to top, some other designs the whole coil will freeze in both situations but maybe only on the air inlet side so it's always best to let your SH and SC tell you what the culprit is.

  • @jasonaguilar4929
    @jasonaguilar4929 2 роки тому +1

    Great video

  • @HonchoBobbyD
    @HonchoBobbyD 11 місяців тому

    Hey y'all, I absolutely appreciate your videos very educational and I can actually follow what you're saying! Thank you so much for doing what you do! I had a question, have you had any issues with Nu-calgons product easyseal? By issue's I mean it causing clogs anywhere in the system? It guarantees it won't cause a clog but I think it may have clogged a txv on a system I did a repair on. Thank you again!

  • @holtrussell
    @holtrussell 2 роки тому +6

    Hi Craig, great video, thanks! Would you be willing to take a guess at how many compressors are permanently damaged due to liquid slugging as a result of a failed indoor blower motor / cap. while the system continues to “compress” liquid? I don’t have a clue personally but would be interested in your educated opinion. Thanks!

    • @funkychunky8270
      @funkychunky8270 2 роки тому

      Liquid receiver / suction accumulator brother

  • @David-yy7lb
    @David-yy7lb 2 роки тому

    Excellent explanation Craig question about hi flow filter, wouldn't that cause more dust to pass through and collect on the evaporator over time and cause flow issues vs a filter that traps everything however is a little more restrictive and cause air flow problems....I guess there's pro's and con's to both filters....do you want more air flow or cleaner air🤷🏿‍♂️

  • @honestman276
    @honestman276 9 місяців тому

    Thanks from Bangladesh.

  • @Heribertozagada
    @Heribertozagada 8 місяців тому +1

    Hi sir I'm bert in Philippines 🇵🇭 I'm learned to much in Refrigeration I'm very interested

  • @ilovenythismuchilovenewyor5801
    @ilovenythismuchilovenewyor5801 2 роки тому

    surprised you didn't mention the orifice on some systems .. like some come w txv some come w the fixed orifice and both can get jammed up and cause a restriction... came across a r22 low side line set was frozen all way up to the evap coil. gauges read 25 psig on low side 15p on high and this was w the evap coil frozen... had to let it all defrost so can get a better 3 min reading for low side evap coil temp then another 7 mins to check the rest. but once I disconnected hoses the low side was defrosted and I heard a hissing so the core valve possibly could of been leaking even tho it had a cap on it before and was frozen before I had a actually put hose on low side ... so was suspicious of leak w possibility of low refrigerant but once again needed thr whole unit to defrost to take the pressures while running and also replace core valves w new ones and continue to test for leaks and rule out if it is low refrigerant, check evap coil for dirt build up because did notice the return and supply grills had alot of black dirt on them which indicates the return didn't have filters in it for long time so they ran the unit w out that filter and it could possibly have lead to the evap coil getting caked up w dirt causing bad air flow and last the fixed orifice could be clogged up some how. ... will find out

  • @noellwilson1273
    @noellwilson1273 9 місяців тому

    Bravo! I kept hearing “air restriction = freezing” but this is the first time someone has said “air restriction = less phase change to vapor in the evaporator = low evaporator pressure = freezing”. I couldn’t understand why I got 62 psi readings (R-22) when I checked the low side and the chart said that was above freezing (36F from memory).
    A question: Is there a valid argument that the new HEPA filters restrict the air flow and that a cheaper “horsehair” filter might work better on an old system?

  • @sissonsk
    @sissonsk 9 місяців тому

    I bought a $20 Honeywell digital and programmable thermostat about 9 years ago. Apparently, it stopped turning the A/C blower on and the evaporator froze up. I couldn't get the fan to turn on at all. I just happened to have an exact replacement and, after I de-iced the evaporator, I got the blower to work with the newer thermostat.
    At least this is what I hope solved the icing problem.

  • @indiantraveller194
    @indiantraveller194 Рік тому

    Good

  • @ozziewelcome5612
    @ozziewelcome5612 2 роки тому +1

    Good 👍

  • @cck1496
    @cck1496 2 роки тому

    Good video. What is A and M on control card?
    Thanks.

  • @anujprakash5136
    @anujprakash5136 3 місяці тому

    Wow 💯

  • @richardhaen
    @richardhaen 9 днів тому

    Good video, got a question for u, My ac has two capacitor one for fan one for compressor can I put in one
    capacitor Com/Fan/H? Same value.
    Thank u
    Richard

  • @bigstepper2235
    @bigstepper2235 2 роки тому

    can you do a video on furnace control board dip switches

  • @btarb242
    @btarb242 2 роки тому +1

    Curious, is it feasible to omit the 2nd stage cooling wire on a 2 stage heat pump to get more heat capacity? example.. manJ heat=53k and cool is 29k. Using a two stage 4 ton unit would get me most of the heat and be only a about 15% oversized for cooling that's limited to the 70% stage 1.

  • @TheWilferch
    @TheWilferch Рік тому

    Any hints on why the outdoor condenser coil ( and also looks like the compressor and tubing inside the condenser housing)....freezes in winter-mode operation "on heat" ???? Bad defrost control?....bad thermostat somewhere?.... faulty reversing valve?.....

  • @mark.r8900
    @mark.r8900 Місяць тому

    Great video. My suction line is frosting up. Indoor temperature is 75F and outdoor ambient is 70F. It's r410a with low suction pressure. The low side saturation temp is 28F. I am getting low superheat but normal subcooling with fixed orifice. Filter is clean and air flow is good. The coil has no frost but frosting just before service valve at outdoor condenser. All amp draws are good. I tried adding some refrigerant but the low side pressure would not rise. I just can't figure this one out. Any help would be greatly appreciated. Thank you.

  • @danh9846
    @danh9846 2 роки тому

    Was wanting to know where to test temp on a vehicle like a bus where to compressor and condenser 20 feet or more apart for proper subcool

  • @nickcurry8515
    @nickcurry8515 2 роки тому +1

    7:10 "I found another guy to do it cheaper" hahahahaha

  • @manitchongtv9090
    @manitchongtv9090 2 роки тому

    Hi sir,it is possible to make AHU that using brine chilled water?

  • @johnleblanc1902
    @johnleblanc1902 3 місяці тому

    cool

  • @javierguadarrama9405
    @javierguadarrama9405 2 роки тому

    I need to replace a system on a condo, so i can't replace the line set. Can you plese show how to flush the lines from R22 to 410A. Thanks

  • @nickthegriffin
    @nickthegriffin Рік тому

    If you had a r22 system 😆 we got rid of that in the UK years ago

  • @LMike2004
    @LMike2004 2 роки тому

    Dehumidifier starting to ice. Are they worth repairing?

  • @douglasnorman8748
    @douglasnorman8748 11 місяців тому

    I have an interesting problem where my AC doesn't cool enough to drop the temp to say 75. It runs too long and the outside unit shuts down I assume it gets too hot. There is no freezing anywhere. The inside heat exchanger gets cold but I don't think it's getting cold enough. The filter is clean and the indoor fan is good and there seems to be plenty of air moving. The outdoor heat exchanger is not dirty. Tech is coming tomorrow

  • @202upt1
    @202upt1 2 роки тому

    Question if one rm is not getting as much air as other rooms what is the problem ??

  • @yasserd86
    @yasserd86 Рік тому

    Dryer does it matter if it’s outside or inside installed ????

  • @FlockofSmeagles
    @FlockofSmeagles 11 днів тому

    I'm having an issue where the coil is freezing from the line that that's leaving the furnace. It looks like there's a leak coming from the silicone seal. Can a leak like that cause freezing?

  • @farrellnuszjr9216
    @farrellnuszjr9216 Рік тому

    I have a question should a closed ac Freon unit every need recharged if it never leaks. Or do all units have to be recharged every year or seasons

    • @danielcovarrubias2331
      @danielcovarrubias2331 9 місяців тому

      It’s a closed system, should never leak. No need for recharge unless there is a leak.

  • @alifn9530
    @alifn9530 Рік тому

    Hight pressure : 103 f°
    Low pressure : 40f°
    Sobcooling : 10 f°
    Superheate : 10f°
    Return air temp : 71f°
    Supply air temp : 50f°
    The évaporateur is always freezing

  • @JP-hj7fc
    @JP-hj7fc 2 роки тому

    How can you test the liquid line restriction or the metering device to determine the problem? And what is the procedure to replace them? De-solder or replace the entire A coil then recharge the system?

    • @justingibson8788
      @justingibson8788 2 роки тому +1

      Take bulb off and warm it with your hand or in a cup of warm water. If super heat doesn't adjust then txv is bad.

    • @justingibson8788
      @justingibson8788 2 роки тому +1

      And for filter dryers test temp on each side. Should be the same.

  • @renteria4540
    @renteria4540 2 роки тому +1

    If you were a teacher. You would be the best

  • @trinisfunhousewithcheyanne3552
    @trinisfunhousewithcheyanne3552 8 місяців тому

    I need help my suction line is freezing.my ac has gas
    I also checked for leaks there is none.my readings are good and i cleaned my ac but still ice only on the suction line.also my blower wheel is making a noise whenever my ac blade is raised up.whenever i lower it the noises stop.anyone has a sollution

  • @fillmorehillmore8239
    @fillmorehillmore8239 Рік тому

    Problem: Indoor blower turns on/new filter.
    Turn on A/C and runs, once the A/C runs for about 20 min the indoor blower turns off for a few min (AC still running) and starts up for 30 seconds or so. The cycle continues and the AC starts to freeze.

  • @viob1359
    @viob1359 Рік тому

    I got a new furnace, and now my 16 year old A frame AC unit is freezing. The Cool fan speed is at High. I have switched my filter to the thinnest possible to increase the airflow but it's still freezing over. The furnace guy blames it on the AC A frame unit siting on the furnace and impeding the air flow. He was no help. He installed a temperature gage on the refrigerant line to stop my thermostat but forgot to connect it to a timer, so his solution is to stop my AC from working.
    I had an AC technician measure the Static air pressure which came out to be 1.07, way outside the manufacturing parameters, it's not even on the chart. The AC technician also said the refrigerant levels are good and we have no leeks. He said there is not enough air intake coming in. The fan sounds too loud when the AC kicks in. Could lowering the fan speed to medium help with the freezing? Do I need to add an intake vent? HELP! 🙂

  • @yannkitson116
    @yannkitson116 2 роки тому +1

    Is the book in metric units?

  • @chriskopec1858
    @chriskopec1858 Рік тому +1

    ❤👍

  • @Elisummit845
    @Elisummit845 2 роки тому +1

    I always tell people there is only 1 reason why an ac freezes. If the temperature of the coil drops below freezing. Why it would drop, there could be a few reasons.

  • @alirezaajamzlbad
    @alirezaajamzlbad 2 роки тому

    پشماممم

  • @janielramirez9842
    @janielramirez9842 Рік тому

    Thars not enough information. U left other details out

  • @eclipse369.
    @eclipse369. 2 роки тому

    How come you don't do commercial refrigeration as well?
    You only residential hvac?

  • @eclipse369.
    @eclipse369. 2 роки тому +1

    Too many electronics nowadays like ecm junk.

    • @MaMa-qh4dy
      @MaMa-qh4dy 2 роки тому

      The cost to replace an ECM module far outweighs the cost/benefit of having ECM motor vs PSC motor.