How to Conduct a Hydrostatic Test on Ductile Iron Pipe

Поділитися
Вставка
  • Опубліковано 11 кві 2019
  • After a pipeline is installed it will need to be tested for proper assembly. In this episode of Iron Strong Jerry Regula explains how to conduct a successful hydrostatic test of ductile iron pipe, and gives some tips on common problems during the test.
    As pipe joints expand under pressure people often think they have a leak. JR teaches us how to overcome this issue.
    DOWNLOAD THE CHECKLIST:
    →resources.mcwaneductile.com/m...
    READ AN ARTICLE ON HYDROSTATIC TESTING:
    →www.mcwaneductile.com/blog/ho...
    *************************************
    Watch more episodes of IronStrong:
    • Playlist
    Learn more about how Ductile Iron Pipe is made:
    ua-cam.com/users/playlist?list...
    → Website: www.mcwaneductile.com
    → Facebook: / mcwaneductile
    → LinkedIn: / mcwaneductile
    → Twitter: / mcwaneductile
    → Contact us: www.mcwaneductile.com/about-u...
    MDV000040
  • Наука та технологія

КОМЕНТАРІ • 87

  • @farmanalikhan4963
    @farmanalikhan4963 Рік тому +2

    Thanks, Mr. J. Regula very useful information you provided I was searching for hydrostatic testing video. Your video was most useful for me. I am a mechanical Technician in Pump sections in Saudi Arabia. I expect more useful videos from you.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому +1

      You are very welcome. Thank you for the compliment. We have a lot of new videos planned for this year. Please keep watching.

  • @sajithandiakkaljoseph5
    @sajithandiakkaljoseph5 3 роки тому +1

    Very informative; thank you Soooo much

  • @Birudev-cl5rp
    @Birudev-cl5rp 3 роки тому +1

    thank you for guidance.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Happy it was useful. Are there other topics you are interested in learning more about? Thanks.

  • @syednadal9142
    @syednadal9142 4 роки тому +2

    Thanks for this vedio keep it up dude

  • @Sajidabbasi786
    @Sajidabbasi786 4 роки тому +2

    Very helpful thank u boss I like u .....god bless u boss......thanks

  • @eyassror4840
    @eyassror4840 7 місяців тому +1

    Thanks

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  7 місяців тому

      You're welcome. Thanks for watching. Spread the word.

  • @cck1496
    @cck1496 2 роки тому +1

    Good video. This drop in pressure (while hydrotesting) due to joint movement is only in DI pipes but not in CS pipes.
    Thanks.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Thanks for the compliment. Please keep watching our videos.

  • @yahyakhan6076
    @yahyakhan6076 11 місяців тому +1

    Very good Job sir love you from Pakistan

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  11 місяців тому

      Thank you for watching, and may all your hydrostatic tests be leak free.

  • @1436am
    @1436am 4 роки тому +4

    Explain more about how trapped air acts in a pressurized line

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Here is a great blog about just that by one of our product engineers, Ken Rickvalsky.
      www.mcwaneductile.com/blog/hydrostatic-testing-of-ductile-iron-pipe-the-diagnostic-version/
      Thanks for watching and thanks for your question.

  • @manjul2015
    @manjul2015 Рік тому +1

    Very nice sir

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому +1

      Happy you enjoyed it. Please look at our other videos.

    • @manjul2015
      @manjul2015 Рік тому

      From where are you

    • @manjul2015
      @manjul2015 Рік тому

      I work in same field

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      We make our pipe in three foundries, Coshocton OH, Phillipsburg NJ and Provo UT. Jerry is one of our talented product engineers. He travels all over America and Canada, and sometimes further, to provide training to our customers and help them successfully complete their projects.

  • @PadraigSmyth0001
    @PadraigSmyth0001 6 місяців тому +2

    Is the makeup water being added to the line during the test to maintain test pressure over the two hours?

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  6 місяців тому

      Thanks for your question. The answer is no. Makeup water is only added & evaluated AFTER the completion of the specified testing time frame. Makeup water is generally how you gauge if there is an active leak or not. There should be nothing added and no pump action occurring during the test period itself.

  • @riddhi2011
    @riddhi2011 4 роки тому +6

    Hello, I really liked your video and setup for the hydro test. Do you have a checklist or BOM for the procurement of setup? I have a small scale testing where my prove test pressure is 30,000 psi. It will be a great help if you can guide me in procuring the apparatus. Thank you!

  • @godfreypoon5148
    @godfreypoon5148 3 роки тому +7

    My wife is angry because I used all the makeup water.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Thank goodness it's almost Christmas and you can get her some more.

  • @pratapreddy8027
    @pratapreddy8027 4 роки тому +1

    How to calculate based on pipe size and what to consider?

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  4 роки тому

      Be sure to subscribe to our channel as we will be covering this subject in a future video.

  • @engineersoutlook7
    @engineersoutlook7 4 роки тому

    I would like to share our experience to your team.
    Thanks

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Thanks for watching. You can contact us at our website McWaneDuctile.com
      I hope your experience was positive.

  • @mrfarabi8502
    @mrfarabi8502 4 роки тому +1

    Thank for sharing your experience, but i am also can all hydrotest process,low medium and high pressurable line,like as 15 to 400 bar(psi) i did complete,
    From Bangladesh

    • @soenaung7249
      @soenaung7249 4 роки тому

      Please suggest me how to test hydrostatic tube for PSI 2,200!

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      We follow testing procedures outlined by the AWWA. Testing to 2200 PSI is not part of that process. Thanks

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Cool thanks. Good luck with your work in Bangladesh.

  • @soenaung7249
    @soenaung7249 4 роки тому

    Firstly thanks for ur video! I have to test PSI 2,200 for 16 cylinders racking tubes line. I m looking for the jet pumb in Myanmar. But it is rare to find here. Please, suggest me for our problem! thanks.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Sorry, I don't understand your question. Feel free to try again. Thanks for watching.

  • @piping2024
    @piping2024 2 місяці тому +1

    🙏🙏

  • @palashsdeliciousfood
    @palashsdeliciousfood 3 роки тому +2

    big 👍694lk nice sharing dear 😍💞

  • @ajeyshetty9765
    @ajeyshetty9765 3 роки тому +2

    Explain about the test set up in detail.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому +1

      Below you will find a link to our tip sheet on the Hydrostatic testing process. I hope this helps. Thanks for watching.
      www.mcwaneductile.com/upl/downloads/tip-sheets/preparing-for-a-hydrostatic-pressure-test-tip-sheet.pdf

  • @PranaPramudita
    @PranaPramudita Рік тому

    bagus

  • @tylerchapman8856
    @tylerchapman8856 Рік тому

    How about testing tr extreme.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Thanks for watching. The TR Extreme is not our product. You'll have to reach out to the manufacturer for the specific requirements of that joint.

  • @kimwee1489
    @kimwee1489 4 роки тому +1

    hi, currently i have this situation, i only have about 4m length of straight pipe, and am required to do pressure test of 150psi for 24 hours by the client, the pressure always drop after 1-2 hours but i cannot find any leak. i am told by my supplier for static pressure test the pressure cannot hold for 24 hours. is there any method to solve this issue? please advise thx

    • @shubhhumanoid
      @shubhhumanoid 3 роки тому

      I am facing the same issue. Have you resolved it ?? Please guide how ?

    • @KuyaZanforextrader
      @KuyaZanforextrader 3 роки тому

      used flange with lowest and highest point connection and always consider the temperature during hydrotesting,stainless are more affected due to temperature condition,if you are using Hydrotesting Chart you will see like a heart beat up and down and that is normal.

    • @PrMnT562
      @PrMnT562 3 роки тому +2

      I know this is old but always fill from the lowest point and always vent from the highest point and like the guy in the bottom said depending on the material that the equipment will be tested temperature has to do a lot .. the colder it is it will drop on the gauge the hotter it is the gauge pressure will go up. Double check all bolted valves flanges and other components that where touched and not touched and always wear a faceshield when hydrotesting equipment.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Thanks to j m for their good advice in the comments.

    • @lesterduncan8778
      @lesterduncan8778 24 дні тому

      You probably have trapped air; try flushing the line with very rapidly flowing water. Let the water set for a few hours to let the air bubbles to settle. Always put a blow off on your gauge assembly and put it on the top or highest point of the pipe. Might help if you put a 90 degree bend fitting on the test end as well.

  • @alexmaccity
    @alexmaccity Місяць тому

    Airs volume becomes half as its pressure goes up. Waters volume stays the same.

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Місяць тому +1

      There is an inverse relationship between gas pressure and volume known as Boyle's Law. That's why it's so important to remove air from your line. It will effect results and can be dangerous.

    • @alexmaccity
      @alexmaccity Місяць тому

      @@McWaneDuctilePipe agreed. It can also affect flow, and cause damage.

  • @hardikpatel-ne7jj
    @hardikpatel-ne7jj Рік тому

    How can I finh H in equation Q

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Sorry, I do not understand your question. Could you provide some more information please?

    • @hardikpatel-ne7jj
      @hardikpatel-ne7jj Рік тому

      That's an equation to find the allowable waterloss per hour.
      L=pipe length in Km.
      D=pipe diameter
      H=average test head over length of pipeline
      under test, in metres
      I don't know how to find H.
      Thanks

  • @eujiahealthywealthylongevi4786
    @eujiahealthywealthylongevi4786 2 роки тому

    what is make up water ?

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      When hydrostatic testing a pipeline, it is the amount of water it takes to regain initial test pressure (assuming it has dropped) after specific amount of time. If you require more make up water to regain the pressure level than you would expect for your test setup, this can be an indication of a leak in your pipeline. Thanks for watching.

  • @balrajchouhan6445
    @balrajchouhan6445 4 роки тому +1

    Yah line isliye

  • @yrun989
    @yrun989 3 роки тому

    2 in 1
    Air test + water presure test
    =Comosiouning test √
    Check√

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Sorry, I don't understand your post. But thanks for watching.

  • @justinsampler5506
    @justinsampler5506 6 місяців тому +1

    Damn you guys test each stick before you put em in?

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  6 місяців тому +1

      Yes indeed. Per AWWA C151 (Ductile Iron Pipe, Centrifugally Cast) each pipe receives its own hydrostatic test during the production process of at least 500-psi.

  • @samirkhan-pj6hx
    @samirkhan-pj6hx 4 роки тому +1

    Mc wane ductile...why Don't you guys work in Bangladesh,we have many pipeline projects going on...can i have your contact e-mail id?

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      You can find contact information on our web page McWaneDuctile.com
      Glad to hear that Bangladesh is continuing to grow stronger.

  • @jamilahmad7802
    @jamilahmad7802 4 роки тому

    Sir I am mechanical engineer ,,and also have a job in gas pipe line of 12 inches , having a experience of 1 year ...if u have a vacancy ,,,so plzz reply me ...bcz I need more money to feed my family ...help me if u can

  • @kefa_mechanophilic4293
    @kefa_mechanophilic4293 5 років тому +1

    Sir give me a job

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  5 років тому +1

      We would love to have you as a team member. Please visit www.mcwane.com/careers/ to apply.

  • @azmuddinansari4989
    @azmuddinansari4989 4 роки тому +1

    Your video is not clear
    Something wrong

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      Sorry you had a problem with the video. Is there a question we can answer for you? Thanks for watching.

  • @afzalkhan-nu7xd
    @afzalkhan-nu7xd Рік тому

    please explain in in hindi

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  Рік тому

      आपकी रूचि के लिए धन्यवाद। हम अपने अंग्रेजी उपशीर्षक में सुधार कर रहे हैं, जिससे उम्मीद है कि वीडियो का अनुवाद बेहतर होगा। हम अपने कई हिंदी भाषी दर्शकों के लिए आभारी हैं, लेकिन दुख की बात है कि फिलहाल हम केवल ऑटो-अनुवादित उपशीर्षक प्रदान कर सकते हैं। आपका दिन अच्छा रहे।

  • @connoro147
    @connoro147 5 років тому

    lololol This guy still uses Ashcroft gauges. If it's not a Crystal I don't even want your numbers gtfo

    • @McWaneDuctilePipe
      @McWaneDuctilePipe  5 років тому

      Thanks for the tip. We will look into using Crystal gauges in future videos.

    • @Elkmonger
      @Elkmonger 3 роки тому

      I test a lot in the North East US and very few liquid mainline pipeline operators I work for will accept the Crystal gauges. I have no idea why. I just outfitted a new test trailer. There's about $8k in dead weights, chart recorder and all the damn Swagelok crap to hook it all together. OR one Crystal gauge will do the same for about $2k and basically no swagelok stuff. Not to mention pulling everything out of the trailer to get certified every 6 months. Crystal set-up is nice.

    • @summitxcontractors6373
      @summitxcontractors6373 2 роки тому +1

      Why on God's green earth would you need a $1,000+ gauge for a relatively low pressure water line test? This is an instructional video for hydrotesting ductile iron water mains, a typical test is 225psi for 2 hours. It's not rocket science and guys have been doing it with success forever.