Determining Primary Connections
Вставка
- Опубліковано 1 січ 2025
- Learn about the primary connection rules for Wye (phase-to-ground) and Delta (phase-to-phase) transformer connections.
Check out our Transformer Connection Series! • Transformer Connection...
Don't forget to subscribe to our UA-cam channel for the best power delivery training and educational videos. @NorthwestLinemanCollege
NEED CAREER TRAINING?
Through training and education, we help thousands have safe and rewarding careers in power delivery. lineman.edu/
CHAPTERS
0:45 - How to determine Wye primary connections
1:21 - How to determine Delta primary connections
2:19 - Example 1: The primary voltage on the nameplate is 19900/34500 Y, with a Phase-to-Neutral voltage of 19900 is a WYE connection
2:34 - Example 2: The primary voltage on the nameplate is 4160/7200 Y, with a Phase-to-phase voltage of 7200 is a DELTA connection
2:50 - Example 3: The primary voltage on the nameplate is 12000, with a Phase-to-phase voltage of 12000 is a DELTA connection
3:05 - Example 4: The primary voltage on the nameplate is 12000/20800 GrdY, with a Phase-to-Neutral voltage of 12000 is a WYE connection