Sensitive Earth Fault (SEF) Protection of Transformer || Standby Earth Fault (SEF) Protection

Поділитися
Вставка
  • Опубліковано 21 жов 2024

КОМЕНТАРІ • 8

  • @ramanjain1313
    @ramanjain1313 Місяць тому

    This is the circuit is for REF ? Why calling it by SEF?

  • @Technicalguy_123
    @Technicalguy_123 4 місяці тому +1

    Ref is operating for external fault even though stability test is correct what could be the issue

    • @360Engineer01
      @360Engineer01  3 місяці тому

      Are you using 4 CT or 5 CT ?
      If 4 CT, check for Neutral CT Location

    • @sanjaykashikar940
      @sanjaykashikar940 Місяць тому +1

      In this video the neutral polarity is wrong, it should be reverse. In healthy condition no issue but it will operate for external earth fault and will not operate on internal fault.

    • @360Engineer01
      @360Engineer01  Місяць тому

      In this video only SEF protection explained and overlooked the polarity of REF

    • @360Engineer01
      @360Engineer01  Місяць тому

      4CT or 5CT configuration?

    • @Technicalguy_123
      @Technicalguy_123 Місяць тому

      @@360Engineer01 4CT