Solar Photovoltaic (PV) Systems, Grounding Electrode System, NEC 2020 - [690.47], (9min:30sec)

Поділитися
Вставка
  • Опубліковано 26 гру 2024

КОМЕНТАРІ • 17

  • @FrancisKoczur
    @FrancisKoczur Рік тому +2

    Residential transformerless inverters that aren't grounded to neutral have been the standard for a decade. No need for confusing language in the code. Grounded and ungrounded transformer inverters still have their place, but referencing to them isn't necessary.
    Keep up the good work.

  • @vassilnikov6814
    @vassilnikov6814 Рік тому +1

    What about when the array is on a the roof of a separate building more than 20 meters away from the main building? How do we install SPD devices in such configuration? If the cable trace is that long wouldn't it be inefficient to install the SPD at the box in the main building only? Wouldn't in such case a separate grounding rod and SPD at the separate building with the array be a preferred option?

    • @gfjardim1983
      @gfjardim1983 9 місяців тому

      You can put an auxiliary grounding electrode on the PV array, but the SPD devices should be in your PV combiner box inside your main building, and its grounding wire have to be bounded at the main panel grounding bar.

  • @captainjohnmccalpin5161
    @captainjohnmccalpin5161 11 місяців тому

    What about grounding requirements for a stand-alone (off-grid) PV system installed in a floating boathouse (covered metal dock on plastic floats, not a houseboat)? There is no utility connection with a grounded service disconnect. What do I need to do to provide a compliant ground for panels, inverter, stand-alone load center, etc.?

    • @MikeHoltNEC
      @MikeHoltNEC  11 місяців тому +1

      Please send me an email, Mike@MikeHolt.com, with this question so I can work this out.

    • @captainjohnmccalpin5161
      @captainjohnmccalpin5161 11 місяців тому

      Will do!

  • @christopherworks400
    @christopherworks400 Рік тому +1

    I work in solar and I got in an argument with the "electrician" that ground rods are Required by code for ground mount array, even though the metal support was driven in the ground 8 feet. And on top of that he said we need 2.
    So am I right that they ARE NOT required?

    • @christopherworks400
      @christopherworks400 Рік тому

      @@TheTubejunky well there was 2 rods for the house, but they wanted 2 more for the array. so there would be 4 total.

    • @kimandylawrence4199
      @kimandylawrence4199 Рік тому

      Yes, you are right. They are not required.

  • @georgevan3102
    @georgevan3102 Рік тому

    What about a line tap pv system. It does not have a ground conductor. Where do you pick up the grounding?

    • @christopherworks400
      @christopherworks400 Рік тому

      we crimp on the the ground coming out of the house and add a second rod.

    • @georgevan3102
      @georgevan3102 Рік тому +1

      @@christopherworks400 250.142 have you ever taken this in to consideration?

  • @kevinthompson4690
    @kevinthompson4690 Рік тому +2

    Same here. We were doing small cell 5G sites with 8x8x 12 foot deep concrete encased steel reinforced pole bases with a #2 tinned copper wire attached to the rebar out of the concrete. Ole inspector walks up and says "Wheres your ground rod? gotta have a ground rod". I said really? You think that a 5/8x 8 foot ground rod is required and is gonna do anything? Non educated is what they are.

  • @WiSeNhEiMeR-1369
    @WiSeNhEiMeR-1369 7 місяців тому

    now explain how to adapt this too a GROUND-MOUNT Arrays 300' from the House Wiring SYSTEM ...
    ...

    • @MikeHoltNEC
      @MikeHoltNEC  7 місяців тому +1

      Nothing (grounding) is required at all, so you are good.

  • @keything8487
    @keything8487 5 місяців тому

    now, get the ahj to agree with this

    • @MikeHoltNEC
      @MikeHoltNEC  5 місяців тому +3

      The 2026 NEC is removing all of this crap, so it won't be a question in the future.