КОМЕНТАРІ •

  • @MysticShiv3r
    @MysticShiv3r 5 років тому +33

    Never have I watched a video of a spark whom is so well spoken and informative. This is a cracking vid mate. You've earned yourself a subscriber. This comes from a fellow spark :)

    • @dsesuk
      @dsesuk 5 років тому +3

      Very kind of you to say so sir.

    • @kangtheconqueror
      @kangtheconqueror 2 роки тому

      Ha, ha, ha... watch a few more videos from DS and you may have to edit the bit about being 'well spoken'!! Isn't that right, Dave?
      All joking aside though, I watch a lot of your vids David and consider your opinion to hold a great deal of sway.
      Your knowledge, together with your industry ethics, is essential viewing in my opinion. Plus, your banter makes for great viewing entertainment!!

  • @rogerlawson6031
    @rogerlawson6031 5 років тому +24

    As an ex emeb / cn / wpd mains engineer I'd be very surprised indeed if the one amp is actually leakage current from a phase conductor unless there's a solid fault to unbonded metalwork that has an impedance of circa 240 ohms 'within the ground' and the nigh on 0.25kW of heat energy is dissipated into mother earth, or a phase conductor is touching damp brickwork etc. (possibly via unnbonded metalwork) and the heat is being absorbed by the building structure. I've had both of these situations to sort out when customers were getting shocks when outside their property because of the potential gradient across sections of brickwork and across the surface of the ground. I mention heat absorption because circa 240W of power loss at one 'point' location would be most likely to quickly raise the temperature to a level where a fire would result. It's perhaps more likely that the problem is a neutral to earth fault within the property, the 1A of current in the main earth connection to the lead sheath of the service cable being some proportion of the neutral current of the whole installation because there wil be a tendency for the neutral bar to be at a slightly higher potential than the earth connection of the 'tns' type supply at this property - hence all of the instalation neutral current will be 'attracted' to some degree to flow from the neutral bar, along the neutral of the faulty circuit and via the fault into the cpc or bonded metalwork etc, back to the main earth bar in the consumer unit and then via the main earth lead to the lead sheath of the service cable....which will (should!) have an almost zero impedance link back to the supply transformer neutral point. The crossed colours on the armoured cable also has me wondering - is the neutral of that circuit actually connected to the earth bar of the consumer unit and the cpc conected to the neutral bar? - that would also explain what's happening - the 1A would be the neutral current from the load of that circuit!

    • @tasmedic
      @tasmedic 5 років тому +3

      That, everyone, is the voice of experience and wisdom. I hope this person teaches sparkys how to wire things up. There are a lot of crap ideas in the regulations, and a lot of good ways of doing things which aren't in the regulations, too. I get the impression this engineer knows the ins and outs of both these situations.

    • @jackflavell3908
      @jackflavell3908 5 років тому +2

      This is also needs to be taught to all jointers/linesman who havent got a clue what ohms law is

  • @rusrus29
    @rusrus29 5 років тому +3

    I blimin love your videos!! you have a unique and addictive channel." I love how you go through the fault testing side in such detail" ! it's a channel that stands out from the rest on here....Thank you..

    • @dsesuk
      @dsesuk 5 років тому

      Thanks Russel, very kid of you to say so.

    • @coralbay00
      @coralbay00 4 роки тому

      What do you charge per circuit if you don't mind me asking. I've been caught out a few times with a small dwelling that has several circuits. 👍

  • @christastic100
    @christastic100 5 років тому +9

    From my experience that cut out is a 60 amp version. Even then it takes a long period of time to blow on overloads such as it is . As for the split ring main I use a signal generator to trace the runs . Can be very good for finding cpc and other breaks too . Great to watch

  • @richardwallace3477
    @richardwallace3477 5 років тому +7

    Tip: Instead of taking your earth leakage from the earth cable (which could potentially include currents from other properties) put your clamp meter around the two tails and you will get a true reading of the leakage from the installation - ie the difference between the current in and the current out.

  • @davidclark3603
    @davidclark3603 5 років тому +5

    That was a very interesting video David. I did years of testing many moons ago and it can be very taxing and tricky. Well done on spotting all the faults. It’s not easy, especially when you’ve got heaps of extensions, additions and alterations galore. I agree, R.C.B.O.s throughout. That’s my basic choice these days. It would be good to see a metal clad fire proof board in there. I hope you get the work, I think you’ll do a nice neat and tidy job of it. I hope you do a video of the shower switch you mentioned. That sounds very interesting. I don’t know about them? Thanks again for the video David. Have a good weekend!

    • @dsesuk
      @dsesuk 5 років тому +2

      Thanks David, I might see if I can push out that shower priority board video tomorrow (hangover pending).

  • @alantorrance6153
    @alantorrance6153 4 роки тому +1

    Very interesting, especially the ramifications as to potential disastrous failures and the widespread remedial work needed. Headaches - big ones for the new owner.

  • @albertkleyn111
    @albertkleyn111 4 роки тому +1

    Excellent, as always. If I did not live in the boondocks in Ireland, every job would go to you and Nigel.
    Albert.

    • @dsesuk
      @dsesuk 4 роки тому

      Thanks Albert!

  • @pauldavies9709
    @pauldavies9709 5 років тому +35

    Good video mate. Would be good to do a follow up to this video with the new DB and investigate the earth leakage source.

    • @dsesuk
      @dsesuk 5 років тому +13

      Was thinking the same. Might be a while before it's all done and dusted at that site, although I think we'll get the work.

    • @jgoddard0757
      @jgoddard0757 5 років тому +6

      I agree, the final outcome would be interesting!

    • @floorpizza8074
      @floorpizza8074 5 років тому

      @@dsesuk I hope you do. Would be nice to see them get a proper installation instead of the mess they currently have. Edit: Actually, I see this is an older video. Did you get the job?

    • @dsesuk
      @dsesuk 5 років тому +5

      @@floorpizza8074 Yes, we've been appointed for the work, but the new board still hasn't gone in. We've since been back for some remedial work to allow the upgrade to go ahead, but the delay is down to scheduling and to our waiting for some new consumer unit models to come out as manufacturers switch from type AC to type A RCBO's. We should hopefully be doing the board change in the next couple of weeks.

    • @floorpizza8074
      @floorpizza8074 5 років тому +2

      @@dsesuk Good to hear! Love it when guys that do high quality work (and take great pride in it) get the job. I know you're really busy, but would love to see a bit of video from that job. :)

  • @DaC-lt5mk
    @DaC-lt5mk 5 років тому +2

    Nice to see someone working properly

  • @stephenpower9572
    @stephenpower9572 5 років тому +2

    Another great video. Nice to see a video of you out on site. Look forward to seeing the device for shower load. Thanks for sharing.

  • @simonbmr
    @simonbmr 4 роки тому +1

    And this is the best reason I have ever seen for EICRs. It often seems like a pointless paperwork exercise, but then you find this mess.

  • @chrisjinks5197
    @chrisjinks5197 5 років тому +1

    I do EICRs most days good to see someone posting videos about the daily rubbish we see. Keep up the good work!

    • @dsesuk
      @dsesuk 5 років тому

      Thank you for that compliment

  • @matthaddock6490
    @matthaddock6490 5 років тому +3

    David great video, as a learner this give me a good inside what you come across these discrepancies when doing a test 👍

  • @paulteasdale7112
    @paulteasdale7112 5 років тому +3

    Excellent video David, amazing what you find! Thanks for sharing.

    • @dsesuk
      @dsesuk 5 років тому +1

      I found a can of Guinness in this case!

  • @laernulienlaernulienlaernu8953
    @laernulienlaernulienlaernu8953 5 років тому +1

    I’m not surprised that the incoming cable has overheated! It was probably originally serving a 3 bed house with maybe an electric cooker and an immersion heater plus a few sockets and lights

  • @adriantyler1820
    @adriantyler1820 5 років тому +2

    I purchased a 5 bedroom villa with pool in Thailand.
    When any of the 3 instantaneous water heaters are used, the lights go dim.
    The voltage at KWH falls from 220V to 200V.
    Luckily KWH is in the garden in a box with my neighbor"s and get to make an actual ring main when I do repair.
    They have same size cables and under voltage problem on our private estate.
    KWH are for from private distribution board.

  • @kangtheconqueror
    @kangtheconqueror 5 років тому +1

    'Exciting' be blowed! This video is fascinating. Cheers David.

    • @dsesuk
      @dsesuk 5 років тому

      The ones I think are really boring and waffle-filled always seem to do better than those I've spent a wodge of time and effort on!

  • @rossmurdoch7870
    @rossmurdoch7870 3 роки тому +1

    Hi David, Second time watching this one. Really good advice.
    One observation, I think you should not be confident applying the correct cost for the jobs you offer to do.
    Professional advice and honest evaluation is a commodity which must have a higher value than a rushed cheap fix which will not stand the test of time.
    The people buying this place will have a couple of grand to protect their investment, I would assume.
    Get your bill in, and don't miss them for time spent saving their new home from burning to the ground.

  • @sdgelectronics
    @sdgelectronics 5 років тому +3

    Earth current is probably from another property with a failed CNE. You should clamp the two live conductors at the same time to determine the origin of the fault

  • @horatiofluffytop
    @horatiofluffytop 5 років тому +3

    Really interesting and informative video, thanks for a great Chanel David.

  • @LAsparkTVWireTestLimited
    @LAsparkTVWireTestLimited 7 місяців тому

    Just watched this again 4 years since I first watched it. I will never tire of listening to your geriatric mumblings.

  • @matthewcollis-long5233
    @matthewcollis-long5233 5 років тому +1

    Excellent and informative stuff DSES!! Keep it coming please.

  • @olafdossier7897
    @olafdossier7897 5 років тому

    Your videos are scarey A F. I don't want to touch any electrical switch or socket in my house anymore - fantastic content, how can you only have 6.3K subs?

    • @dsesuk
      @dsesuk 5 років тому +1

      It's a combination of bad language and uncontrollable nasal hair that keeps the subscribers away!

  • @benjackson1498
    @benjackson1498 5 років тому +2

    Really interesting mate 👌great content as always, really enjoy your chanel keep up the good work

  • @ashmanelectricalservices4318
    @ashmanelectricalservices4318 5 років тому +2

    I can remember about 10 years back when staying at a Park Resort chalet, the electric shower and cooker having some kind of 2 way control switch, meaning when one was being used, the other couldn't. I guess it was their way of preventing potential overload.

  • @CrazySparkie63
    @CrazySparkie63 5 років тому +2

    Around 4.8 KWh a day leaking to Earth. I worst I found was over 32A leaking to Earth in old stables at a riding school in Kent (100mA RCD fried)!

    • @Christian-dc1sb
      @Christian-dc1sb 5 років тому +1

      on alot of livery yards and riding schools as well the electrics are awful so that doesn't surprise me at all

  • @LAsparkTVWireTestLimited
    @LAsparkTVWireTestLimited 5 років тому +1

    Really interesting. Thanks, I didn't know you could cook 63amp RCDs without them operating. I don't think I knew that anyway. It's never been an issue. Also didn't know you could get a device to stop two loads being used at once. And good points about more than one lighting cct hanging off an MCB. I always forget to check that before I price things up, and it did once completely snooker me, although I got the money back in other ways as they booked me for the rewire and board change. But it weren't funny. I hate lighting circuits, especially with dimmers and intermediate switches etc, you're supposed to test every damn bit of them, and it just takes for ever.

  • @MartiA1973
    @MartiA1973 5 років тому +7

    Really useful. When are home buyers going to start asking for these reports before purchase.

    • @dsesuk
      @dsesuk 5 років тому +5

      I know. You wouldn't pay top price for a car without an MOT, yet people just aren't aware of the checks they should be doing before forking out five or six figure sums for a house.

    • @cameronloggenberg2867
      @cameronloggenberg2867 5 років тому +2

      In South Africa it is a legal requirement to have the full electrics tested, you also have to have the water and woodwork (roofs, floor joists). Means that cowboys cannot get away with things.

    • @curtisj2165
      @curtisj2165 5 років тому +2

      I thought it was required as part of the house buyers pack

    • @dsesuk
      @dsesuk 5 років тому +2

      @@curtisj2165 I believe this sort of thing was required as part of the Home Information Pack in England and Wales, but then the HIPs were scrapped a few years ago. We still come across plenty of people who ask us to perform an EICR after they've splashed out and moved in.

    • @matthewcollis-long5233
      @matthewcollis-long5233 5 років тому +1

      David Savery Electrical Services o

  • @andrewstone841
    @andrewstone841 5 років тому +1

    Great video thanks David! Seen exactly the shower thing a couple of times now with multiple en-suite hmo conversions.
    The subject needs more attention to it, especially on the generally terrible EICR form, would love to see how you tackled detailing this on the cert.

    • @dsesuk
      @dsesuk 5 років тому +1

      Hi Andrew. It is an awful form, I quite agree! The failed RCD I've coded as a C2 in item 4.8 (manual operation of circuit breakers and RCD's) because it won't react in the event of a leakage fault, and as a C1 in item 4.19 (RCD's provided for additional protection) as it's handling more current than it was designed for, so all bets are off as to how it will react. The failed RCD also shows up elsewhere on the checklist of course (items 5.12.1, 5.12.3, 5.12.5 and 6.1). As the demand of the installation is potentially more than the service head should be handling, I've put that as a C3 in item 1.2. It could perhaps be argued that a C1 or C2 applies, but it's been coping for the past fifteen years, and besides the common sight of the tarry insulation having leaked out, there's no outward evidence of it being unable to cope. We have an enquiry in with WPD about replacing the head to 100A PME with an isolator, and we have the go-ahead for a board change. One of the showers will be decommissioned as they're turning that bathroom into a utility room, so that should help the situation!

    • @andrewstone841
      @andrewstone841 5 років тому +1

      Thanks for the detail David. Ar the difficulties of trying to express a problem with something that’s apparently been fine for an age, but good call on the service head item i feel.
      I would have probably gone with just C2s for the rcd but can’t fault you!
      At least it seems your client is interested in getting it improved, that’s 90% of the battle in my experience, and if you’re board changing with 2 showers you can get the rcd load sorted even if they don’t want to spring for rcbo’s.
      Not a bad result at all.
      Top notch work as always mate!

  • @rogerlawson6031
    @rogerlawson6031 5 років тому +2

    Having looked again at the video, david says that it isn't a simple case of 'crossed cores' on the armoured cable, (and the circuit appears to be rcbo protected) so l hope he gets the job of sorting out why there's an amp of current in the earth lead and lets us know the answer...RL.

  • @henrytwigger2245
    @henrytwigger2245 5 років тому +2

    Electric showers are an excuse for bad plumbing !
    Apart from the maximum demand issue, there's also the peak rate issue. If you are going to heat water with electricity, which is expensive anyway, why no use off peak electricity to heat a tank of water at night ? Modern insulated tanks stay hot for a long time.
    You need to keep the electric shower on constantly while you are showering, to stabilize the temperature. While you're soaping up, you'll need to direct the shower away and waste hot water. With a thermostatic mixing valve you can get a quick blast of hot water to wet down; stop and soap up; and get another quick blast to wash off. You'll use less water in the shower and save dosh !
    But you'll need a mains pressure, stainless steel hot water tank. But really everyone should have one of those nowadays.
    When the new smart electricity meters take off, using up cheep rate electricity is going to be even more important. When the wind blows and all the wind turbines come on-line, there's a glut of power. So why not get ready to take advantage of it by boosting your hot water on the cheep ? That's if this technology ever arrives !

  • @artisanelectrics
    @artisanelectrics 5 років тому +2

    Great video!

    • @dsesuk
      @dsesuk 5 років тому +5

      I need to follow your example of filming on site more!

  • @Pentium100MHz
    @Pentium100MHz 5 років тому +1

    Interesting that you can get high power single phase line in the UK. In Lithuania, if you want more than 5-10kW, you will get three phases.

    • @dsesuk
      @dsesuk 5 років тому

      You find few overhead cables here unless you go out into the countryside, it's all underground in the urban and suburban areas. I guess when they were rebuilding after WW2, they figured up to 100A single phase ought to be enough for anybody (domestically), although in these days of instantaneous hot water heating, induction hobs and electric vehicles it's all looking a bit creaky. A lot of digging up can be required to upgrade to a three-phase supply.

  • @the_real_hislordship
    @the_real_hislordship 5 років тому +1

    100 amp single phase? It amazes me that three phase isn't used more often with so many large loads. One shower per phase, split the other loads as well. Reduce voltage drop.
    Here (South Africa) I have 3 x 60A incoming (now it's normally 3 x 80A).

    • @nrg-5003
      @nrg-5003 4 роки тому

      It will amaze you even more that the dno's give each property a diversity of only 2kw when designing their network. So on a typical housing estate with about 150 homes all capaple of drawing 60 to 100 amp each!! Is all fed from only a 500kva or 1mva transformer which is only capable of delivering around 700 to 1.45ka! If that is not diversity i don't know what is, and amazingly it all works!

  • @sosurko
    @sosurko 5 років тому

    Great video. Helps to see someone else carry out an EICR and how you investigate

  • @samuelfellows6923
    @samuelfellows6923 5 років тому +1

    Your description of the property - two pre-war houses turned into a mansion - if the price goes into the millions I call them that.

  • @RWATraineeElectrician
    @RWATraineeElectrician 4 роки тому +2

    Was the previous spark playing "pin the tail on the donkey" when wiring the extension?

  • @robertchapman4726
    @robertchapman4726 3 роки тому

    As soon as you see an SwA terminated without a gland the alarm for shoddy work and incompetence should ring loud.

  • @mohammedkhan5344
    @mohammedkhan5344 5 років тому +11

    This is For all those guys who ignored the electrical science in college ank kept saying it will never be useful. P=VI

    • @ef7480
      @ef7480 4 роки тому

      Indeed.... VIR PIV,,,

  • @rossmurdoch7870
    @rossmurdoch7870 4 роки тому +2

    Hi David,
    Would it be worth asking for a 3 phase supply and reworking from there?
    Regards

    • @mahrous65
      @mahrous65 3 роки тому

      yes u right i did not say any thing about the max demand and diversity how to solve the demand .the rcd do not solve the high demand.

  • @idontthinkso2058
    @idontthinkso2058 2 роки тому

    Even with the service cable changed and new 100amp bs 88 .the circiuts demand current is still over 100 amp supply ..
    3 showers 40 amp each ..NO DIVERSITY ON SHOWERS SO 3X 40 120 A ? .
    A 3 PHASE SUPPLY IS REQUIRED ..

  • @sandman873
    @sandman873 5 років тому +5

    Do you get fries with an EIC?

  • @johnnevin5706
    @johnnevin5706 4 роки тому

    Thank you, David, for your upload

    • @dsesuk
      @dsesuk 4 роки тому

      Cheers John, thanks for your comments.

  • @ursusmaritimus7159
    @ursusmaritimus7159 5 років тому +1

    Interesting video, thanks. It reminds me of an installation I was slightly involved in (I was doing the data cabling only) around fifteen years ago which had two electric showers. The system was TNS and the head really old with ceramic fuse carriers. The supply was strangely two-phase and neutral (with only one phase in use) and the electrician suggested getting the DNO to supply a second head for the second phase, with a separate CU connected to it for the second shower. What I didn’t get is that assuming the service head fuses are to protect the supply cable, surely the neutral would be carrying the combined current of both phases? The DNO guys seemed perfectly happy with the arrangement when they came (I recall the guy touching the neutral in the head with his finger and quipping “polarity test”!). Interested to know any thoughts…

    • @projectbuild9784
      @projectbuild9784 5 років тому +2

      The different phases are out of phase so when one is peaking the other is 120 degrees out of phase. They never put peak power out at the same time so the neutral isn't dealing with two synchronised phases which is the problem you seem to be imagining.

    • @petehiggins33
      @petehiggins33 5 років тому

      @@projectbuild9784 It's even better than that. If you add together the neutral currents from two different phases each being say 10A then the amplitude of the combined current is also 10A (and not 20A). This assumes sinusoidal currents which heavy loads will be.

  • @carletonmould2001
    @carletonmould2001 4 роки тому +1

    Hi Dave great video. I came back and watched this video after testing a single dwelling with over 30 circuits... If you don't mind me asking, what was the outcome in the end..?

  • @stuartmc18
    @stuartmc18 3 роки тому

    This EICR has possibly saved the property owner from a house fire!

  • @tent7014
    @tent7014 2 роки тому

    In the Shire of Will the Bard, I would have expected some Quipping and Japping

  • @jasonhowe1697
    @jasonhowe1697 5 років тому +1

    by looking at that
    likely ex gov 50's-60's house with retro fitted rcd that is only really designed internally in the rcd itself to hold 1 circuit unlike the 10-20 amp breakers of yester year where you overload to a degree before frying the break..
    with the the rcd breakers are built today it is 1 point to 1 circuit
    I suspect with the granny flat modification you are looking at the power co to come and install a 200-300 amp service
    split between each home area..
    looking at the extension i would say dyi bodge job within the life of the home
    my opinion i'd do an electrical gut and bring it into todays code rather leave it alone and do a date of install grandfathered mess
    the main rcd should be around 100-150 amps
    covering 2 30 amp circuits 2-6 15 amp circuits wall circuits, 2-3 10 amp circuits for lights..

    • @jasonhowe1697
      @jasonhowe1697 5 років тому

      @Cupid Stunt in australia skinny 80 amp main breaker with 2 x30 amp breakers feeding 3 single points and 4 double points and the other feeding 3-4 double points
      on 15 amp domestic wiring .
      1 circuit has 2x outside singles, 1 internal single (fridge), 2 points double (bedroom)
      2 points bathroom 1x double washer/dryer 20 amps draw, fridge 10-15 amps draw..
      on an 15amp domestic wire.. @240watts mains
      though the basic point that the point to save cash 2xc15s were used where they could of wired each point individually given the amount of real estate in the fuse box..
      Main point I was getting at most likely would been better if this was an ex council rental would of been to gut completely than mess around with the bullshit of grandfathered date of install which leaves people that don't know any better of blinders on see no evil, report no evil..
      I am a firm believer of meet or exceed minimum electrical safety codes of today than live in the grandfathered systems of date of install.. as it leaves the consumer in a legal time mess

  • @ashmanelectricalservices4318
    @ashmanelectricalservices4318 5 років тому

    Yes the RCD main switch is fried but has the DNO service fuse ever blown... It looks as though the service cable has suffered the most as a result of the overloading.

    • @sdgelectronics
      @sdgelectronics 5 років тому

      No degradation is apparent on the service cable.This is just standard PILC with a cloth outer covering.

    • @TheEulerID
      @TheEulerID 5 років тому

      Given the state of that system, it's almost like there isn't a working fuse in there.

  • @artisanelectrics
    @artisanelectrics 5 років тому +1

    Whoever decided to put consumer units under stairs deserves a slap! 😂

    • @curtisj2165
      @curtisj2165 5 років тому

      It's there because nobody wants to see it

    • @andrewstone841
      @andrewstone841 5 років тому

      Would rather it be there than over the front door or the downstairs toilet

    • @curtisj2165
      @curtisj2165 5 років тому +1

      @@andrewstone841 or in pride of place in the living room

  • @KevinRoseYT
    @KevinRoseYT 5 років тому

    Are you sure that the brown has been used as the neutral at the RCBO? I think you've made a mistake. Remember that different RCBOs have their connections the other way round. The brown is at the front and going to the upper L terminal. The upper terminal is always the front and lower always the back irrespective of which one is L or N. The only swap is the grey and black.

    • @dsesuk
      @dsesuk 5 років тому

      Hi Kevin. That was a 'voice typo' addressed in the description; I said brown, but I meant black. I didn't notice the error until after upload which is why there is no on-screen correction.

  • @robertchapman4726
    @robertchapman4726 3 роки тому

    If your adding circuits to an existing install and not even labeling the circuits....then you should ensure your spurs dont mark the floor whilst you are there

  • @PJB71
    @PJB71 5 років тому

    David, that was an interesting video, sometimes it’s unbelievable what you actually find. I find it hard to believe that there’s 3 electric showers & 2 cooking circuits as well as everything else. In a domestic situation, sometimes, I just don’t want the rectifications. It would be interesting to see the EICR & your reasons behind the coding. It would also be interesting to see your plain English version to the client. I have found electricians tend to code & have different interpretations of the regs. I have installed a priority switch many years ago for 2 showers. I am curious to know what you would do with the third.

    • @dsesuk
      @dsesuk 5 років тому +1

      Thanks Patrick, you're right about the coding, it is open to interpretation and often down to the discretion of the inspector as to how something should be listed. Besides that, the report is an awful form and there's nothing in the inspection schedule checklist specifically about demand. Apart from the individual circuit faults, the failed RCD I've coded as a C2 in item 4.8 (manual operation of circuit breakers and RCD's) because it won't react in the event of a leakage fault, and as a C1 in item 4.19 (RCD's provided for additional protection) as it's handling more current than it was designed for, so all bets are off as to how it will react. The failed RCD also shows up elsewhere on the checklist of course (items 5.12.1, 5.12.3, 5.12.5 and 6.1). As the demand of the installation is potentially more than the service head should be handling, I've put that as a C3 in item 1.2. It could perhaps be argued that a C1 or C2 applies, but it's been coping for the past fifteen years, and besides the common sight of the tarry insulation having leaked out, there's no outward evidence of it being unable to cope. Other's may have coded things differently, but whichever way you look at it, the report deems the installation to be unsatisfactory with 23 observations listed, and the covering email that went with it had about 1200 words explaining the issues and what needs to be done. The client tells me she has already contacted Western Power about putting in a new 100A PME service and isolator after I sent her a link to their contact form, and she has asked me to go ahead with a board change plus remedials so we should have a follow-up video in a few weeks.

    • @mickbitchum4664
      @mickbitchum4664 5 років тому +1

      @@dsesuk congratulations on being awarded the remedial works.... I think🤔🤣

    • @dsesuk
      @dsesuk 5 років тому +1

      @@mickbitchum4664 It might be a bit of a short straw job!

  • @johnschlesinger2009
    @johnschlesinger2009 5 років тому

    The tails going to the cutout look like 16mm. I bet the cutout is 60A, which explains the overheating. Those things can carry 80A for quite a while. The board is a real mess!

    • @dsesuk
      @dsesuk 5 років тому

      Not pretty is it?! It is 25mm on the tails there. We had Western Power out yesterday who have confirmed it's a 100A fuse, the earthing is properly soldered onto the sheath and the cutout is in good nick. They've rubber-stamped it as fit for purpose to carry on, so that's some good news for the homeowner!

  • @ottoschless4115
    @ottoschless4115 5 років тому

    Maximum demand can be alleviated slightly with led lighting, new energy consumption appliances and going to gas hot water. Correct , split the sub circuit rcd to rcbo's. It is not to wiring rules to have multiple circuits on an individual rcd now.

    • @dsesuk
      @dsesuk 5 років тому

      LED lighting is a no-brainer, gas appliances are fine, so long as you accept that gas is on the wane and will cost a lot more a few years from now (there will be many switching from gas to electricity in the future). The wiring regs do still permit the use of RCD's for multiple circuits however, in fact, 18th Edition introduced a new reg specifically stating this, 531.3.5.2, although the implementation on this site is poor.

    • @ottoschless4115
      @ottoschless4115 5 років тому

      @@dsesuk My work is in Australia and rcd circuit protection cannot be greater than a 50/50 ratio. In other words if you have 4 power circuits then they have to be on a 2 to 2 rcd ratio and not 1 rcd for all. I have found recently with the more reasonable price of rcbo's that the majority of customers will go with all individual circuit protection on light and power circuits. We normally install a 3 phase service line and there is no problem with max. demand issues. It seems the installation there has not been inspected by the regulatory authority. Probably a cash job.

    • @dsesuk
      @dsesuk 5 років тому

      @@ottoschless4115 Ah, well you probably have more sensible rules than us - the regs here didn't even acknowledge the RCD issue until last year's 18th Edition, and even then it seems to rubber-stamp it rather than recommending a ratio. We're mainly single phase domestically here, and with most services underground that isn't going to change easily. As for regulatory authorities, there are none. This was probably all done by the builder rather than an electrician, no certificates, no warranties, nobody checking until it's all too late!

    • @ottoschless4115
      @ottoschless4115 5 років тому

      @@dsesuk Thanks for your reply. The electrical trade there really needs some scrutiny, otherwise you will be inundated with cowboys. Hopefully nobody gets injured or killed by someones stupidity. If you are correct and the builder did it, ( electrically unlicensed ),well he will be severly fined and punished here. A notification of electrical work certificate must be given to the regulatory authoriry here when the connected load is increased with any additional installation. Anyway enjoy your work.

  • @rattlehead85
    @rattlehead85 5 років тому +4

    The joys of carrying out EICR’s on properties post purchase when you find stuff that’s in need of attention 😩😩

    • @09weenic
      @09weenic 4 роки тому

      rattlehead85 exactly - it should be compulsory for the buyer to obtain a current EICR for the property

  • @gd-bq7em
    @gd-bq7em 2 роки тому

    Hi David a friend of mine once went to a house with 4 electric showers. So he called napit and spoke to an adviser and he said he ust to work Blackpool area and ust to see that situation often and his answer was there is no way all 4 showers could run at the same time any way because the water pressure would not be strong enough.
    And it kind of makes sense I know if I run my shower and some one turns tap on there water just trickles out of the shower.
    What's your take on it.
    I have never actually tested to see if the shower still pulls the 32 amp if water not coming through at full pressure

  • @markyd2633
    @markyd2633 5 років тому +12

    Now that was a very interesting vid......Thanks for that.......by the way I am being serious....enjoyed that

    • @dsesuk
      @dsesuk 5 років тому

      Thanks for the feedback!

  • @rogerbean393
    @rogerbean393 5 років тому +1

    Hi there , quality videos, thank you.
    Do you like the TIS MFT Pro ? Noticed you had a Metrel in another video.
    What’s you preference and why ?

    • @dsesuk
      @dsesuk 5 років тому +3

      Thanks Roger, I have a Metrel MI3100s, a Megger MFT1552, a Fluke 1651B and the TIS MFT Pro just because I like my toys! They're all fine instruments, and I can work with any of them. The Fluke was retired as it lacks an auto RCD test and I was getting some odd readings occasionally on the resistance function. The Megger was my original tester and still works, but I now keep it in a secondary box that is used only when additional personnel are working with us. The MFT Pro fits in my main tool box so is my everyday machine for basic faultfinding, and the Metrel is my calibrated machine used for the EICR and initial verification work. I prefer the Metrel over all the other testers simply because it displays more information at-a-glance. The voltage between line, neutral and earth is always on the screen regardless of the selected test, the Max Zs value for the selected protective device is shown on the display when loop testing so you can see how close you are to the limit, it supports phase rotation unlike my Megger and Fluke models and it works well with the neck strap (I can't figure how the TIS is supposed to be worn!) It also has a good clear display with nice big numbers and can be placed on charge without having to extract the batteries unlike all the others. The TIS machine has a couple of functions the Metrel lacks - PQA and earth leakage, but you need an expensive accessory to make use of them. I have one here, and will do a video showing it in action soon. The TIS has updateable firmware, so there may be an update in the future which allows it to do a couple of the things the Metrel currently does, e.g. show the max Zs for the selected device (it knows the number as it issues a pass/fail when testing, so there's no reason why it shouldn't display it for the operators reference), and show either the voltage or a warning of a voltage when one is present and the menu screen is selected (at present, it's the only tester that doesn't display any indication of live connection when first switched on, you have to enter one of the menus first). The TIS is the only tester of my bunch which can store results for later download - a feature I don't use!

    • @martynfulcher7386
      @martynfulcher7386 5 років тому

      David Savery Electrical Services o

    • @rogerbean393
      @rogerbean393 5 років тому

      David
      Thanks for reply , just brought a TIS voltage indicator after just viewing the video.
      Like you I have a megger/fluke and a metrel
      Like the touch screen.
      Think I might buy the Pro as it’s been a good month.
      Love the humour and knowledge base.

    • @dsesuk
      @dsesuk 5 років тому +1

      @@rogerbean393 Blimey Roger, now I'm getting worried that I'm influencing you to spend too much on the toys!

  • @graemebell8242
    @graemebell8242 5 років тому +2

    What is the story behind the McDonalds cap? I got more interested in the hat than the faults. Lol

    • @dsesuk
      @dsesuk 5 років тому +1

      Daughter #1 used to work there, so it's spare and...well... I needed a hat.

    • @graemebell8242
      @graemebell8242 5 років тому

      Fair play to you. 😂

  • @michaellack5139
    @michaellack5139 5 років тому +1

    I did a test on a split load just yesterday and found all power rhs and all lights on lhs.. come on sparkys really....if you don’t know what your doing just leave it

  • @MrPaul1f
    @MrPaul1f 5 років тому +1

    Great video, be great if you could do a follow up

  • @MrBanzoid
    @MrBanzoid 5 років тому

    Great vid. It explains a lot. Thanks and subscribed.

  • @adrianwint6177
    @adrianwint6177 5 років тому +10

    Your "earth leakage" test is flawed. You are measuring the current in the main earthing conductor with the bonding still connected on what appears to be a PME system. You are measuring diverted network neutral currents which will exist in a healthy system. Repeat your test by clamping both meter tails into the current clamp & see if you get the same result.

    • @dsesuk
      @dsesuk 5 років тому +7

      It's not PME, but off camera I did check with the bonding off and via the tails. Results were similar, so I went with what was easier to demonstrate. I take your point though.

    • @anwah100
      @anwah100 5 років тому +1

      Its not pme

  • @londontrada
    @londontrada 5 років тому +2

    I thought Rik Mayall was dead.

  • @jasontrundell8349
    @jasontrundell8349 5 років тому

    good video mate informative and to the point well done

  • @brotheradam
    @brotheradam 4 роки тому

    I like all the information. Wouldnt it be better to use two or even three split boards? One for running the other two and common areas? then one for the sections? Shouldnt the Granny flat have its board in the flat, like a Shed? So in effect, board one from the meter would be three outputs for other boards, plus common lights, second board for main house, third board for granny flat, ad fourth board being shed?

    • @brotheradam
      @brotheradam 4 роки тому

      In USA and Jamaica the granny flat and the shed are usually on their own boards, as sub panels from the main board. In Jamaica actually a multifloor house is usually set with a panel on each floor, for that floor, and a main panel supplies those panels.

    • @dsesuk
      @dsesuk 4 роки тому +1

      Hi Adam. Had this been my design when being extended/renovated, then I would have made a more logical layout of the circuits and perhaps used a sub-board to split things off. Sadly, what we found here was a builder's breakfast that someone had thrown in about fifteen years prior. A lack of planning and execution left the place with more circuits than were needed all coming back to an oversubscribed board in a single location. When we performed the remedials and upgraded the board in a later video, some of the circuits were combined into more logical arrangements, but without being able to damage finishes and renew large parts of the wiring, we were left with the single location and making the best of what we could.

  • @tasmedic
    @tasmedic 5 років тому

    Bring another phase in. It might sound clever to put a contacter in so only one shower can be used at a time, (which is all that is actually needed to do the job, nothing new or exciting about that) but if you do that, what exactly is the point of having more than one shower? You'll end up with the usual scenario of teenagers fighting over the shower at weekends. Which is probably why the extra showers were put in to start with.

  • @hannahranga
    @hannahranga 5 років тому +2

    I wonder if they meant to fit a 63A rcd and breaker combo (or that was fitted till they got fed up with the "nuisance" tripping and got a fuckwit who just replaced it with an rcd)

    • @Berkeloid0
      @Berkeloid0 5 років тому +2

      Apparently some people confuse the rating on the RCD thinking it will trip like a breaker at its rated current, not realising that RCDs don't work like that. I've seen a few videos where plain RCDs were installed as if they were MCBs/RCBOs, with the installer apparently not knowing the difference.

  • @90sw12
    @90sw12 5 років тому

    Great video. Really well explained 👍

  • @simonmaverick9201
    @simonmaverick9201 3 роки тому

    Isn't it possible to have the showers off a separate incomer tail supply fitted by the electricity supplier??

  • @KevinRoseYT
    @KevinRoseYT 5 років тому

    Would it not have been more accurate to measure the earth leakage by putting the clamp around the line and neutral and measuring the resulting difference between the two? By measuring the earthing conductor you only get part of the earth leakage current as the rest will be flowing through parallel earth paths like bonding, pipework etc.

    • @dsesuk
      @dsesuk 5 років тому

      Yes. I'll show that in a future video.

  • @deankeys8185
    @deankeys8185 4 роки тому

    will you have to remove some of the loading so it sits under the 100hrc main fuse ? be nice as i'm a crap 16th ed spark. great video's as i'm learning more now than when i was at tech.

    • @dsesuk
      @dsesuk 4 роки тому +1

      Hi Dean. I'm always nice! Well, mostly. But yes, two of the electric showers will be booted out. One's going on the boiler, the other is being converted into a utility room.

    • @deanames5614
      @deanames5614 4 роки тому

      @@dsesuk many thanks and keep up with the great vids

  • @mark90229
    @mark90229 Рік тому

    Need priority switches for the showers

  • @andrewmayes3271
    @andrewmayes3271 5 років тому

    Great vid once again is there an easy way IE app or website to find out who the snow is for a property

    • @dsesuk
      @dsesuk 5 років тому +1

      One DNO lookup is here: www.energynetworks.org/info/faqs/who-is-my-network-operator.html

  • @michaelwhite28
    @michaelwhite28 5 років тому

    I enjoyed it. Why are you wearing a cap under the stairs? are you allowed to be there?

    • @dsesuk
      @dsesuk 5 років тому

      Keep the cobwebs out of my hair!

  • @carforumwanker
    @carforumwanker 3 роки тому

    David , Can you tell us more about your MFT you are using ?

    • @dsesuk
      @dsesuk 3 роки тому

      That's the TIS MFT Pro which I carry in my main toolbox. There's an older video of it where I was a bit sniffy about the thing after I bought it in 2018, but I get on rather well with it after a firmware update addressed the main issue I had at the time. I keep meaning to do a new video showing its cheaper sister, the MFT Eco, and how they compare, but there are never enough hours in the week.

  • @carlrobson5745
    @carlrobson5745 2 роки тому

    Probably a builder lashed the board in who thimks he can do electrics as its only three wires in it 😵‍💫

  • @mikeenglish1492
    @mikeenglish1492 5 років тому

    Considering the amount of defects would you not of recommended a rewire? Good vid, very interesting

    • @dsesuk
      @dsesuk 5 років тому +2

      It's not necessarily worth throwing out the baby with the bathwater. Most final circuits tested okay. Some rooms are being refurbished, but others are in good nick, so hard to convince the homeowner to start knocking holes in the place unless it's really a write-off.

  • @mondotv4216
    @mondotv4216 5 років тому

    Interesting how popular electric showers are in the UK. Do they actually save money over an off peak storage tank or is it purely done for convenience and space? In Australia we generally have instantaneous gas or gas or electric or even solar storage tanks. Of course we don’t have a ring system either so you’re probably wondering how we survive without getting electrocuted daily :)

    • @dsesuk
      @dsesuk 5 років тому +1

      It's a convenience thing I guess. Traditionally, people did have hot water tanks, but they're generally ripped out of our pokey little homes for more storage space. Electric showers are easy to install and can heat water on demand which makes them handy for a larger family environment. On a back-to-bricks refurb, a combi boiler which can heat the water via gas would be better. Don't knock your lack of rings, they're awful things, a throwback to WW2 that nobody else in the world bothers with. I don't install rings myself, they're for the old boys who won't change, or the cowboys who know no better!

    • @mondotv4216
      @mondotv4216 5 років тому

      David Savery Electrical Services Oh I know rings are a pain compared to a conventional radial circuit. Did they come about because of a shortage of copper in WW2?

    • @dsesuk
      @dsesuk 5 років тому +1

      @@mondotv4216 So Wikipedia tells me!

  • @AllkoDH
    @AllkoDH 5 років тому

    Hey, thanks for this video. How does current leakage occur? How is it getting on that earth wire?

    • @dsesuk
      @dsesuk 5 років тому +6

      I'm not showing the current leakage measured properly here as others have commented, but where it is coming from this installation, it'll be either through appliances that have a natural leakage such as with some electronic equipment, or more likely through poor insulation resistance. Two of the socket circuits on this RCD have zero readings when I.R. testing, and if the RCD were operable then it would be tripping all over the place.

  • @zjzozn
    @zjzozn 5 років тому

    Great example of jobs we don’t really want, but then enjoy putting right. Two shower circuits make me shudder 😳

    • @dsesuk
      @dsesuk 5 років тому

      It's one of those where a lot of time could be lost putting it right!

    • @sdgelectronics
      @sdgelectronics 5 років тому

      Two showers is usually fine. Just make a priority switching unit to take care of it.

  • @Roverturbo
    @Roverturbo 4 роки тому

    I thought you had to contact the dno if wanting to connect two or more electric showers?

    • @dsesuk
      @dsesuk 4 роки тому

      In theory, I think (and I may be wrong) that if your MD exceeds 60A then you're supposed to inform the DNO, but in practice I've never seen it done. The only time I inform the DNO of a load to be connected is on a car charger installation. Personally, I wouldn't recommend more than one electric shower on a 100A single phase installation, and if more than one is insisted on, then I'd advise a load sharing option such as the Garo product I spoke of in another video. I suspect that most installers just do what the client asks for, and to hell with the consequences because nobody is policing anything.

  • @johnwaby4321
    @johnwaby4321 4 роки тому

    Don't you just love circuits not labelled up . And some that just say plugs with no location indicated.

  • @ArcanePath360
    @ArcanePath360 5 років тому

    What is the difference between EICR and NICEIC? I had a certificate for the latter when I bought my home but I've found nothing but horror shows all round the house. You wouldn't believe some of the things I've uncovered.

    • @dsesuk
      @dsesuk 5 років тому

      An EICR is an Electrical Installation Condition Report which is a process that may be undertaken by a suitably qualified and insured electrician to ascertain the current state and safety of your existing electrical installation and to compile a report compliant with that laid out by BS7671 showing the results of the test and inspection process. NICEIC are an accrediting body the same as NAPIT, Elecsa, Stroma, NAPIT et. al. Someone registered with an accrediting body should, in theory, know their onions, as continual assessment by that body should ensure they're working within their means. My company is accredited with NICEIC to undertake EICR work as I hold specific qualifications and professional indemnity insurance to do so. Someone else may be registered with another accrediting body to the same standard. That said, you'd be amazed at the crap reports we come across, both by chancers who aren't accredited at all, or by those who are for installation work only but not testing/inspection. If you think you've been short changed on an inspection by someone who is accredited, it may be worth speaking with the accreditation people on their helpline number or to have someone else cast a second opinion.

    • @ArcanePath360
      @ArcanePath360 5 років тому

      @@dsesuk Thanks. It was a number of years ago and I've put right most things myself as I went along, while my builder Dad did extensive work on the home, replacing walls, ceilings, floors etc. I saw things electrical wire running over heating pipes, an outlet spurred off the cooker socket and installed on the inside of a cooker extractor (where the steam from cooking passes directly over it) to power the fan, metal light switch face plates which aren't earthed, wires running out through the wall on the outside of the house, going in through the top of the junction box with a busted gland and cloth tape wrapped round it.... just off the top of my head. These all felt like one off things at the time I put right but they all added up to make me wonder what other sins are going on that I haven't seen. I did notice the old black and red wiring in the ceiling in parts of the house.

  • @maxdunning5612
    @maxdunning5612 Рік тому

    just been testing a few properties with the issue regarding maximum demand, what did you code it as ive not been able to find any info from bpg4 ot any forums, last resort will be to call niceic

    • @dsesuk
      @dsesuk Рік тому

      If I think too much current is being pulled through a device not rated for it, then I'd code it C1 Max. This isn't a fault current issue, it's the everyday design current that hasn't been factored in here.

  • @TheEulerID
    @TheEulerID 5 років тому

    Get rid of the electric showers, put in shower pumps or, better, a mains pressure hot water storage system, like a Megaflow. Three 10 kW electric showers in a domestic premises is crazy, besides which, you don't even get a decent shower. More money, but the proper way to do it.
    Either that, or with two kitchens, three electric showers and all the rest, they'd better get the order in for three phase supply...

    • @dsesuk
      @dsesuk 5 років тому

      I agree, a Megaflow or similar would have been ideal, and it's a shame the previous owners and the idiot builder who converted the garage into a 'house within a house' with it's two additional showers and cooker just didn't think about it. It's difficult to retrofit now that we have fitted kitchens and (in much of the new section) a flat roof, so running new pipework would be tricky. Work is already underway to sort all this out though, WPD have been out and confirmed the head is in good nick and has a 100A fuse, one shower is being decommissioned as that bathroom is to be converted into a utility room and we'll be making some other changes, so a follow-up video in a few weeks should detail the differences.

    • @TheEulerID
      @TheEulerID 5 років тому

      @@dsesuk An excellent video by the way, but there was so much wrong with that installation it's one of those what on earth were they thinking of moments. It was an electrical fire waiting to happen.

  • @muzikman2008
    @muzikman2008 5 років тому

    Good point.. Well raised 😉👍

  • @carlp1581
    @carlp1581 5 років тому

    Superb video!!

  • @ghspaelectricalservices9296
    @ghspaelectricalservices9296 5 років тому

    Good vlog was talking about max demand earlier today

  • @alinili5569
    @alinili5569 5 років тому

    People charge by the circuit looks like they do good works and proper and safe testing but people just say price or set price they don’t do test and check every points or they way they should do I noticed that for few years and lots of people go by price regardless of their safety and good jobs I charge 70 call out and 25 per circuit on domestic and three phase 90 and 35 per circuit and truly I don’t like to do EICR

  • @paullyons4624
    @paullyons4624 5 років тому +1

    Great vid. Would be good to see a video of the shower sharing thingy. You were in your element under there with all that alcohol

    • @dsesuk
      @dsesuk 5 років тому

      I couldn't touch a drop unfortunately! Yes, I'll get a vid uploaded of the shower switcher! It's high on my video to-do list because it should be quite quick and simple as I have one a metre from my desk!

  • @Volt268
    @Volt268 5 років тому +1

    Is there a calculation that could be applied to work out the maximum demand?

    • @dsesuk
      @dsesuk 5 років тому +6

      See Appendix A of the OSG for maximum demand and diversity. It's a tricky one as you can never really be sure what the client will be connecting up, but unless you have known load values, then you assume 100W per lighting point (and can then take 66% of all lighting overall), 100% for the highest rated two electric showers/instantaneous water heaters, then 25% for any subsequent, 100% for the highest rated socket circuit, then 40% for each additional, 100% of any immersion heaters, cookers are 10A plus 30% of the remaining load plus an extra 5A if the control unit has a socket built in (etc.) I've also done it via measurement by using a clamp meter set to record a MAX value over a period of 24 hours average use. Usually you don't have to worry too much about it, unless you come across an installation with some heavy circuits such as multiple showers, car charge points etc. or if you get called out somewhere where the main fuse has blown without an obvious cause.

    • @Volt268
      @Volt268 5 років тому +2

      @@dsesuk sounds like a lot that I need to get my head around then. Will research more into it. Thanks for taking the time to reply. Great vids btw 👍🏻

  • @richsand007
    @richsand007 5 років тому

    Great video, just wondered which form filling software you’re using? Thanks

    • @dsesuk
      @dsesuk 5 років тому +1

      Thanks. I'm using Easycert. I've been meaning to do some videos on using it for a while now, I'll try to get them out this month!

    • @richsand007
      @richsand007 5 років тому

      Yes that would be helpful if you get a chance as there’s not much on UA-cam about it. I’ve had to stop using ELECSA online software, it’s just so bad now. Temporarily moved on to Electraform to keep my sanity!

    • @dsesuk
      @dsesuk 5 років тому +1

      Yeah, the CPS in-house solutions are poor. Electraform looks good, but they're pay by cert, and when I did the maths for the number of certs I issue in a year, I found sticking with Easycert was cheaper. It has some flaws, as I'm sure they all do, but I'll be starting work on those videos soon (it may be a three-part job), so watch this space!

  • @peterward8308
    @peterward8308 5 років тому +2

    IT hasn't failed anything,minis unsatisfactory.

  • @barrybritcher
    @barrybritcher 5 років тому

    Excellent video.

  • @davidroche6973
    @davidroche6973 5 років тому +3

    Do I spy a Maccy D hat 😉, but a great video. Thank you

    • @dsesuk
      @dsesuk 5 років тому +5

      Royaaaaale wi' cheese my friend.

  • @matijakobas5369
    @matijakobas5369 5 років тому

    Hi i am wondering why in the UK households always use obe phase system while here in Croatia most of the houses use three phase(my little 75 sq m apatment too).That house you are working in seems huge and they only have single phase electric. Why? Isn't three phases much better. For instance cooker in Croatia is connected by three phase and it has same power as one in the UK, while using much less power per phase. Wouldn't bringing three phase into that house solve all the problems?

    • @dsesuk
      @dsesuk 5 років тому +1

      I don't know, but I assume it's down to cost. I don't know what it's like in Croatia, but unlike many countries our cabling infrastructure is largely all underground in the towns and cities, and I imagine that after World War II, those responsible for rebuilding figured 60-100A single phase ought to be enough for anyone domestically. Generally, it is, but where a service needs upgrading, a lot of digging is called for which is expensive on the public carriageway, and not very desirable for someone who has a smart looking driveway or garden in front of their house!

  • @paulmorrey733
    @paulmorrey733 5 років тому

    Very interesting Thanks Dave