Hvac no cooling service call, Trane chiller locked out with sensor issues

Поділитися
Вставка
  • Опубліковано 5 лис 2024

КОМЕНТАРІ • 69

  • @HughesManHVAC
    @HughesManHVAC 4 роки тому +1

    Nice video 👍

  • @MegaDee911
    @MegaDee911 3 роки тому

    I'm glad that worked out for you. I have these sensors dropping left and right here in Florida.

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      Thanks MegaDee911! Always verify my sensors on P.M.s they do have a high failure rate, even though Trane told me they have improved

  • @princesswalt4010
    @princesswalt4010 3 роки тому +2

    I adore the sound of the VFD drives spinning on up

  • @MrBerniebling
    @MrBerniebling 3 роки тому +1

    The Hateful paste get everywhere no matter how hard I try to be neat! Nice vid

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      🤣, you know that's right! Thanks for watching!

  • @Ratman_Bejo
    @Ratman_Bejo 3 роки тому

    thank you for sharing your knowledge of service chiller

  • @Clifford03
    @Clifford03 2 роки тому

    The CHL I service is barely 2yrs old and I already have a bad sensor … Thanks for the heads up

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому +1

      They are a consistent problem with the sensors not reading correctly. Trane says they have improved the sensor design though they look the same to me. Just be sure to use the paste on them and verify your temperatures periodically. Thanks for watching Clifford!

    • @Clifford03
      @Clifford03 Рік тому

      @@EverythingHVACRI gotta agree with you … Found my 3rd faulty suction line temp sensor on Friday … Do I have to pay for the Trane software to bind the new sensor .?

    • @EverythingHVACR
      @EverythingHVACR  Рік тому +1

      I believe tech view software is free. I think I saw a link posted by subcool hvac on one of his videos recently, but It shouldn't be too hard to find.

  • @anthonywoolf9087
    @anthonywoolf9087 3 роки тому +3

    Exactly what my hand said 🤣🤣 nice I like it

  • @youssef1bentaleb168
    @youssef1bentaleb168 2 роки тому

    nice video bro a need your help

  • @danydjdberonbentzron8274
    @danydjdberonbentzron8274 3 роки тому

    Saludos desde Reynosa Tamaulipas México animo

  • @urielhernandez9848
    @urielhernandez9848 3 роки тому

    Excelllent information

  • @hirafatima4568
    @hirafatima4568 3 роки тому

    Nice video....thanks for sharing

  • @Max-Svift
    @Max-Svift 3 роки тому

    There is no temperature sensor reading on the CH530 display. We connect through the TechView interface. Visible connections 16pcs. Through TechView it shows: active - 0 / inactive 16 pcs. Why so? Is there a step-by-step instruction on how to bind a sensor?

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      You may have a failed sensor, go to binding view and see if it's there then unbind old sensor that's not reading and bind new sensor. If sensor is there you'll see it in the binding view, it may show up as "Red" because it's not reading all other operating sensors will show "green" always verify sensor temperature readings with a K type probe. -0 is an unusual reading

    • @Max-Svift
      @Max-Svift 3 роки тому

      @@EverythingHVACR How do I switch to snap mode? When I select the types of connections, all 16 sensors light up "red". A must burn only one, since only one faulty sensor.

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      Not sure what snap mode is but if all sensors show red you may have another issue, I have never seen one do that. That would make me think none are communicating, you could try a re boot of system. You may have to get ahold of Trane tech support.

  • @Rudy_Suseno1980
    @Rudy_Suseno1980 2 роки тому

    Is the trane Type R, has a drain valve

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому

      I don't think there is a drain valve but could be wrong, been a long time since this video

  • @joshstevens9826
    @joshstevens9826 3 роки тому

    First hit bind, and don't hit yes yet. After u have hit bind, then put ur magnet on, then hit yes.
    I've been thru that frustrating situation before.

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      Correct, it's much easier on the new chillers, all can be done from the control panel without using tech view. Thanks for watching!

  • @jayronesantos4567
    @jayronesantos4567 4 роки тому

    What is the name brand of thermal paste you used?

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 6 місяців тому

    Good ole CGAM

    • @EverythingHVACR
      @EverythingHVACR  6 місяців тому +1

      Yessir, all good except the sensors 😆

  • @kundanchavan2482
    @kundanchavan2482 2 роки тому

    Train rtac3504 chiller why going low evaporated temperature

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому

      Could be a lot of things, start with the basics Water flow, water flow, water flow. It's like air flow gotta have it, or you got another failing trane sensor.

  • @jasonpham0223
    @jasonpham0223 2 роки тому

    hello sir
    my chiller ch530 circuit 1 stopped after running for 20 mins. and show on the screen External circuit lockout. how do i solve this. please help

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому +2

      External lock out sounds like it's going to be External to the chiller, could be many things but you need to check all pumps, flow switches and anything that may be controlling this chiller.

  • @Noypihvac
    @Noypihvac 3 роки тому

    That the most problem with trane cgam suction temp sensor out of range temp reading

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      Yeah, all the sensors really, I've replaced a water temp sensor, it gets out of whack and locks out on low water flow. Thanks for watching!

    • @1MaximusDecimusMeridius1
      @1MaximusDecimusMeridius1 3 роки тому

      Mine is showing 226 deg suction temp 😂😂

  • @rakeshbishnoi3639
    @rakeshbishnoi3639 2 роки тому

    Hello sir ..my system show "chiller excessive loss of communication" alarm ...so what can i do ... Please provide solutions

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому

      I have never seen excessive loss of communication but sounds like you need to start with basic checks, Verify all voltage and that all components operate and no fuses blown. Communication loss is just something not communicating. After voltages and all other things are verified make sure all sensors are reading... correctly... a power reset may be necessary especially if there were any power issues that may have caused a board or control problem.

  • @jonnymac31
    @jonnymac31 3 роки тому

    CGAM best practices, step 1: update software lol. The easy rider is a necessary evil. Get a drop on you and 10 min later your the tin man.

  • @robhorner-starlakeny7426
    @robhorner-starlakeny7426 3 роки тому

    What do you mean when you say "bind" and/or "rebind" the sensor?

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому +2

      The sensors communicate information back to the control. You must remove the old sensor and un bind so the control does not see that sensor anymore. The you have to pull the new sensor in to the control and re bind. Basically setting the control to see that specific sensor. There are many videos on binding trane sensors. Thanks for watching!

    • @robhorner-starlakeny7426
      @robhorner-starlakeny7426 3 роки тому

      @@EverythingHVACR Thank you!

    • @_Padma_TausikHasan
      @_Padma_TausikHasan 3 роки тому

      Why is the magnetic LED to be caught while binding, and how does the LED light up when the magnet is caught?

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      Good question and maybe one for trane, I would guess for one thing it keeps you from buying just any sensor and installing it this way you must go back to trane for parts.

  • @aircooledchilleralltypes4938
    @aircooledchilleralltypes4938 3 роки тому

    Can you please send me the software

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому +2

      That software is free, you should be able to download it, no licensing needed. Its called tech view.

    • @lawrencebauzon4429
      @lawrencebauzon4429 3 роки тому

      Can be download free?

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому

      Honestly I'm not sure if it's free, it is not used as much anymore and usually the license that cost so it may be.

    • @lawrencebauzon4429
      @lawrencebauzon4429 3 роки тому +1

      @@EverythingHVACR Thanks bro.

    • @EverythingHVACR
      @EverythingHVACR  3 роки тому +1

      👍🙏💯

  • @bernieclement3373
    @bernieclement3373 2 роки тому

    How to bind a EEV theres no led!

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому

      Thanks Bernie! Is that a question? Not sure if the EEV binds it might be wired directly to the board. If it does bind you have to swipe a magnet just like the temp sensors then LED should light up.

    • @bernieclement3373
      @bernieclement3373 2 роки тому

      @@EverythingHVACR That circuit will not run. the program shows 22 things its looking at, but the EEV circuit 2 needs to be binded it had some com problem i had to rebind 3 other things.

    • @bernieclement3373
      @bernieclement3373 2 роки тому

      Anyways a Trane tec coming to help in maybe a week or so, oh well.

    • @EverythingHVACR
      @EverythingHVACR  2 роки тому +1

      If it won't bind you may need a new Valve, otherwise should bind the same way as the sensors I would think but I've never had a problem with the EEVs before

    • @bernieclement3373
      @bernieclement3373 2 роки тому

      @@EverythingHVACR Hello! Update on the chiller, the module harness that plugs into the eev is bad and they dont make them anymore. It sucks that chiller is only 10 years old so need to upgrade to new version of eev, short module harness and board up front that it plugs into. Confirmed by the trane tech to troubleshoot problem.