Ground Rods at Metal Poles, NEC 2020 - [250.4(A)(5)], (25min:09sec)

Поділитися
Вставка
  • Опубліковано 10 жов 2024

КОМЕНТАРІ • 161

  • @bigmikeh5827
    @bigmikeh5827 2 роки тому +8

    Mike. Shared this video with guys at work. You have created a learning environment and discussion. Your video has helped us all understand the difference between BONDING and Grounding.

  • @chrismeehan8996
    @chrismeehan8996 Рік тому +2

    Great video , I am a retired maintenance electrician and Love watching these videos . Thank you .

  • @dandearman2871
    @dandearman2871 2 роки тому +9

    Hello Mike. My Dad told me of a lightning problem they had at the Timken company at their Bruster plant. Lightning would hit the chain link fence, travel down the fence, jump across the opening at the main gate, into the guard booth on the other side and hit a water well casing that was inside the booth. He said they drove and connected ground rods next to each fence post and this helped but didn't completely solve the problem. They finally replaced all of the fence posts with very long post.

  • @hgbugalou
    @hgbugalou 2 роки тому +5

    I think some of the problem is people think they have to do this for 'lightning' safety. There seems to be a lack of understanding that lightning protection is its whole other ballgame and a single ground rod isn't going to protect anything or anyone.

  • @icevariable9600
    @icevariable9600 2 роки тому +2

    Fantastic video. I actually stumbled on it while I was meticulously going through your book. I had more questions about the voltage gradient && contact resistance of ground rods (seeking clarification) and found your video. Thank god! Because I actually think that one job I was on, the foreman had us skip the grounding of the parking light poles, saying "we'll just drive ground rods at each pole". As an apprentice, I know for a fact I'll be pissing off some journeyman foreman by telling him we're doing this wrong if he chooses to install ground rods in place of an effective ground fault current path. Thanks Mike! Love your books. You're literally saving people.

    • @brianhouse5983
      @brianhouse5983 5 місяців тому

      It's unfortunate that in our industry we can['t have adult conversations about this type of thing. Everyone is more worried about being in command than being correct. We are changing over a hundrted years of "tradition" in our industry. Thank you for taking the time to become educated and sharing that with others.

  • @stephenrosenthal5252
    @stephenrosenthal5252 Рік тому +1

    Should only be refered to as a short circuit path, not ground fault. Unless it is a stray voltage scenario in which some voltage is seeking ground or gfci.
    But as far as a ground fault path it truly is a short circuit path

  • @larryhendrickson8446
    @larryhendrickson8446 2 роки тому +1

    Thanks for the video very good content. What I found is It’s not an NEC requirement but it’s in the NECA NEIS 501 Standard for installing Exterior Lighting Systems

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +3

      I call this 'dinosaur do do.' Next time I speak with Mike Johnson (NECA), I'll let him know that it should be removed. Thanks

  • @maksmadman
    @maksmadman 2 роки тому +1

    Got You, Mike. I always was aware that most electricians don’t understand the Main Concept of Earth : equal amount of positive and negative in the Earth and as far as we know in Universe. If you intend to get the Deamons throughout this turmoil: Them gonna break loose
    Thanks, Mike for all your input
    I am an electrician and musician
    For 20 years

  • @FosterFarmsOk
    @FosterFarmsOk 2 роки тому +4

    I wish more electrical engineers around here would watch this video. Every new construction job i have bid and done has ground rods shown in the drawings at the poles

    • @hugh7364
      @hugh7364 2 роки тому

      i think wire fences post for livestock fields are recommended to be connected to ground electrode for lightning protection as per NFPA 780 Standard for the installation of lighting protection

  • @xXBuckOFiveXx
    @xXBuckOFiveXx 2 роки тому +6

    I was working for a lightning contractor and we had a bunch of small light pole/mail boxes in an hoa. The mail person stopped delivering mail because they were getting shocked. The light poles were fed from buried rmc conduit that was rotted away with no egc. I was belittled because my suggested fix was to replace all the conduit and install a egc. Boss sent someone else out to drive ground rods😕

    • @crissd8283
      @crissd8283 2 роки тому +2

      This doesn't surprise me. Many electricians are obsessed with worthless ground rods. I hate how stupid some electricians are.

    • @adamdnewman
      @adamdnewman 2 роки тому +1

      @@crissd8283 Not just the electricians plenty of other trades and inspectors with little to no electrical know-how obsessed also!

    • @brianhouse5983
      @brianhouse5983 5 місяців тому

      Your story is one of many. We have to keep educationg those that will listen. Eventually all of the "Electrosaurs" will be extinct and we won't have these issues.

  • @rb8049
    @rb8049 Рік тому +2

    Ground rods serve two purposes. 1. To attempt to bring the EGC/metal/neutral to the potential of the local Earth. 2. Provide a path to Earth for lightning. It is not a means to trip circuit breakers.

  • @royamberg9177
    @royamberg9177 2 роки тому +2

    Seen lightning hit communication tower with 3 4/0 ground wires going to ground field. Even the guy wires that were hooked to ground field smoke. To protect from lightning is very difficult the only thing that helps is the whole thing went high at one time if that's the right terminology. So minimal damage took place

  • @jimmceachern8967
    @jimmceachern8967 Рік тому

    You said in this video that the portable generator did not need a ground rod but if your generator is a bonded neutral generator and providing back up power to a residential house with a switched neutral transfer switch you would then need a ground rod.

  • @bigmikeh5827
    @bigmikeh5827 2 роки тому

    Just shared this with several of my graduates as a reminder.

  • @vince6829
    @vince6829 4 місяці тому +1

    Thank you for sharing your knowledge.

  • @rockyirwin9283
    @rockyirwin9283 2 роки тому +1

    That why when I work on any pole I check it with ncv meter to the metal to see if it is energized

  • @philiphorner31
    @philiphorner31 2 роки тому +2

    I had a 277 parking lot 20 amp breaker pulling 45amps on the circuit.
    Thankfully nobody died.

  • @patthesoundguy
    @patthesoundguy 2 роки тому +4

    It's scary how inspectors here in Nova Scotia require ground rods connected to outdoor event stages... so you have a fault to the stage structure the whole stage becomes live! If a ground rod can't be driven and the stage is adjacent to a large body of water like the ocean or lake they have us throw a ground plate or rod in the water. Scary stuff!!!

    • @adamdnewman
      @adamdnewman 2 роки тому

      Going to literally get killer voltage gradient in fresh water

    • @hgbugalou
      @hgbugalou 2 роки тому +1

      I have heard nightmare electrical situations in this industry. You just added a couple more. I am happy I don't frequent concerts and outdoor events.

  • @mav3kur294
    @mav3kur294 2 роки тому +1

    Hahahaha that example of the fence with the ground rod kills me.

    • @seantreakle1174
      @seantreakle1174 2 роки тому +1

      Mike your energizing the ground if the sprinklers were on you'd really get cooked

    • @seantreakle1174
      @seantreakle1174 2 роки тому +2

      Love the show Mike I've learned so much here thank you man

  • @riccosrbertoletti8004
    @riccosrbertoletti8004 2 роки тому +3

    This reminds me of a argument amongst technicians when i used to install burglar alarms for ADT. 16.5 vac. Transform did not have a grounding conductor. ADT requires we ground the panel. We argued that grounding the panel only made a path for lighting through the panel to the ground. Lighting strikes would often run current through the alarm wires into the panel if it was grounded. Without grounding the panel, the current found a different path. What are your thoughts on this?

    • @jrdn.lauren
      @jrdn.lauren 2 роки тому +1

      The very remote chance that lightning would strike the building vs the possibility of static buildup shocking customers touching the panel or causing interference with electronics. That's my understanding at least

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +2

      Watch this video on why you should NOT ground the fire alarm panel to the earth. ua-cam.com/video/WlnFNTay-9Q/v-deo.html

  • @austinmckinsey8718
    @austinmckinsey8718 Рік тому +1

    In your view, do outdoor metal poles with only POE devices (WAPs/Cameras) fed from building require an EGC? I've watched the entire video and reviewed the code but I can't find a clear answer. Is the pole "likely to be energized" by POE fault? By the letter of the Article 100 definition of "energized", the answer is yes. So do you run a dedicated EGC from the building telecom/electrical ground bar to the pole?

  • @bosvark4x4adventures
    @bosvark4x4adventures Рік тому +1

    Thanks Mike love your content

  • @mav3kur294
    @mav3kur294 2 роки тому +1

    Great video Mike! Thanks for sharing.

  • @zjalva4672
    @zjalva4672 2 роки тому +1

    Would calling it an equipment bonding jumper be used to clear up confusion?

  • @illestofdemall13
    @illestofdemall13 2 роки тому +4

    It's very dangerous when people THINK they know how to do something but really don't.

  • @chronos131
    @chronos131 2 роки тому +1

    Are there any issues installing auxiliary electrodes in addition to having an EGC? The reason I ask is for ground mounted solar array the inspectors always want ground rods installed. Of course we are still running an EGC in addition to the ground rods.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      I have a problem with this practice, watch ua-cam.com/video/WlnFNTay-9Q/v-deo.html and ua-cam.com/video/Ypo99VRxT44/v-deo.html

  • @dandearman2871
    @dandearman2871 2 роки тому +2

    Mike. I'd like to hear your thoughts about grounding drums and containers of flammable liquids and storage cabinets for flammable liquids for protection from fires that could be caused from a static spark?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      That is a totally different concept and there are NFPA standards that address this issue, particularly NFPA 30, Flammable and Combustible Liquids Code.

    • @dandearman2871
      @dandearman2871 2 роки тому

      @@MikeHoltNEC Thanks.

  • @johnkulpowich5260
    @johnkulpowich5260 2 роки тому +1

    Thanks Mike very useful

  • @mahadihasan93
    @mahadihasan93 2 роки тому +1

    If a lightning strikes a pole with effective ground fault current path, what will happen to the cable ensuring effective ground fault path from pole to source. How should we size that cable to ensure the damage don't happen to the cable. What should be the minimum size of that cable considering lightning?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      The National Electrical Code is not a standard that has anything to do with lightning. If lightning struck a pole, then everything that was damaged needs to be simply replaced. Nothing you can do about this, except to provide lightning protection system per NFPA 780 for the pole. Of course that would make no sense.

  • @V21IC
    @V21IC 2 роки тому

    Mike, you're making a lot sense as usually.
    Isn't a concrete slab like an electrode?
    So why do they try to ground a post bonded to a concrete slab?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I don't understand your comment. See ua-cam.com/video/mpgAVE4UwFw/v-deo.html

  • @whoguy4231
    @whoguy4231 2 роки тому

    This is a very tricky subject. The wire bonded to the light pole metal structure providing the fault current return path should theoretically be at ground(0v) voltage. However in practice this may not be the case and again lead to electrocution. Tricky indeed!

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      The earth will be zero volts related to the phase conductors, but that is irrelevent. Please watch my video MikeHolt.com/Fundamentals.

  • @illestofdemall13
    @illestofdemall13 2 роки тому +2

    Some jerk really messed people's heads up by saying "electricity wants to go to ground."

  • @GmdElectric
    @GmdElectric 2 місяці тому

    In the metal chain link fence situation, if an inspector says it needs to be bonded because it is likely to be energized, would it be ok to just take the correct size wire to the EGC, not rods.?

    • @MikeHoltNEC
      @MikeHoltNEC  2 місяці тому

      This fence is not likely to be energized as defined by the NEC, in Article 100. "Conductive material that could become energized because of the failure of electrical insulation or electrical spacing."
      Note: if they had not connected the fence to the metal pole, the young man would not have been electrocuted.

  • @bosque1999
    @bosque1999 2 роки тому +3

    What is the implication for grounding rods at sub-panels that have equipment grounding conductors to the main panel? Thanks

    • @poolsdoc9178
      @poolsdoc9178 2 роки тому

      It doesn’t have to be a grounding rod, any kind of GE(grounding electrode) will work as the one required by the NEC at remote buildings with electric power.It has the same purpose than the one at the service and is among other things to bleed out any kind of induced and dangerous voltages preventing arching fires,damage of equipments and electrocution by voltage accumulation on metal parts.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      No that is not the reason - watch ua-cam.com/video/mpgAVE4UwFw/v-deo.html

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      You my friend are 100% correct!

    • @danielsullivan9865
      @danielsullivan9865 2 роки тому

      @@MikeHoltNEC Why does the code keep changing on grounding electrode separate buildings isolated groundlng conductor versus Grounded Conductor Bonded as a main panel. 2 ungrounded conductors one grounded conductor. Versus 2 ungrounded conductors and one grounded conductor and one Isolated grounding conductor bonded to the grounding electrode? When the utility provider loses its ground from the transformers you’ve got problems either way.Potential difference in grounds becomes apparent water pipes always Stray voltage

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@danielsullivan9865 I have no clue what you just said. There have not been any NEC changes on the practice of 'grounding' for at least the past fifty years I'v been in the electrical trade.

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 роки тому +1

    Nice video!😆
    🥃🥃🍺🍺🍺🎯🏌🏻‍♀️

  • @fishandgameman
    @fishandgameman 2 роки тому

    I see towers with antenna arrays everywhere with grounding electrodes and their respective conductors at the base. Sometimes up to four or more. Cell tower sites have grounding electrodes everywhere with every metal piece of equipment tied together. Maybe it’s only to prevent a difference of potential for worker safety while in the site area. I’ve seen similar sites where the grounding electrode conductors appear to have been purposely removed but still present. I wonder if they have something to do with the radio frequency and it’s proper propagation. There is a mono pole antenna tower I’m familiar with that the terminations are loose enough you can rotate them around by hand.

  • @charletonzimmerman4205
    @charletonzimmerman4205 2 роки тому +1

    Do some research, on conductor, transmission of Energy "WAVES", it is not moving of electrons, inside of wire, its the field surrounding, of conductor, that moves Power. Lightning is air gap, field power, yes that ground rod is required, of 30ft larger metal poles, as in traffic light standards, I Installed a "LOT", of em.

    • @MrMaxyield
      @MrMaxyield 2 роки тому

      First part of your statement is Correct . This video proves it...
      ua-cam.com/video/bHIhgxav9LY/v-deo.html

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Are you saying that we need a ground rod at a metal pole for the electric energy to get to the light for it to illuminate? Are you an electrician in the US?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Are you saying that we need a ground rod at a metal pole for the electric energy to get to the light for it to illuminate? Are you an electrician?

  • @trumanburbank6899
    @trumanburbank6899 2 роки тому +1

    How to protect a light pole from lightning - replace as necessary.

  • @trumanburbank6899
    @trumanburbank6899 2 роки тому

    Hi Mike. I was wondering if the provenance of your name is Overholtzer. You kind of remind me of that side of my family. Thanks. Great video, as always.

  • @georgespangler1517
    @georgespangler1517 2 роки тому

    So your saying the neural is all you need in your home? Code just made me put 2 ground rods over 6 foot apart s house I'm restoring bonded with the neutral

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      The video is about a ground rod at a pole, not a home. Please watch this video - MikeHolt.com/Fundamentals.

  • @onelesho3199
    @onelesho3199 2 роки тому

    Mike I have questions ! Don't we all say that the earth is neutral or it's zero? And if you hit the hot wire with neutral will trip the breaker? So "If we hit the hot wire to ground rode will trip the breaker "?
    Why it didn't trip in your live example?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      Everything you said is 100% false, please watch ua-cam.com/video/mpgAVE4UwFw/v-deo.html

    • @nicnac2400
      @nicnac2400 2 роки тому

      Electricity travels back to the source. When you connect the hot wire to neutral it sends a very large amount of current through the circuit back to the source tripping the breaker

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@nicnac2400 Why would you connect a hot wire to the neutral? What does your statement have to do with the silly practice of grounding a metal pole to the earth (when it's already connected to the earth via the metal bolts)?

  • @krisssilco
    @krisssilco 2 роки тому

    With that video of you putting in that ground rod and the generator, what would you have to do to get hurt. Why didn't you get shocked when you touched the metal of the equipment

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I don't know what video you are describing.

  • @rb8049
    @rb8049 Рік тому

    Add ground rods to provide shortest paths to Earth from conduit that goes to the roof or to poles or elevated antennas. You want lightning to form plasma paths to the Earth. You don’t want lightning wrapping around the house or traveling through your house. Call these lightning grounds if you wish. Extra ground for motors or whatever not required by NEC are absurd.

  • @jamesscholz8338
    @jamesscholz8338 2 роки тому

    Gonna step out on a limb here. Taking the lighting's perspective, i imagine it's goal in life is to connect the clouds to the dirt. If that involves a tree, the aerial service of a building, the ground rod at the utility pole, the ground rod at the service, a building's wiring or plumbing, or whatever else is conductive enough to get the job done, it will use. Of course the rebar, the threaded studs, and concrete of a pole light's base functions as a sort of concrete encased electrode. So, I'm guessing here, the auxiliary ground rod MIGHT(purely hypothetical here) help prevent the circuit conductors from getting fried when lightning hits the pole.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      Of course our goal is not to help lightning get to the earth... Also a metal pole is already in the earth and doesn't need any additional grounding, but remember grounding is not needed in the first place. See ua-cam.com/video/mpgAVE4UwFw/v-deo.html

  • @danielsullivan9865
    @danielsullivan9865 2 роки тому

    What’s the reason for all the ground rods and ground ring on cell towers. All the ones I inspected were pretty much design the same way

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      That type of grounding has nothing to do with the National Electrical Code. It's purpose is to reduce the difference of potential between metal parts in the even of an lightning strike.

    • @danielsullivan9865
      @danielsullivan9865 2 роки тому

      @@MikeHoltNEC I thought it had to do with noise and interference with signals

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@danielsullivan9865 What do you think 'noise' is? Grounding of a cell tower system has nothing to do with reducing the interference of the signal. It simply is a way to reduce the difference of potential between the metal parts of the cell tower to the earth. If you get any documentation otherwise, please share it with me.

  • @corinnemuir1542
    @corinnemuir1542 2 роки тому +1

    I think mike knows Joe “ a buddy of mine” Rogan

  • @benzaguru4548
    @benzaguru4548 2 роки тому

    Can FMC used in old house consider as effective ground fault current path?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      Read 250.118 and let me know what it says please.

    • @benzaguru4548
      @benzaguru4548 2 роки тому +1

      @@MikeHoltNEC yes I read the article. OCPD should be less than. 20 A. But 250.118 5 d got me confused. It said combing length of conduict not exceed 6 feet. So that mean FMC used in old house ran mor than 6 feet are not consider as effective ground fault current path?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@benzaguru4548 If the NEC says a maximum of six feet, then clearly anything more is a violation. What about this is confusing?

    • @benzaguru4548
      @benzaguru4548 2 роки тому

      @@MikeHoltNECthanku. not any more. That's why we need seperate equipment grounding conductor in FMC that used in old house. All those FMC are ran longer than 6 feet. So we can not use three prong receptacle without seperate equipment ground conductor.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@benzaguru4548 You my friend are sounding like a Code expert. Congratulations. But when replacing receptacle, they don't need an EGC, see 406.4 on the rules for replacing receptacles, and the GFCI option.

  • @musajarjusey6132
    @musajarjusey6132 2 роки тому

    Sir, how can I get the books and the price?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Call our office at 888.632.2633, they will take care of you and get you the best price. Thanks, we look forward to helping you!

  • @bob847vid
    @bob847vid 2 роки тому

    Do you have to ground a roof mounted over the air TV antenna? If you do, do you have to ground it near the main panel existing grounding, or can you ground it near where that antenna is separately?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Please watch this video for your answer.

    • @bob847vid
      @bob847vid 2 роки тому

      @@MikeHoltNEC I always watch videos before I comment. So either I’m not getting it, or it’s not covered.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@bob847vid I understand, please watch this video and let me know if you now 'get it.' ua-cam.com/video/mpgAVE4UwFw/v-deo.html

    • @bob847vid
      @bob847vid 2 роки тому

      @@MikeHoltNEC so following the video which I watched before but watched again thinking about this particular application, I’m assuming we treat the TV antenna like a solar array on the roof. In that case no separate earth grounding rod should be installed. I still don’t know if a the antenna mast or coax cable shielding should be attached to any grounding though? Should
      It run to the existing grounding rod at the service panel?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@bob847vid This video is about why the grounding of a metal pole serves no purpose and that we need an equipment grounding conductor to the metal pole to clear a ground fault. Questions related to TV and satilite antennas - Watch ua-cam.com/video/cwB9xd-CzTU/v-deo.html, questions related to Solar - watch ua-cam.com/video/NkDYphpg8sM/v-deo.html and ua-cam.com/video/Ypo99VRxT44/v-deo.html

  • @ForensicCats
    @ForensicCats 2 роки тому

    Great job Mike... I hope these ''old'' engineers wake up...

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +1

      They are dinosaurs, we'll need to wait until they and others move one...

    • @ForensicCats
      @ForensicCats 2 роки тому

      @@MikeHoltNEC , thank you Mike, your knowledge is so valuable and yet, people watch your content and do not fight back... Perhaps, the contract specs do call for those ''details'' but, the contractor could push liability back -- simple, reference the ''unsafe condition'' and ask for another review addressing the ''path'' that may be created by using this ''extra bonding''...
      Mike, I recall your video; the water and the military guy... it was interesting...
      I recall, turning on water and putting an electrical meter in the ''hot leg'' and the the leg in the water flow... yes, I was able to get a volt reading (of course)...
      Again, thank you for your eduction.

  • @0786RICARDO
    @0786RICARDO 2 роки тому

    Shouldn't it be bond fault then?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Yea... but the NEC uses the term 'ground fault' so we are stuck with that term.

    • @0786RICARDO
      @0786RICARDO 2 роки тому

      @@MikeHoltNEC what would be the right denomination? Neutral bonding mass fault or something of the sort?

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@0786RICARDO Since all my work is related to the National Electrical Code, the proper term is 'ground fault' in accordance with Article 100 Definitions.

  • @sts242
    @sts242 4 місяці тому

    If lightning hits a pole with a ground rod it will glass the rod making it unaffective in the future.

    • @MikeHoltNEC
      @MikeHoltNEC  4 місяці тому

      That is possible - www.rakov.ece.ufl.edu/Gas.html

  • @ronaldkovacs7080
    @ronaldkovacs7080 2 роки тому

    I believe “Mythbusters” tried the male dog thing, except it was a person and the third rail of a subway. Could get it to happen.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      That episode has nothing related to the discussion of opening the circuit protection device by using the earth.

  • @alldayjack4830
    @alldayjack4830 2 роки тому

    It seems to me that installing a ground rod at a sub panel in a shed is begging for a lighting strike at a nearby tree to travel from the tree roots,to the ground rod, to the equipment grounding conductor in the sub panel, bringing it to the main service panel in the house. WHY ?
    What purpose is it serving at the shed?
    Probably, the reason the designers and contractors spec and use ground rods at these locations are LAWYERS.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      Please watch this video - ua-cam.com/video/mpgAVE4UwFw/v-deo.html

  • @nicnac2400
    @nicnac2400 2 роки тому

    Could ground rods at light poles help protect from lighting strikes affecting poles down stream? It would obviously not stop it in its tracks but with the high impedance down stream for the electrical system for the high energy pulse of lighting i would imagine it would at least have a chance at saving down stream light poles.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому +2

      Nope. When lightning hits the first pole, it simply destroys the light fixture, and not likely to damage the copper wire to the fixture. So it's not going to damage the wire to different pole.

  • @jeanious2009
    @jeanious2009 5 місяців тому

    It’s in the architectural drawings, engineer asks for those stupid ass ground rods on those light poles or near machinery.

    • @MikeHoltNEC
      @MikeHoltNEC  5 місяців тому

      Yes, but some inspectors require even if not on the plans and others require the plans to include this design. How sad...

  • @midnightwatchman1
    @midnightwatchman1 2 роки тому

    the grounding is that it is not really taught anywhere even in university

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I know, please watch ua-cam.com/video/mpgAVE4UwFw/v-deo.html

  • @warn3535
    @warn3535 2 роки тому

    Dr Phil? Is that you?

  • @tfun101
    @tfun101 2 роки тому

    11:32 is literally the dumbest thing I’ve ever seen. 🤣

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      The sad thing is that this is 'reality.'

  • @midnightwatchman1
    @midnightwatchman1 2 роки тому

    great presentation. lol solar DC systems are much easier it is much more difficult to design and implement AC systems. I remember designing a synchronous generator for a power station that was my most difficult class in electrical engineering in college

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      What, you watch a video about ground rods and you don't think I'm that smart to do Solar? When you get a chance, visit MikeHolt.com/Solar, it contains the books and videos that I produced on this topic...

    • @midnightwatchman1
      @midnightwatchman1 2 роки тому

      @@MikeHoltNEC sorry I mistyped. I was not talking about you specifically. I was really saying AC systems are much difficult than DC solar systems

    • @midnightwatchman1
      @midnightwatchman1 2 роки тому +1

      @@MikeHoltNEC I learned all my grounding know from you actually

  • @voltmanip
    @voltmanip 5 місяців тому

    mike thats a globe ????????????????

  • @skinlab4239
    @skinlab4239 2 роки тому

    I'm going to assume that you've never been in Coral Gables or Florida period. It's sand....

    • @mikeholt9781
      @mikeholt9781 2 роки тому

      What is your point? By the way, I went to Miami High and attended UM in coral gables.

    • @skinlab4239
      @skinlab4239 2 роки тому

      @@mikeholt9781 watch and listen to what you said.

    • @skinlab4239
      @skinlab4239 2 роки тому

      A post driver was in the picture.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      That was not in Coral Gables, that was in Kendal.

  • @slickruler2336
    @slickruler2336 2 роки тому

    Ground rods are for the grid not your safety.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      This is a metal pole, there is no requirement to ground the pole, and there is not requirement to ground the 'grid.' What the heck is a 'grid?' Please watch this video - MikeHolt.com/Fundamentals.

    • @slickruler2336
      @slickruler2336 2 роки тому

      @@MikeHoltNEC what’s the point of a ground rod ? It’s not to keep you safe and it doesn’t disperse enough energy to make a bit of difference on a home that has a surge. Now if you have a couple hundred grounding rods on the homes connected to the the POWER GRID !!! It will make a difference it’s only to protect the power grid. So if you think you need an extra grounding rod on your home you better call an electrician that knows wth he’s talking about to find the lose or broken common or ground that’s causing your appliance to become electrified. Let’s see why would they want or need a grounded metal pole on their grid ? Hmm 🤔 probably because they need it to divert a surge.

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      @@slickruler2336 Grounding of the metal pole does not assist in diverting a surge, whatever that means. Please watch MikeHolt.com/Fundamentals

  • @coldfinger459sub0
    @coldfinger459sub0 2 роки тому

    Really love the content of the videos it’s excellent.
    But the room Echo picked up by the microphone is so much trying to listen to the video on a phone in a mobile location makes it inAudible .
    Turning up the sound to maximum sound volume just trying to listen to the word content with any background noise in the listeners area still cannot pick up all the words meaning in contacts.
    Still great content listen to all your videos just have to go home and listen to this one in a dead silent room on a larger speaker system

    • @MikeHoltNEC
      @MikeHoltNEC  2 роки тому

      I messed up the audio (dead battery), so I had to go with what I had. Sorry,.