Autonics Tutorial : How to troubleshoot temperature controller

Поділитися
Вставка
  • Опубліковано 2 січ 2025

КОМЕНТАРІ • 8

  • @susususu3878
    @susususu3878 Рік тому

    it has been worked without any problem until now, but it suddenly occurs "oPEn. what's the problem?

    • @AutonicsCorp
      @AutonicsCorp  Рік тому

      [oPEn] means sensor disconnection. Please check the sensor connection status again. Also, the input sensor specifications may have changed. Please check [In-t] in parameter 3 group. 00:50

  • @Chigz_geey
    @Chigz_geey 11 місяців тому

    Set value temperature is 136. Process temperature rises very slowly and gets stuck at 112 . What might be the problem

    • @AutonicsCorp
      @AutonicsCorp  10 місяців тому

      First, if you tell us the model name of the product you are using, we can give you a more accurate solution.
      Second, please use the Auto-tuning function of the temperature controller.
      This is a function that calculates a PID value optimized for the environment in which it is used.
      Third, the heater performance itself may be lacking.
      Check whether the temperature does not rise even though the front OUT indicator is ON.
      If this is the reason, the heater may need to be replaced.

  • @MusclePumpp
    @MusclePumpp Рік тому

    tengo un error se queda en OPEN

    • @AutonicsCorp
      @AutonicsCorp  Рік тому

      Si el sensor de temperatura no está conectado o si el tipo de sensor de temperatura no coincide, se mostrará "[oPEn]".
      Por favor, conecte el sensor de temperatura y configure el tipo de sensor de entrada del grupo de parámetros 3 como [in-t], de acuerdo con el tipo de sensor de temperatura utilizado.

  • @bagusdwip227
    @bagusdwip227 Рік тому

    Why out XXXX

    • @AutonicsCorp
      @AutonicsCorp  Рік тому

      Sorry. Can I get a more detailed information about XXXX?